98-6010. Central Sprinkler Corporation and Central Sprinkler Co., Complaint  

  • [Federal Register Volume 63, Number 46 (Tuesday, March 10, 1998)]
    [Notices]
    [Pages 11656-11658]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 98-6010]
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    CONSUMER PRODUCT SAFETY COMMISSION
    
    [CPSC Docket No. 98-2]
    
    
    Central Sprinkler Corporation and Central Sprinkler Co., 
    Complaint
    
    AGENCY: Consumer Product Safety Commission.
    
    ACTION: Publication of a complaint under the Consumer Product Safety 
    Act.
    
    -----------------------------------------------------------------------
    
    SUMMARY: Under Provisions of its Rules of Practice for Adjudicative 
    proceedings (16 CFR Part 1025), the Consumer Product Safety Commission 
    must publish in the Federal Register Complaints which it issues. 
    Published below is a Complaint in the matter of Central Sprinkler 
    Corporation and Central Sprinkler Company.
    
    SUPPLEMENTARY INFORMATION: The text of the Complaint appears below.
    
        Dated: March 4, 1998.
    Sadye E. Dunn,
    Secretary.
    
    Complaint
    
        In the Matter of: Central Sprinkler Corp., a Corporation, 451 
    North Cannon Avenue Lansdale, PA 19446 and Central Sprinkler Co., a 
    Corporation, 451 North Cannon Avenue Lansdale, PA 19446, 
    Respondents.
    
    Nature of Proceedings
    
        1. This is an administrative proceeding pursuant to Section 15 of 
    the Consumer Product Safety Act (CPSA), 15 U.S.C. 2064, for public 
    notification and remedial action to protect the public from substantial 
    risk of injury presented by a brand of automatic fire sprinklers. This 
    proceeding is governed by the Rules of Practice for Adjudicative
    
    [[Page 11657]]
    
    Proceedings before the Consumer Product Safety Commission, 16 CFR Part 
    1025.
    
    Jurisdiction
    
        2. This proceeding is instituted pursuant to the authority 
    contained in sections 15(c), (d), and (f) of the CPSA, 15 U.S.C. 2064 
    (c), (d), and (f).
    
    Parties
    
        3. Complaint Counsel is the staff of the Legal Division of the 
    Office of Compliance of the U.S. Consumer Product Safety Commission, an 
    independent regulatory commission established by Section 4 of the CPSA. 
    15 U.S.C. 2053.
        4. Respondents Central Sprinkler Corporation and Central Sprinkler 
    Company (``the Central entities'') are Pennsylvania corporations with 
    their principal place of business located at 451 North Cannon Avenue, 
    Lansdale, Pennsylvania 19446.
        5. The Central entities are ``manufacturers'' of consumer products 
    distributed in commerce pursuant to 15 U.S.C. 2052(a)(4).
    
    The Consumer Product
    
        6. The ``Omega'' series automatic fire sprinklers (``Omega'' or 
    ``Omegas'') is a line of automatic fire sprinklers manufactured by the 
    Central entities and designed to suppress and/or extinguish fire. 
    Omegas are installed in homes, apartment buildings, schools, nursing 
    homes, and athletic facilities, among other places. Omegas are 
    ``consumer products'' under 15 U.S.C. 2052(a)(1). There are various 
    Omega models, including, but not limited to: C-1; C-1A; C-1A PRO; C-1A 
    PRO ID; ED-20; EC-20A; EC-20 AID; HEC-12; HEC-12 ID; HEC-12 PRO; HEC-
    12A PRO; HEC-12 RES; HEC-20; HEC-20 ID; R-1; R-1A; R-1M; AC; M; and 
    Flow Control. Approximately ten million Omegas, which Respondents have 
    produced and sold since approximately 1982, are in service in the 
    United States.
    
    Defect or Defects
    
        7. Paragraphs 1 through 6 are incorporated as though set forth in 
    full text.
        8. Omegas are designed to perform in accordance with Underwriters 
    Laboratories, Inc.'s Standard for Safety UL 199 (``Standard for 
    Automatic Sprinklers for Fire Protection Service''), and National Fire 
    Protection Association (``NEPA'') Standard 13, when exposed to certain 
    temperatures.
        9. At the Omega's triggering temperature, a fusible pellet is 
    supposed to melt, causing a plunger to release, which in turn frees 
    several ball bearings from a retaining groove. With the aid of two 
    springs, the plunger housing is then supposed to release. When the 
    Omega is connected to a sprinkler system, water is then supposed to be 
    released in a particular spray pattern. The plunger housing is sealed 
    with an o-ring.
        10. Omegas do not and will not function in a significant percentage 
    of instances. Because of this failure to operate, Omegas are defective 
    pursuant to 15 U.S.C. 2064(a)(2) and 16 CFR 1115.4.
    
