98-15003. Protection of Stratospheric Ozone; Refrigerant Recycling; Substitute Refrigerants  

  • [Federal Register Volume 63, Number 112 (Thursday, June 11, 1998)]
    [Proposed Rules]
    [Pages 32044-32099]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 98-15003]
    
    
    
    [[Page 32043]]
    
    _______________________________________________________________________
    
    Part II
    
    
    
    
    
    Environmental Protection Agency
    
    
    
    
    
    _______________________________________________________________________
    
    
    
    40 CFR Part 82
    
    
    
    Protection of Stratospheric Ozone; Refrigerant Recycling; Substitute 
    Refrigerants; Proposed Rule
    
    Federal Register / Vol. 63, No. 112 / Thursday, June 11, 1998 / 
    Proposed Rules
    
    [[Page 32044]]
    
    
    
    ENVIRONMENTAL PROTECTION AGENCY
    
    40 CFR Part 82
    
    [FRL-6107-1]
    
    
    Protection of Stratospheric Ozone; Refrigerant Recycling; 
    Substitute Refrigerants
    
    AGENCY: Environmental Protection Agency (EPA).
    
    ACTION: Proposed rule.
    
    -----------------------------------------------------------------------
    
    SUMMARY: The Environmental Protection Agency (EPA) is proposing to 
    amend the rule on refrigerant recycling promulgated under section 608 
    of the Clean Air Act to clarify how the requirements of section 608 
    extend to refrigerants that are used as substitutes for 
    chlorofluorocarbon (CFC) and hydrochlorofluorocarbon (HCFC) 
    refrigerants. This proposed rule would supplement a self-effectuating 
    prohibition on venting substitute refrigerants to the atmosphere that 
    became effective on November 15, 1995. It would also exempt certain 
    substitute refrigerants from the prohibition on the basis of current 
    evidence that their release does not pose a threat to the environment. 
    In addition, EPA is proposing to change the current requirements for 
    CFC and HCFC refrigerants to accommodate the proliferation of new 
    refrigerants on the market and to strengthen and clarify the existing 
    leak repair requirements for equipment containing CFC and HCFC 
    refrigerants. This proposed rule will significantly reduce emissions of 
    environmentally harmful refrigerants in a cost-effective manner.
    
    DATES: Written comments on the proposed rule must be received by August 
    10, 1998, unless a hearing is requested by June 18, 1998. If a hearing 
    is requested, written comments must be received by August 31, 1998. If 
    requested, a public hearing will be held at 10:00 am, July 1, 1998, at 
    501 3rd St. NW, Washington, DC in the 1st Floor Conference Room. 
    Individuals wishing to request a hearing must contact the Stratospheric 
    Ozone Information Hotline at 1-800-296-1996 by June 18, 1998. To find 
    out whether a hearing will take place, contact the Stratospheric Ozone 
    Information Hotline between June 22, 1998 and July 1, 1998.
    
    ADDRESSES: Comments should be submitted in duplicate to the attention 
    of Air Docket No. A-92-01 VIII.H at: Environmental Protection Agency, 
    401 M Street, SW., Washington, DC 20460. Additional information may be 
    found at Air Docket No. A-91-42, which is incorporated by reference for 
    purposes of this rulemaking. (Please do not submit comments on this 
    proposed rule to A-91-42.) The Air and Radiation Docket and Information 
    Center is located in room M-1500, Waterside Mall (Ground Floor), 
    Environmental Protection Agency, 401 M Street, SW., Washington, DC 
    20460. Dockets may be inspected from 8 a.m. to 5:30 p.m., Monday 
    through Friday. A reasonable fee may be charged for copying docket 
    materials.
    
    FOR FURTHER INFORMATION CONTACT: Debbie Ottinger, Program 
    Implementation Branch, Stratospheric Protection Division, Office of 
    Atmospheric Programs, Office of Air and Radiation (6205-J), 401 M 
    Street, SW., Washington, DC 20460. The Stratospheric Ozone Information 
    Hotline at 1-800-296-1996 can also be contacted for further 
    information.
    
