99-10493. Union Electric Company; Notice of Consideration of Issuance of Amendment to Facility Operating License and Opportunity for a Hearing  

  • [Federal Register Volume 64, Number 80 (Tuesday, April 27, 1999)]
    [Notices]
    [Pages 22658-22661]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 99-10493]
    
    
    -----------------------------------------------------------------------
    
    NUCLEAR REGULATORY COMMISSION
    
    [Docket No. 50-483]
    
    
    Union Electric Company; Notice of Consideration of Issuance of 
    Amendment to Facility Operating License and Opportunity for a Hearing
    
        The U.S. Nuclear Regulatory Commission (the Commission) is 
    considering issuance of an amendment to Facility Operating License No. 
    NPF-30, issued to the Union Electric Company (UE or the licensee), for 
    operation of the Callaway Plant, Unit 1 (CW), located in Callaway 
    County, Missouri.
        The initial notice of consideration of issuance of amendment to 
    facility operating license and opportunity for hearing was originally 
    published in the Federal Register (63 FR 53468) on October 5, 1998. The 
    information included in the supplemental letters indicates that the 
    original notice, that included 14 proposed beyond-scope issues (BSIs) 
    to the Improved Technical Specifications (ITS) conversion, needs to be 
    expanded (to add 17 new BSIs) and revised (to delete 7 previous BSIs) 
    to include a total of 24 BSIs. This notice supersedes the previous 
    notice.
        The proposed amendment, requested by the licensee in a letter dated 
    May 15, 1997, as supplemented by letters dated June 26, August 4, 
    August 27, September 24, October 21, November 23, November 25, December 
    11 and December 22, 1998, and February 5, March 9, April 7, and April 
    21, 1999, would represent a full conversion from the current Technical 
    Specifications (CTS) to a set of ITS based on NUREG-1431, ``Standard 
    Technical Specifications, Westinghouse Plants,'' Revision 1, dated 
    April 1995 (the STS). NUREG-1431 has been developed by the Commission's 
    staff through working groups composed of both NRC staff members and 
    industry representatives, and has been endorsed by the staff as part of 
    an industry-wide initiative to standardize and improve the Technical 
    Specifications (TS) for nuclear power plants. As part of this 
    submittal, the licensee has applied the criteria contained in the 
    Commission's ``Final Policy Statement on Technical Specification 
    Improvements for Nuclear Power Reactors (Final Policy Statement),'' 
    published in the Federal Register on July 22, 1993 (58 FR 39132), to 
    the CTS, and, using NUREG-1431 as a basis, proposed an ITS for CW. The 
    criteria in the Final Policy Statement were subsequently added to 10 
    CFR 50.36, ``Technical Specifications,'' in a rule change that was 
    published in the Federal Register on July 19, 1995 (60 FR 36953) and 
    became effective on August 18, 1995.
        This conversion is a joint effort in concert with three other 
    utilities: Pacific Gas & Electric Company for Diablo Canyon Power 
    Plant, Units 1 and 2 (Docket Nos. 50-275 and 50-323); TU Electric for 
    Comanche Peak Steam Electric Station, Units 1 and 2 (Docket Nos. 50-445 
    and 50-446); and Wolf Creek Nuclear Operating Corporation for Wolf 
    Creek Generating Station (Docket No. 50-482). This joint effort 
    includes a common methodology for the licensees in marking-up the CTS 
    and NUREG-1431 Specifications, and the NUREG-1431 Bases, that has been 
    accepted by the staff. This includes the convention that, if the words 
    in a CTS specification are not the same as the words in the ITS 
    specification but they mean the same or have the same requirements as 
    the words in the ITS specification, the licensees do not indicate or 
    describe a change to the CTS.
        This common methodology is discussed at the end of Enclosure 2, 
    ``Mark-Up of Current TS''; Enclosure 5a, ``Mark-Up of NUREG-1431 
    Specifications''; and Enclosure 5b, ``Mark-Up of NUREG-1431 Bases,'' 
    for each of the 14 separate ITS sections that were submitted with the 
    licensee's application. For each of the 14 ITS sections, there is also 
    the following: Enclosure 1, the cross reference table, sorted by CTS 
    and ITS Specifications; Enclosure 3, the description of the changes to 
    the CTS section and the comparison table showing which plants (of the 
    four licensees in the joint effort) that each change applies to; 
    Enclosure 4, the no significant hazards consideration (NSHC) of 10 CFR 
    50.91 for the changes to the CTS with generic NSHCs for administrative, 
    more restrictive, relocation, and moving-out-of-CTS changes, and 
    individual NSHCs for less restrictive changes and with the organization 
    of the NSHC evaluation discussed in the beginning of the enclosure; and 
    Enclosure 6, the descriptions of the differences from NUREG-1431 
    specifications and the comparison table showing which plants (of the 
    four licensees in the joint effort) that each difference applies to. 
    Another convention of the common methodology is that the technical 
    justifications for the less restrictive changes are included in the 
    NSHCs.
        The licensee has categorized the proposed changes to the CTS into 
    four general groupings. These groupings are characterized as 
    administrative changes, relocated changes, more restrictive changes and 
    less restrictive changes.
        Administrative changes are those that involve restructuring, 
    renumbering, rewording, interpretation and complex rearranging of 
    requirements and other changes not affecting technical content or 
    substantially revising an operating requirement. The reformatting, 
    renumbering and rewording process reflects the attributes of NUREG-1431 
    and does not involve technical changes to the existing TS. The proposed 
    changes include (a) providing the appropriate numbers, etc., for NUREG-
    1431 bracketed information (information that must be supplied on a 
    plant-specific basis, and which may change from plant to plant), (b) 
    identifying plant-specific wording for system names, etc., and (c) 
    changing NUREG-1431 section wording to conform to existing licensee 
    practices. Such changes are administrative in nature and do not impact 
    initiators of analyzed events or assumed mitigation of accident or 
    transient events.
        Relocated changes are those involving relocation of requirements 
    and surveillances for structures, systems, components, or variables 
    that do not meet the criteria for inclusion in the TS. Relocated 
    changes are those current TS requirements that do not satisfy or fall 
    within any of the four criteria specified in the Commission's policy 
    statement and may be relocated to appropriate licensee-controlled 
    documents.
        The licensee's application of the screening criteria is described 
    in Attachment 2 to its May 15, 1997, submittal, which is entitled, 
    ``General Description and Assessment.'' The affected structures, 
    systems, components or variables are not assumed to be initiators of 
    analyzed events and are not assumed to mitigate accident or transient 
    events. The requirements and surveillances for these affected 
    structures, systems, components, or variables will be relocated from 
    the TS to administratively controlled documents such as the quality 
    assurance program,
    