    Substantial Risk of Injury
    
        11. Paragraphs 1 through 10 are incorporated as though set forth in 
    full text.
        12. When the Omega fails to activate when exposed to heat from a 
    fire, the sprinkler fails to suppress or extinguish the fire.
        13. Failure of the Omega to function exposes the public to bodily 
    injury and/or death.
        14. All of the approximately 10 million Omegas, manufactured from 
    1982 through the present and sold to, used or enjoyed by the public, 
    could fail to function as the result of the defect referenced above. 
    Omegas are likely to fail in fire situations, and members of the public 
    may suffer bodily injury and/or death as a result.
        15. The defect or defects in the Omegas create a substantial risk 
    of injury to the public within the meaning of section 15(a)(2) of the 
    CPSA, 15 U.S.C. 2064(a)(2).
        16. Omegas present a substantial product hazard as described in 
    sections 15(a)(2), (c) and (d) of the CPSA, 15 U.S.C. 2064(a)(2), (c) 
    and (d), and action under these provisions in the public interest.
    
    Relief Sought
    
        Wherefore, in the public interest, Complaint Counsel requests that 
    the Commission:
        A. Determine that Respondents' Omega presents a ``substantial 
    product hazard'' within the meaning of section 15 of the CPSA, 15 
    U.S.C. 2064.
        B. Determine that public notification under section 15(c) of the 
    CPSA, 15 U.S.C. 2064(c), is required in order to adequately protect the 
    public from the substantial product hazard presented by Omegas, and 
    order Respondents to:
        (1) Give prompt public notice of the defect in the Omegas, the 
    severe risk of injury they pose to the public, and the available 
    remedies to remove the risk of injury;
        (2) Mail notice to each person who is or has been a manufacturer, 
    distributor or retailer of the Omega;
        (3) Mail notice to every person to whom Respondents know the Omega 
    was delivered or sold; and
        (4) Include in the notice required by (1), (2) and (3) above a 
    complete description of the hazard presented, a warning to have Omegas 
    replaced immediately, and clear instructions for having Omegas replaced 
    by Respondents. The form and content of the notice will be specified by 
    the Commission.
        C. Determine that action under section 15(d) of the CPSA, 15 U.S.C. 
    2064(d) is in the public interest and order Respondents to:
        (1) Cease immediately manufacturing for sale, offering for sale, 
    and distributing in commerce Omega series fire sprinklers;
        (2) Cease requiring ``performance'' testing of Omegas by all 
    building owners as any pre-condition to remedial action;
        (3) Elect to repair all Omegas so they will perform properly; to 
    replace all Omegas with a like or equivalent product which performs 
    properly; or to refund to consumers the purchase price of the Omegas;
        (4) Make no charge to consumers and to reimburse them for any 
    foreseeable expenses incurred in availing themselves of any remedy 
    provided under any order issued in this matter;
        (5) Reimburse distributors and sprinkler contractors for expenses 
    in connection with carrying out any Commission Order issued in this 
    matter, including the costs of removal and replacement;
        (6) Submit a plan satisfactory to the Commission, within ten (10) 
    days of service of the final Order, directing that actions specified in 
    paragraphs B(1) through B(4) and C(1) through C(5) above be taken in a 
    timely manner;
        (7) Keep records of all actions taken to comply with paragraphs 
    C(1) through C(6), above; and supply these records to the Commission, 
    at the Commission's request, for a period of three (3) years after 
    entry of a Final Order issued by the Commission requiring notice and 
    remedial action, for the purpose of monitoring compliance with the 
    Final Order;
        (8) Notify the Commission at least 60 days prior to any change in 
    its business (such as incorporation, dissolution, assignment, sale, or 
    petition for bankruptcy) that results in, or is intended to result in, 
    the emergence of successor ownership, the creation or dissolution of 
    subsidiaries, going out of business, or any other change that might 
    affect its financial or operational ability to comply with the final 
    Order and the
    
    [[Page 11658]]
    
    corrective action plan submitted and approved pursuant to the Order; 
    and
        (9) Take such other and further actions as the Commission deems 
    necessary to protect the public health and safety and to comply with 
    the CPSA.
    
        Dated: March 3, 1998.
    
        Issued by Order of the Commission.
    Alan H. Schoem,
    Assistant Executive Director, U.S. Consumer Product Safety Commission, 
    Office of Compliance, 4330 East West Highway, Bethesda, Maryland 20814, 
    301-504-0621.
    [FR Doc. 98-6010 Filed 3-9-98; 8:45 am]
    BILLING CODE 6355-01-M
    
    
    

Document Information

Published:
03/10/1998
Department:
Consumer Product Safety Commission
Entry Type:
Notice
Action:
Publication of a complaint under the Consumer Product Safety Act.
Document Number:
98-6010
Pages:
11656-11658 (3 pages)
Docket Numbers:
CPSC Docket No. 98-2
PDF File:
98-6010.pdf