    SUPPLEMENTARY INFORMATION: The contents of this preamble are listed in 
    the following outline:
    
    I. Regulated Entities
    II. Background
        A. Section 608 of the Clean Air Act
        B. Factors Considered in the Development of this Proposal
        C. Public Participation
    III. Scope of Statutory and Proposed Regulatory Requirements
        A. Overview of Proposed Requirements
        1. HFCs and PFCs
        2. Chemically Active Common Gases
        3. Hydrocarbons
        4. Proposed Changes to Requirements for CFCs and HCFCs
        B. Determination of Whether Release or Disposal Poses a Threat 
    to the Environment
        1. Methodology
        2. HFCs and PFCs
        3. Chemically Active Common Gases
        4. Hydrocarbons
        5. Inert Atmospheric Constituents
    IV. The Proposed Rule
        A. Definitions
        1. Appliance
        a. Inclusion of Heat Transfer Devices in the Term ``Appliance''
        b. Coverage of One-Time Expansion Devices
        c. Secondary Loops
        2. Full Charge
        3. High-pressure Appliance
        4. Higher-pressure Appliance
        5. Leak Rate
        6. Low-pressure Appliance
        7. Opening
        8. Reclaim
        9. Refrigerant
        10. Substitute
        11. Technician
        12. Very-high-pressure Appliance
        B. Required Practices
        1. Evacuation of Appliances
        a. Evacuation Requirements for Appliances Other Than Small 
    Appliances, MVACs, and MVAC-like Appliances
        b. Evacuation Levels for Small Appliances
        c. Evacuation Levels for Disposed MVACs, MVAC-like Appliances, 
    and Small Appliances
        d. Request for Comment on Establishing Special Evacuation 
    Requirements for Heat Transfer Appliances
        e. Proposed Clarifications of Evacuation Requirements
        2. Disposition of Recovered Refrigerant
        a. Background
        b. Extending Purity Requirements to HFC and PFC Refrigerants
        c. Updating the Purity Standard
        d. Generic Standard of Purity
        e. Possible Application of Standard of Purity to New 
    Refrigerants
        3. Leak Repair
        a. Comfort Cooling Chillers
        b. Commercial Refrigeration
        c. Industrial Process Refrigeration
        d. Cross-sector Issues
        e. Coverage of HFC and PFC Appliances
        f. Clarification of Current Requirements
        4. Proposed Changes for Servicing of MVAC-like Appliances
        a. Background
        b. Recent Amendments to Subpart B
        c. Today's Proposal
        C. Equipment Certification
        1. Certification of Recovery and Recycling Equipment Intended 
    for Use with Appliances Except Small Appliances, MVACs, and MVAC-
    like Appliances
        a. Background
        b. Certification of Recovery/recycling Equipment Used with HFCs 
    and PFCs
        c. Use of Representative Refrigerants in Equipment Testing
        d. Additional Refrigerants
        e. Materials Compatibility
        f. Fractionation
        g. Flammability
        2. Certification of Recovery and Recycling Equipment Intended 
    for Use with Small Appliances
        3. Approval of Equipment Testing Organizations to Test Recovery 
    Equipment with HFC and PFC Refrigerants
        4. Use of Existing CFC/HCFC Recovery Equipment with HFC and PFC 
    Refrigerants
        D. Technician Certification
        E. Sales Restriction
        F. Safe Disposal of Small Appliances, MVACs, and MVAC-like 
    Appliances
        1. Coverage of HFCs and PFCs
        2. Possible Clarifications
        G. Certification by Owners of Recycling or Recovery Equipment
        H. Servicing Apertures
        I. Prohibition on Manufacture of One-Time Expansion Devices that 
    Contain Other than Exempted Refrigerants
        J. Recordkeeping Requirements
    V. Summary of Supporting Analyses
        A. Executive Order 12866
        B. Unfunded Mandates Reform Act
        C. Paperwork Reduction Act
        D. Regulatory Flexibility
        E. National Technology Transfer and Advancement Act
        F. Children's Health Protection
    
    [[Page 32045]]
    
    I. Regulated Entities
    
        Entities potentially regulated by this action include those who 
    manufacture, own, maintain, service, repair, or dispose of all types of 
    air-conditioning and refrigeration equipment; those who sell or reclaim 
    refrigerants; and manufacturers of refrigerant recycling and recovery 
    equipment. Regulated categories and entities include:
    