    [[Page 22659]]
    
    the Final Safety Analysis Report (FSAR), the ITS Bases, the Technical 
    Requirements Manual (TRM) that is incorporated by reference in the 
    FSAR, the Core Operating Limits Report (COLR), the Offsite Dose 
    Calculation Manual (ODCM), the Inservice Testing (IST) Program, or 
    other licensee-controlled documents. Changes made to these documents 
    will be made pursuant to 10 CFR 50.59 or other appropriate control 
    mechanisms, and may be made without prior NRC review and approval. In 
    addition, the affected structures, systems, components, or variables 
    are addressed in existing surveillance procedures that are also subject 
    to 10 CFR 50.59. These proposed changes will not impose or eliminate 
    any requirements.
        More restrictive changes are those involving more stringent 
    requirements compared to the CTS for operation of the facility. These 
    more stringent requirements do not result in operation that will alter 
    assumptions relative to the mitigation of an accident or transient 
    event. The more restrictive requirements will not alter the operation 
    of process variables, structures, systems, and components described in 
    the safety analyses. For each requirement in the CTS that is more 
    restrictive than the corresponding requirement in NUREG-1431 that the 
    licensee proposes to retain in the ITS, they have provided an 
    explanation of why they have concluded that retaining the more 
    restrictive requirement is desirable to ensure safe operation of the 
    facility because of specific design features of the plant.
        Less restrictive changes are those where CTS requirements are 
    relaxed or eliminated, or new plant operational flexibility is 
    provided. The more significant ``less restrictive'' requirements are 
    justified on a case-by-case basis. When requirements have been shown to 
    provide little or no safety benefit, their removal from the TSs may be 
    appropriate. In most cases, relaxations previously granted to 
    individual plants on a plant-specific basis were the result of (a) 
    generic NRC actions, (b) new NRC staff positions that have evolved from 
    technological advancements and operating experience, or (c) resolution 
    of the Owners Groups' comments on the Improved Standard Technical 
    Specifications. Generic relaxations contained in NUREG-1431 were 
    reviewed by the staff and found to be acceptable because they are 
    consistent with current licensing practices and NRC regulations. The 
    licensee's design will be reviewed to determine if the specific design 
    basis and licensing basis are consistent with the technical basis for 
    the model requirements in NUREG-1431, thus providing a basis for these 
    revised TS, or if relaxation of the requirements in the current TS is 
    warranted based on the justification provided by the licensee.
        These administrative, relocated, more restrictive, and less 
    restrictive changes to the requirements of the CTS do not result in 
    operations that will alter assumptions relative to mitigation of an 
    analyzed accident or transient event.
        In addition to the proposed changes solely involving the 
    conversion, there are also changes proposed that are different than the 
    requirements in both the CTS and the improved Standard Technical 
    Specifications (NUREG-1431). The first 7 beyond-scope issues (BSIs) 
    were included in the previous (superceded) notice and still apply to 
    the conversion, however there are 17 additional BSIs. The additional 
    BSIs are discussed in the licensee's response to requests for 
    additional information (RAIs) from the NRC staff. These proposed BSIs 
    to the ITS conversion are as follows:
        1. ITS Surveillance Requirement (SR) 3.2.1.1 and SR 3.2.1.2--add 
    frequency of once within 24 hours to CTS 4.2.2.2.d for verifying the 
