94-10530. Detroit Edison Co. (Fermi 2); Exemption  

  • [Federal Register Volume 59, Number 84 (Tuesday, May 3, 1994)]
    [Unknown Section]
    [Page 0]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 94-10530]
    
    
    [[Page Unknown]]
    
    [Federal Register: May 3, 1994]
    
    
    -----------------------------------------------------------------------
    
    NUCLEAR REGULATORY COMMISSION
    [Docket No. 50-341]
    
     
    
    Detroit Edison Co. (Fermi 2); Exemption
    
    I
    
        Detroit Edison Company (the licensee) is the holder of Facility 
    Operating License No. NPF-43 which authorizes operation of the Fermi 2 
    Nuclear Plant at steady-state reactor power levels not in excess of 
    3430 megawatts thermal. The Fermi 2 facility is a boiling water reactor 
    located at the licensee's site in Monroe County, Michigan. The license 
    provides, among other things, that it is subject to all rules, 
    regulations, and Orders of the Nuclear Regulatory Commission (the 
    Commission) now or hereafter in effect.
    
    II
    
        Paragraph III.C of appendix J to 10 CFR part 50 requires, in part, 
    that valves, unless pressurized with fluid (e.g., water, nitrogen) from 
    a seal system, shall be tested by pressurizing with air or nitrogen at 
    a test pressure of Pa (56.5 psig), the calculated peak containment 
    internal pressure as a result of the design basis accident. Further, 
    the combined leakage rate of all penetrations and valves subject to 
    Type B and C testing shall be less than 0.60 La (La is the maximum 
    allowable leakage rate at Pa). Leakage from containment isolation 
    valves that are sealed with fluid from a seal system may be excluded, 
    provided the leakage rates for these valves do not exceed the Technical 
    Specification leakage requirements and the seal system fluid inventory 
    is sufficient to ensure the sealing function for 30 days following an 
    accident at a pressure of 1.10 Pa.
        Pursuant to 10 CFR 50.12(a), the NRC may grant exemptions from the 
    requirements of the regulations (1) which are authorized by law, will 
    not present an undue risk to the public health and safety, and are 
    consistent with the common defense and security; and (2) where special 
    circumstances are present.
    
    III
    
        By letter dated May 24, 1993, the licensee requested an exemption 
    from the requirements of 10 CFR part 50, appendix J, III.C for 
    performing Type C integrated leak rate tests of the containment 
    isolation valves in the Low pressure coolant injection (LPCI) lines of 
    the residual heat removal (RHR) system. The valves in question are the 
    loop A and B LPCI isolation valves, which are motor-operated gate 
    valves, outboard of containment and which are operable from the control 
    room and are designated as E11-F015 A and B. The licensee proposed, as 
    alternative testing, an external leakage test, with water as the test 
    medium, at a pressure of 1045 psig with an allowable leakage value of 5 
    milliliters per minute (ml/min). The license also provided 
    justification in its May 24, 1993, letter to reclassify the inboard 
    containment LPCI valve configuration (which consists of a reverse flow 
    swing check valve with a 1-inch, locked closed, solenoid-operated 
    bypass valve) as other than containment isolation valves and thus no 
    longer subject to Type C testing.
        The staff evaluated the licensee's proposal for reclassification of 
    the inboard containment valves and concluded that the licensee's 
    proposal met the guidance in the Standard Review Plan (SRP), NUREG-
    0800, Section 6.2.4 for differing from the explicit requirements of 
    General Design Criterion 55 in 10 CFR part 50, appendix A for 
    containment isolation valves (CIVs). Subsection II.6.e allows only a 
    single CIV outside containment, if the system is closed outside 
    containment and certain other criteria are met. Details concerning the 
    staff's review are contained in the staff's safety evaluation dated 
    April 22, 1994.
        Two aspects of the RHR system form the basis for the proposed 
    exemption. It is a closed system outside of containment, and the 
    containment penetrations will be water sealed during a loss of coolant 
    accident (LOCA). The licensee's analyses showed that a water seal. 
    pressurized to greater than 1.1 Pa (62.15 psig), would exist outboard 
    of the LPCI CIV for at least 30 days following the design basis LOCA 
    despite the most limiting single active failure. However, if one or 
    both of the LPCI CIVs is shut, that water seal might not prevent 
    external valve leakage (valve stem or bonnet leakage). The licensee 
    also showed that a water seal, would exist inboard of the LPCI CIVs 
    following a design basis LOCA. The licensee's analyses demonstrated 
    that the volume of the water seal is sufficient to last for greater 
    than 30 days assuming the leakage limit proposed in their alternative 
    testing acceptance criteria. The licensee's analyses also showed that 
    through seat leakage of the LPCI CIVs would be in toward containment 
    and would not deplete the water seal.
        Although the external leakage water seal would prevent atmosphere 
    from leading out of containment, it does not satisfy the requirements 
    for a water seal contained in Appendix J. Appendix J allows water 
    sealed valves to be excepted from the normal Type C testing with air, 
    but it requires that the water seal be pressurized to at least 1.1 Pa 
    during an accident. The water leg inboard of the LPCI CIVs does not 
    meet this requirement. Nevertheless, the staff has determined that the 
    licensee's analyses of the water seals provide sufficient assurance 
    that containment atmosphere leakage out of containment will be 
    prevented during an accident to justify granting the requested 
    exemption from Type C testing of the LPCI CIVs with air as the test 
    medium. The licensee's alternative test will measure external valve 
    leakage with a limit of 5 ml/min using water as the test medium at a 
    pressure of 1045 psig.
    