    ------------------------------------------------------------------------
              Category                  Examples of regulated entities      
    ------------------------------------------------------------------------
    Industry....................  Manufacturers of air-conditioning or      
                                   refrigeration equipment.                 
                                  Technicians who service, maintain, repair,
                                   or dispose of air-conditioning and       
                                   refrigeration equipment.                 
                                  Owners of air-conditioning and            
                                   refrigeration equipment, including       
                                   building owners and operators, grocery   
                                   stores, chemical, pharmaceutical, and    
                                   petrochemical manufacturers, ice machine 
                                   operators, utilities.                    
                                  Manufacturers of recycling and recovery   
                                   equipment.                               
                                  Refrigerant reclaimers.                   
                                  Scrap yards and auto dismantlers.         
    ------------------------------------------------------------------------
    
        This table is not intended to be exhaustive, but rather provides a 
    guide for readers regarding entities likely to be regulated by this 
    action. This table lists the types of entities that EPA is now aware 
    could potentially be affected by this action. Other types of entities 
    not listed in the table could also be affected. To determine whether 
    your company is regulated by this action, you should carefully examine 
    the applicability criteria contained in section 608 of the Clean Air 
    Amendments of 1990; discussed in regulations published on December 30, 
    1993 (58 FR 69638); and discussed below. If you have questions 
    regarding the applicability of this action to a particular entity, 
    consult the person listed in the preceding FOR FURTHER INFORMATION 
    CONTACT section.
    
    II. Background
    
        Effective November 15, 1995, section 608(c)(2) of the Clean Air Act 
    prohibits the knowing release of substitutes for CFC and HCFC 
    refrigerants during the maintenance, service, repair, or disposal of 
    air-conditioning and refrigeration equipment, unless EPA determines 
    that such release does not pose a threat to the environment. Although 
    EPA is proposing to determine that releases of some substitute 
    refrigerants do not pose a threat to the environment, there are other 
    substitutes, specifically HFCs and PFCs, for which EPA is not proposing 
    to make such a determination. Thus, EPA is proposing a regulation that 
    will clarify how the venting prohibition of section 608(c)(2) must be 
    implemented for HFC and PFC refrigerants, as well as any other 
    refrigerants whose release EPA does not find does not pose a threat to 
    the environment. EPA is also proposing to strengthen the existing leak 
    repair requirements for some types of appliances containing CFCs and 
    HCFCs, in recognition of design changes that have lowered achievable 
    leak rates.
        By establishing requirements regarding the maintenance, service, 
    repair, and disposal of appliances containing HFC and PFC refrigerants, 
    EPA believes that this proposed rule would help to minimize any 
    environmental harm that might result from the transition away from 
    ozone-depleting chemicals. In this respect, this proposed rule is 
    similar to regulations being implemented under sections 609 and 612 of 
    the Act. This rule would directly limit emissions of gases that result 
    in global warming, whose possible consequences are discussed at length 
    in section III.B.2 below. In addition, the proposed rule would reduce 
    emissions of ozone-depleting refrigerants by establishing a consistent 
    regulatory framework for all halocarbon refrigerants and by lowering 
    leak rates for appliances containing ozone-depleting refrigerants. The 
    environmental and human health consequences of ozone depletion include 
    increased rates of skin cancer and cataracts, suppression of the immune 
    system, increased formation of ground-level ozone, damage to crops and 
    other plants, and damage to marine microorganisms at the base of the 
    aquatic food chain. The establishment of a consistent regulatory 
    framework would also facilitate compliance with the Section 608 
    National Recycling and Emissions Reduction Program by simplifying and 
    clarifying regulatory requirements.
    