    axial heat flux hot channel factor is within limits after achieving 
    equilibrium conditions.
        2. ITS Limiting Condition for Operation (LCO) 3.3.9--revise Action 
    5.b of CTS Table 3.3-1 to increase the verification interval for 
    unborated water source isolation valve position from 14 days to 31 
    days.
        3. ITS LCO 3.4.7 and SRs 3.4.5.2, 3.4.6.2, and 3.4.7.2--revise 
    steam generator (SG) level requirements from 10% wide range to 4% 
    narrow range in CTS SRs 4.4.1.2.2 and 4.4.1.3.2 for Modes 3, 4, and 5 
    to ensure SG tubes are covered and provide an adequate heat sink.
        4. ITS LCO 3.4.1.2--revise applicability note to CTS LCO 3.4.9.3 to 
    allow a longer time, up to 1 hour, for both centrifugal charging pumps 
    to be capable of injecting into the reactor coolant system.
        5. ITS LCO 3.7.15--changes reference for the spent fuel pool level 
    from that above top of fuel stored in racks to that above the top of 
    racks in CTS LCO 3.9.11.
        6. ITS 5.6.5.a--adds the refueling boron concentration to the core 
    operating limits report in CTS 6.9.1.9.
        7. ITS 5.7.1--changes limits for high radiation areas in CTS 6.12.1 
    to reflect the requirements of revised 10 CFR Part 20.
        8. Change 1-34-LS-2 (ITS Table 1.1-1), question 1.1-9, response 
    letter dated April 21, 1999. The proposed change adds notes to CTS 
    Table 1.2 to identify the number of reactor vessel head closure bolts 
    required to be fully tensioned for Modes 4 and 5. A Note is also 
    proposed to address Mode 6 bolt requirements.
        9. Change 1-7-LS-3 (ITS Table 3.3-1), question 3.3-107, response 
    letter dated November 25, 1998. The proposed change to CTS Table 3.3-1 
    would (1) extend the completion time for CTS Action 3.b from no time 
    specified to 24 hours for channel restoration or changing the power 
    level to either below P-6 or above P-10, (2) change the applicable 
    modes and delete CTS Action 3.a because it is now outside the revised 
    intermediate range neutron flux channel applicability, and (3) add a 
    less restrictive new action that requires immediate suspension of 
    operations involving positive reactivity additions and a power 
    reduction below P-6 within two hours, but no longer requires a 
    reduction to Mode 3.
        10. Change 1-22-M (ITS SR 3.3.1.8), question 3.3-49, response 
    letter dated November 25, 1998. The proposed change would add quarterly 
    channel operational tests (COTs) to CTS Table 4.3-1 for the power range 
    neutron flux-low, intermediate range neutron flux, and source range 
    neutron flux trip functions. The CTS only require a COT prior to 
    startup for these functions. New Note 19 (which is from the STS) would 
    be added to require that the new quarterly COT be performed within 12 
    hours after reducing power below P-10 for the power range and 
    intermediate range (P-10 is the dividing point marking the 
    applicability for these trip functions), if not performed in the 
    previous 92 days. New Note 20 (which is from the STS), would be added 
    to state that the P-6 and P-10 interlocks are verified to be in their 
    required state during all COTs on the power range neutron flux-low and 
    intermediate range neutron flux trip functions.
        11. Change 1-46-M, (ITS Table 3.3.1-1 and 3.3.2-1), question 3.3-
    04, response letter dated March 9, 1999. The proposed change would 
    revise CTS Table 3.3-1 Action 13 and CTS Table 3.3-3 Action 36 to 
    require an inoperable SG low-low level (normal containment environment) 
    instrument channel be placed in the tripped condition within 6 hours. 
    The option to place the associated environmental allowance monitor 
    (EAM) channels in trip would be deleted.
        12. Change 4-09-LS-36, (ITS SR 3.4.11.1), question 3.4.11-4, 
    response letter dated September 24, 1998. The proposed change would 
    limit the CTS SR 4.4.4.2 requirement to perform the
    
