99-55507. CFR Correction  

  • [Federal Register Volume 64, Number 22 (Wednesday, February 3, 1999)]
    [Rules and Regulations]
    [Pages 5188-5189]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 99-55507]
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    ENVIRONMENTAL PROTECTION AGENCY
    
    Recommended Test Methods for State Implementation Plans
    
    40 CFR Part 51
    
    
    CFR Correction
    
        In Title 40 of the Code of Federal Regulations, parts 50 to 51, 
    revised as of July 1, 1998, the text appearing on page 345 duplicates 
    the text on page 344 and should be removed. As corrected the text on 
    page 345 should read as follows:
    * * * * *
    high level of precision and accuracy for the purposes of this test. 
    This method is not meant to replace the calibration requirements of 
    test methods. In addition to the requirements in this method, all 
    the calibration requirements of the applicable test method must also 
    be met.
        3.2.1 Prepare the gas dilution system according to the 
    manufacturer's instructions. Using the high-level supply gas, 
    prepare, at a minimum, two dilutions within the range of each 
    dilution device utilized in the dilution system (unless, as in 
    critical orifice systems, each dilution device is used to make only 
    one dilution; in that case, prepare one dilution for each dilution 
    device). Dilution device in this method refers to each mass flow 
    controller, critical orifice, capillary tube, positive displacement 
    pump, or any other device which is used to achieve gas dilution.
        3.2.2 Calculate the predicted concentration for each of the 
    dilutions based on the flow rates through the gas dilution system 
    (or the dilution ratios) and the certified concentration of the 
    high-level supply gas.
        3.2.3 Introduce each of the dilutions from Section 3.2.1 into 
    the analyzer or monitor one at a time and determine the instrument 
    response for each of the dilutions.
        3.2.4 Repeat the procedure in Section 3.2.3 two times, i.e., 
    until three injections are made at each dilution level. Calculate 
    the average instrument response for each triplicate injection at 
    each dilution level. No single injection shall differ by more than 
    2 percent from the average instrument response for that 
    dilution.
        3.2.5 For each level of dilution, calculate the difference 
    between the average concentration output recorded by the analyzer 
    and the predicted concentration calculated in Section 3.2.2. The 
    average concentration output from the analyzer shall be within 
    2 percent of the predicted value.
        3.2.6 Introduce the mid-level supply gas directly into the 
    analyzer, bypassing the gas dilution system. Repeat the procedure 
    twice more, for a total of three mid-level supply gas injections. 
    Calculate the average analyzer output concentration for the mid-
    level supply gas. The difference between the certified concentration 
    of the mid-level supply gas and the average instrument response 
    shall be within 2 percent.
        3.3 If the gas dilution system meets the criteria listed in 
    Section 3.2, the gas dilution system may be used throughout that 
    field test. If the gas dilution system fails any of the criteria 
    listed in Section 3.2, and the tester corrects the problem with the 
    gas dilution system, the procedure in Section 3.2 must be repeated 
    in its entirety and all the criteria in Section 3.2 must be met in 
    order for the gas dilution system to be utilized in the test.
    
    4. References
    
        1. ``EPA Traceability Protocol for Assay and Certification of 
    Gaseous Calibration Standards,'' EPA-600/R93/224, Revised September 
    1993.
    
    [55 FR 14249, Apr. 17, 1990; 55 FR 24687, June 18, 1990, as amended 
    at 55 FR 37606, Sept. 12, 1990; 56 FR 6278, Feb. 15, 1991; 56 FR 
    65435, Dec. 17, 1991; 60 FR 28054, May 30, 1995; 62 FR 32502, June 
    16, 1997]
    
    Appendixes N-O [Reserved]
    
    Appendix P to Part 51--Minimum Emission Monitoring Requirements
    
        1.0 Purpose. This appendix P sets forth the minimum requirements 
    for continuous emission monitoring and recording that each State 
    Implementation Plan must include in order to be approved under the 
    provisions of 40 CFR 51.165(b). These requirements include the 
    source categories to be affected; emission monitoring, recording, 
    and reporting requirements for those sources; performance 
    specifications for accuracy, reliability, and durability of 
    acceptable monitoring systems; and techniques to convert emission 
    data to units of the applicable State emission standard. Such data 
    must be reported to the State as an indication of whether proper 
    maintenance and operating procedures are being utilized by source 
    operators to maintain emission levels at or below emission 
    standards. Such data may be used directly or indirectly for 
    compliance determination or any other purpose deemed appropriate by 
    the State. Though the monitoring requirements are specified in 
    detail, States are given some flexibility to resolve difficulties 
    that may arise during the implementation of these regulations.
        1.1 Applicability. The State plan shall require the owner or 
    operator of an emission source in a category listed in this appendix 
    to: (1) Install, calibrate, operate, and maintain all monitoring 
    equipment necessary for continuously monitoring the pollutants 
    specified in this appendix for the applicable source category; and 
    (2) complete the installation and performance tests of such 
    equipment and begin monitoring and recording within 18 months of 
    plan approval or promulgation. The source categories and the 
    respective monitoring requirements are listed below.
        1.1.1 Fossil fuel-fired steam generators, as specified in 
    paragraph 2.1 of this appendix,
    
    [[Page 5189]]
    
    shall be monitored for opacity, nitrogen oxides emissions, sulfur 
    dioxide emissions, and oxygen or carbon dioxide.
        1.1.2 Fluid bed catalytic cracking unit catalyst regenerators, 
    as specified in paragraph 2.4 of this appendix, shall be monitored 
    for opacity.
    * * * * *
    
    [FR Doc. 99-55507 Filed 2-2-99; 8:45 am]
    BILLING CODE 1505-01-D
    
    
    

Document Information

Published:
02/03/1999
Department:
Environmental Protection Agency
Entry Type:
Rule
Document Number:
99-55507
Pages:
5188-5189 (2 pages)
PDF File:
99-55507.pdf
CFR: (1)
40 CFR 51