    A. Section 608 of the Clean Air Act
    
        Section 608 of the Clean Air Act, as amended in 1990, provides the 
    legal basis for this rulemaking. It requires EPA to establish a 
    comprehensive program to limit emissions of ozone-depleting 
    refrigerants, and prohibits the release of these refrigerants, and 
    eventually their substitutes, during the servicing and disposal of air-
    conditioning and refrigeration equipment.
        Section 608 is divided into three subsections. In brief, the first, 
    section 608(a), requires regulations to reduce the use and emission of 
    class I substances (CFCs, halons, carbon tetrachloride, and methyl 
    chloroform) and class II substances (HCFCs) to the lowest achievable 
    level, and to maximize the recycling of such substances. Section 608(b) 
    requires that the regulations promulgated pursuant to subsection (a) 
    contain requirements concerning the safe disposal of class I and class 
    II substances. Finally, section 608(c) establishes self-effectuating 
    prohibitions on the venting into the environment of class I or class II 
    substances, and eventually their substitutes, during servicing and 
    disposal of air-conditioning or refrigeration equipment.
        Specifically, subsection 608(c) provides in paragraph (1) that, 
    effective July 1, 1992, it is ``unlawful for any person, in the course 
    of maintaining, servicing, repairing, or disposing of an appliance or 
    industrial process refrigeration, to knowingly vent or otherwise 
    knowingly release or dispose of any class I or class II substance used 
    as a refrigerant'' in a manner that ``permits such substance to enter 
    the environment.'' The statute exempts from this self-effectuating 
    prohibition ``de minimis releases associated with good faith attempts 
    to recapture and recycle or safely dispose'' of a substance. EPA 
    considers releases to meet the criteria for exempted de minimis 
    releases when they occur while the recycling and recovery requirements 
    of the section 608 and 609 regulations are followed (40 CFR 82.154(a)). 
    Section 608(c)(2) extends the prohibition on venting to substances that 
    are substitutes for class I and class II refrigerants, effective 
    November 15, 1995, unless the Administrator determines that such 
    venting or release does not pose a threat to the environment.
        On May 14, 1993, EPA published final regulations implementing 
    subsections (a), (b), and (c)(1) (58 FR 28660). These regulations 
    include evacuation requirements for appliances being serviced or 
    disposed of, standards and testing requirements for recycling and 
    recovery equipment, certification requirements for technicians, purity
    
    [[Page 32046]]
    
    standards and testing requirements for used refrigerant sold to a new 
    owner, certification requirements for refrigerant reclaimers, leak 
    repair requirements, and requirements for the safe disposal of 
    appliances that enter the waste stream with the charge intact.
        EPA is today proposing regulations to implement and clarify the 
    requirements of section 608(c)(2), which extends the prohibition on 
    venting to substitutes for CFC and HCFC refrigerants. EPA believes that 
    these regulations are also important to the Agency's efforts to 
    continue to carry out its mandate under section 608(a) to minimize 
    emissions of ozone-depleting substances. In addition to sections 608 
    (a) and (c), EPA is relying on its authority under section 301(a) of 
    the Act to promulgate these requirements.
        While section 608(c) is self-effectuating, EPA regulations are 
    necessary to define ``(d)e minimis releases associated with good faith 
    attempts to recapture and recycle or safely dispose'' of such 
    substances and to effectively implement and enforce the venting 
    prohibition. EPA believes that these regulations will help to implement 
    the prohibition by providing: (1) Clear guidance to technicians working 
    with substitute refrigerants on what releases do and do not constitute 
    violations of the prohibition, (2) information on the performance of 
    recycling and recovery equipment intended for use with substitute 
    refrigerants through the equipment certification program, and (3) 
    information on how to recycle effectively and efficiently through the 
    technician certification program. Section 301(a) authorizes EPA to 
    ``prescribe such regulations as are necessary to carry out (its) 
    functions under this Act.'' Section 608(c) provides EPA authority to 
    promulgate regulations to interpret, implement and enforce the venting 
    prohibition. Section 301(a) supplements EPA's authority under section 
    608(c) to promulgate regulations to carry out EPA's functions under 
    section 608(c).
        Section 608(a) provides EPA additional authority to promulgate many 
    of the requirements proposed today. Section 608(a) requires EPA to 
    promulgate regulations regarding use and disposal of class I and II 
    substances that ``reduce the use and emission of such substances to the 
    lowest achievable level'' and ``maximize the recapture and recycling of 
    such substances.'' Section 608(a) further provides that ``(s)uch 
    regulations may include requirements to use alternative substances 
    (including substances which are not class I or class II substances) * * 
    * or to promote the use of safe alternatives pursuant to section 612 or 
    any combination of the foregoing.'' As discussed further below, 
    improper handling of substitute substances is likely to produce 
    contamination (and therefore reduction in recycling) and release of 
    class I and class II substances. EPA's authority to promulgate 
    regulations regarding use of class I and II substances, including 
    requirements to use alternatives, is sufficiently broad to include 
    requirements on how to use alternatives, where this is needed to reduce 
    emissions and maximize recycling of class I and II substances.
        In particular, certification requirements for technicians who 
    perform work that could release substitute refrigerants to the 
    atmosphere, as enforced through a sales restriction on substitutes, are 
    critical to fulfill the statutory goals for class I and II substances. 
    Technician certification and a sales restriction are necessary to 
    ensure that persons lacking the expertise tested through certification 
    do not release or contaminate class I and II substances in the course 
    of using substitutes to recharge or perform other work on systems 
    containing class I and II substances. In addition, applying one 
    consistent set of requirements to all relevant refrigerants will 
    promote compliance with and enforcement of those requirements for both 
    ozone-depleting refrigerants and their substitutes by reducing 
    complexity and minimizing loopholes.
        As discussed below, EPA is proposing requirements very similar to 
    those for CFCs and HCFCs for some alternative refrigerants, while EPA 
    is proposing to exempt other refrigerants from the prohibition on 
    venting because their release or disposal does not pose a threat to the 
    environment.
    