    [[Page 22660]]
    
    92-day surveillance of the pressurizer power operated relief (PORV) 
    block valves so that it is not required to be performed if the block 
    valve is closed to meet CTS LCO 3.4.4 Action a. A note is also proposed 
    to be added to action d to state that the Action does not apply if the 
    block valve is inoperable solely to satisfy CTS LCO 3.4.4 Action b or 
    c.
        13. Change 10-20-LS-39 (ITS LCO 3.7.10), question 3.7.10-14, 
    response letter dated October 21, 1998. The proposed change would add 
    an action to CTS LCO 3.7.6 for ventilation system pressure envelope 
    degradation that allows 24 hours to restore the control room pressure 
    envelope through repairs before requiring the unit to perform an 
    orderly shutdown. The new action has a longer allowed outage time than 
    LCO 3.0.4 which the CTS would require to be entered immediately. The 
    change would recognize that the ventilation trains associated with the 
    pressure envelope would still be operable.
        14. Change 2-25-LS-23 (ITS SR 3.8.4.7 and SR 3.8.4.8), the change, 
    proposed in the amendment application, would allow substitution of a 
    modified performance discharge test for the battery service test in CTS 
    SR 4.8.2.1.e.
        15. Change 1-09-A (ITS 5.0), question Q5.2-1, response letter dated 
    September 24, 1998. The proposed change would replace CTS 6.2.2.e 
    requirements concerning overtime with a reference to administrative 
    procedures for the control of working hours.
        16. Change 1-15-A (ITS 5.2.2.f), question Q5.2-1, response letter 
    dated September 24, 1998. The proposed change would revise CTS 6.2.2.g 
    to eliminate the title of Shift Technical Advisor (STA). The 
    engineering expertise would be maintained on shift, but not as a 
    separate individual, as allowed by the Commission's Policy Statement on 
    engineering expertise.
        17. Change 2-17-LS-1 (ITS 5.5.7), question Q5.5-2, response letter 
    dated September 24, 1998. The proposed change would add an allowance to 
    the CTS for the reactor coolant pump flywheel inspection program to 
    permit an exception to the examination requirements specified in CTS SR 
    6.8.5.b (Regulatory position C.b.4 of NRC Regulatory Guide 1.14, 
    ``Reactor Coolant Pump Flywheel Integrity,'' Revision 1.) The exception 
    would allow either an ultrasonic volumetric or surface examination as 
    an acceptable inspection method.
        18. Change 2-18-A (ITS 5.0), question Q5.2-1, response letter dated 
    September 24, 1998. The proposed change would revise the CTS 6.8.4.e.7 
    dose rate limits in the radiological effluents controls program to 
    reflect 10 CFR Part 20 requirements.
        19. Change 2-22-A (ITS 5.5.4.k), question Q5.2-1, response letter 
    dated September 24, 1998. The proposed change would revise the 
    radiological effluents controls program in CTS 6.8.3.e to add 
    clarifying statements denoting that the provisions of CTS 4.0.2 and 
    4.0.3, which allow extensions to surveillance frequencies, are also 
    applicable to these program activities.
        20. Change 3-18-LS-5 (ITS 5.6.4), question Q5.2-1, response letter 
    dated September 24, 1998. The CTS 6.9.1.8 requirement to provide 
    documentation of all challenges to the power operated relief valves 
    (PORVs) and safety valves on the reactor coolant system would be 
    deleted. This would be based on NRC Generic Letter (GL) 97-02, 
    ``Revised Contents in the Monthly Operating Report,'' which reduced the 
    requirements for submitting such information to the NRC. The GL did not 
    include these valves for information to be submitted.
        21. Change 9-14-M (ITS SR 3.4.12.3). The change, proposed in the 
    amendment application, would add a new surveillance requirement to CTS 
    LCO 3.4.9.3 on overpressure protection systems to verify each 
    accumulator is isolated when the accumulator pressure is greater than 