    IV
    
        Accordingly, the Commission concluded that the licensee's proposed 
    alternative testing plan and analyses provide sufficient assurance that 
    the containment atmosphere would not leak out of containment through 
    the LPCI CIVs during a design basis accident and that containment 
    integrity will be maintained by granting the proposed exemption.
        The special circumstances for granting this exemption pursuant to 
    10 CFR 50.12 have also been identified. As stated in part in 10 CFR 
    50.12(a)(2)(ii), special circumstances are present when application of 
    the regulation in the particular circumstances is not necessary to 
    achieve the underlying purpose of the rule. The purpose of Section 
    III.C of Appendix J is to measure containment isolation valve leakage 
    rates. This leakage, when summed with the allowable Type A and Type B 
    leakage is limited to a value which ensures overall containment 
    integrity in preventing the uncontrolled release of radioactivity to 
    the environment. The licensee has demonstrated through analyses and by 
    proposing alternative testing criteria, that containment integrity will 
    be maintained. Consequently, the Commission concludes that the special 
    circumstances of 10 CFR 50.12 (a)(2)(ii) exist in that application of 
    the regulation in these particular circumstances is not necessary to 
    achieve the underlying purpose of the rule.
    
    V
    
        Accordingly, the Commission has determined that, pursuant to CFR 
    50.12 this exemption as described in Section III above is authorized by 
    law, will not present an undue risk to the public health and safety, 
    and is consistent with the common defense and security. The Commission 
    further determines that special circumstances as provided in 10 CFR 
    50.12(a)(2)(ii) are present justifying the exemption.
        Therefore, the Commission hereby grants an exemption as described 
    in Section III above the requirements in 10 CFR 50.12, Appendix J, 
    III.C. for performing Type C containment integrated leak rate tests of 
    the CIVs in the LPCI lines of the RHR system and approves the 
    licensee's alternative testing plan.
        Pursuant to CFR 51.32, the Commission has determined that the 
    granting of this exemption will have no significant impact on the 
    environment (59 FR 19028).
        This exemption is effective upon issuance.
    
        Dated at Rockville, Maryland, this 22nd day of April 1994.
    
        For the Nuclear Regulatory Commission.
    Elinor G. Adensam,
    Acting Director; Division of Reactor Projects--III/IV; Office of 
    Nuclear Reactor Regulation.
    [FR Doc. 94-10530 Filed 5-2-94; 8:45 am]
    BILLING CODE 7590-01-M
    
    
    

Document Information

Published:
05/03/1994
Department:
Nuclear Regulatory Commission
Entry Type:
Uncategorized Document
Document Number:
94-10530
Pages:
0-0 (1 pages)
Docket Numbers:
Federal Register: May 3, 1994, Docket No. 50-341