    or equal to the maximum reactor coolant system (RCS) pressure for the 
    existing RCS cold leg temperature allowed by the pressure/temperature 
    limit curves provided in the pressure temperature limit report.
        22. Change 14-09-M (ITS 3.7.16), question 3.7.16-3, response letter 
    dated March 9, 1999. The proposed change would add a new LCO, with 
    actions and surveillance requirements from the ITS, to the CTS for the 
    allowable fuel storage boron concentration. The new specification is 
    based on ITS 3.7.17 with the proposed minimum acceptable boron 
    concentration for the spent fuel storage pool being 2165 ppm boron.
        23. Change 1-15-A (ITS SR 3.3.1.15), question TR-3.3-007, response 
    letter dated December 22, 1998. The proposed change would modify the 
    applicability of the reactor trip on turbine trip function in CTS Table 
    3.3-1 by adding a new footnote (c) stating that this function would 
    only be required to be operable above the P-9 interlock. This is 
    proposed since this function is blocked below the P-9 interlock. The 
    applicability change would also be reflected in the revised trip 
    actuating device operational test (TADOT) requirements for functional 
    unit #16 in CTS Table 4.3-2.
        24. Change 1-30-M (ITS LCO 3.3.9) questions 3.3-119 and 3.3-121, 
    response letter dated April 21, 1999. The proposed change would add a 
    new LCO with actions and SR from the ITS for the boron dilution 
    mitigation system. Additional restrictions not in the CTS would be 
    added to address the requirement that one RCS loop shall be in 
    operation for Modes 2 (below P-6), 3, 4 and 5. This is not included in 
    the CTS or ITS 3.3.9.
        Before issuance of the proposed license amendment, the Commission 
    will have made findings required by the Atomic Energy Act of 1954, as 
    amended (the Act) and the Commission's regulations.
        By May 27, 1999, the licensee may file a request for a hearing with 
    respect to issuance of the amendment to the subject facility operating 
    license and any person whose interest may be affected by this 
    proceeding and who wishes to participate as a party in the proceeding 
    must file a written request for a hearing and a petition for leave to 
    intervene. Requests for a hearing and a petition for leave to intervene 
    shall be filed in accordance with the Commission's ``Rules of Practice 
    for Domestic Licensing Proceedings'' in 10 CFR Part 2. Interested 
    persons should consult a current copy of 10 CFR 2.714 which is 
    available at the Commission's Public Document Room, the Gelman 
    Building, 2120 L Street, NW., Washington, DC, and at the local public 
    document room located at the Elmer Ellis Library, University of 
    Missouri, Columbia, Missouri, 65201. If a request for a hearing or 
    petition for leave to intervene is filed by the above date, the 
    Commission or an Atomic Safety and Licensing Board, designated by the 
    Commission or by the Chairman of the Atomic Safety and Licensing Board 
    Panel, will rule on the request and/or petition; and the Secretary or 
    the designated Atomic Safety and Licensing Board will issue a notice of 
    hearing or an appropriate order.
        As required by 10 CFR 2.714, a petition for leave to intervene 
    shall set forth with particularity the interest of the petitioner in 
    the proceeding, and how that interest may be affected by the results of 
    the proceeding. The petition should specifically explain the reasons 
    why intervention should be permitted with particular reference to the 
    following factors: (1) the nature of the petitioner's right under the 
    Act to be made a party to the proceeding; (2) the nature and extent of 
    the petitioner's property, financial, or other interest in the 
    proceeding; and (3) the possible effect of any order which may be 
    entered in the proceeding on the petitioner's interest. The petition 
    should also identify the specific aspect(s) of the
    
    [[Page 22661]]
    
    subject matter of the proceeding as to which petitioner wishes to 
    intervene. Any person who has filed a petition for leave to intervene 
    or who has been admitted as a party may amend the petition without 
    requesting leave of the Board up to 15 days prior to the first 
    prehearing conference scheduled in the proceeding, but such an amended 
    petition must satisfy the specificity requirements described above.
        Not later than 15 days prior to the first prehearing conference 
    scheduled in the proceeding, a petitioner shall file a supplement to 
    the petition to intervene which must include a list of the contentions 
    which are sought to be litigated in the matter. Each contention must 
    consist of a specific statement of the issue of law or fact to be 
    raised or controverted. In addition, the petitioner shall provide a 
    brief explanation of the bases of the contention and a concise 
    statement of the alleged facts or expert opinion which support the 
    contention and on which the petitioner intends to rely in proving the 
    contention at the hearing. The petitioner must also provide references 
    to those specific sources and documents of which the petitioner is 
    aware and on which the petitioner intends to rely to establish those 
    facts or expert opinion. Petitioner must provide sufficient information 
    to show that a genuine dispute exists with the applicant on a material 
    issue of law or fact. Contentions shall be limited to matters within 
    the scope of the amendment under consideration. The contention must be 
    one which, if proven, would entitle the petitioner to relief. A 
    petitioner who fails to file such a supplement which satisfies these 
    requirements with respect to at least one contention will not be 
    permitted to participate as a party.
        Those permitted to intervene become parties to the proceeding, 
    subject to any limitations in the order granting leave to intervene, 
    and have the opportunity to participate fully in the conduct of the 
    hearing, including the opportunity to present evidence and cross-
    examine witnesses.
        A request for a hearing or a petition for leave to intervene must 
    be filed with the Secretary of the Commission, U.S. Nuclear Regulatory 
    Commission, Washington, DC 20555-0001, Attention: Rulemakings and 
    Adjudications Staff, or may be delivered to the Commission's Public 
    Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC, 
    by the above date. A copy of the petition should also be sent to the 
    Office of the General Counsel, U.S. Nuclear Regulatory Commission, 
    Washington, DC 20555-0001, and to Mr. John O'Neill, Esq., Shaw, 
    Pittman, Potts & Trowbridge, 2300 N Street, N.W., Washington, D.C., 
    20037, attorney for the licensee.
        Nontimely filings of petitions for leave to intervene, amended 
    petitions, supplemental petitions and/or requests for hearing will not 
    be entertained absent a determination by the Commission, the presiding 
    officer or the presiding Atomic Safety and Licensing Board that the 
    petition and/or request should be granted based upon a balancing of the 
    factors specified in 10 CFR 2.714(a)(1)(I)-(v) and 2.714(d).
        If a request for a hearing is received, the Commission's staff may 
    issue the amendment after it completes its technical review and prior 
    to the completion of any required hearing if it publishes a further 
    notice for public comment of its proposed finding of no significant 
    hazards consideration in accordance with 10 CFR 50.91 and 50.92.
        For further details with respect to this action, see the 
    application for amendment dated May 15, 1997, as supplemented by 
    letters dated June 26, August 4, August 27, September 24, October 21, 
    November 23, November 25, December 11 and December 22, 1998, and 
    February 5, March 9, April 7, and April 21, 1999, which are available 
    for public inspection at the Commission's Public Document Room, the 
    Gelman Building, 2120 L Street, NW., Washington, DC, and at the local 
    public document room located at the Elmer Ellis Library, University of 
    Missouri, Columbia, Missouri, 65201.
    
        Dated at Rockville, Maryland, this 21st day of April 1999.
    
        For the Nuclear Regulatory Commission.
    Mel Gray,
    Project Manager, Section 2, Project Directorate IV & Decommissioning 
    Division of Licensing Project Management, Office of Nuclear Reactor 
    Regulation.
    [FR Doc. 99-10493 Filed 4-26-99; 8:45 am]
    BILLING CODE 7590-01-P
    
    
    

Document Information

Published:
04/27/1999
Department:
Nuclear Regulatory Commission
Entry Type:
Notice
Document Number:
99-10493
Pages:
22658-22661 (4 pages)
Docket Numbers:
Docket No. 50-483
PDF File:
99-10493.pdf