    B. Factors Considered in the Development of this Proposal
    
        In developing these proposed regulations, EPA has considered a 
    number of factors. First, EPA has considered which non-ozone-depleting 
    refrigerants should be classified as ``substitute'' refrigerants. EPA 
    is proposing to adopt a definition that is similar to that adopted by 
    EPA in its Significant New Alternatives Policy (SNAP) Program, except 
    the proposed definition omits the proviso of the SNAP definition that a 
    substitute be ``intended for use as a replacement for a class I or 
    class II substance.'' For the purposes of section 608, therefore, EPA 
    proposes to consider a refrigerant a substitute in a certain end-use if 
    the substance is used as a substitute for CFCs or HCFCs in that end-use 
    by any user. That is, EPA would consider a refrigerant a ``substitute'' 
    for CFCs or HCFCs under section 608 if any of the following were the 
    case: (1) The substitute refrigerant immediately replaced a CFC or HCFC 
    in a specific instance, (2) the substitute refrigerant replaced another 
    substitute that replaced a CFC or HCFC in a specific instance (was a 
    second- or later-generation substitute), or (3) the substitute 
    refrigerant had always been used in a particular instance, but other 
    users in that end-use had used it to replace a CFC or HCFC.
        EPA does not believe that it is appropriate under section 608 to 
    consider the intent or history of an individual user in determining 
    whether a refrigerant is a ``substitute'' for CFCs or HCFCs in a given 
    instance. First, it is reasonable to interpret ``substitute'' to 
    include second- or later as well as first-generation substitutes for 
    CFCs and HCFCs. As discussed earlier, the goal of these regulations is 
    to minimize any environmental harm that might be associated with the 
    transition away from CFC and HCFC refrigerants. In many cases, the 
    transition away from CFCs and HCFCs is a multi-step process, with 
    substitutes supplanting each other as they are tested and developed. In 
    the absence of the phaseout of CFCs and HCFCs, the later-generation 
    substitutes would probably never have been used. Thus, even if a 
    substance is not being used as a direct substitute for CFCs or HCFCs in 
    a particular instance, its use is the result of the transition away 
    from CFCs and HCFCs and the substance serves as a substitute for these 
    chemicals. (Of course, the environmental impact of the release of the 
    chemical is the same regardless of what it replaces.)
        Second, it is also reasonable to interpret ``substitute'' to mean a 
    refrigerant that is occasionally used as a substitute for CFC or HCFC 
    refrigerants in a given end-use (e.g., cold storage warehouses), even 
    if the refrigerant has always been used by a particular user or in a 
    particular end-use. EPA has broad authority to promulgate and implement 
    clear, enforceable regulations, and exercise of this authority would be 
    impeded if the Agency had to attempt to trace the individual histories 
    of specific appliances in implementing and enforcing the requirements. 
    As an example of how this definition would work under these 
    regulations, ammonia used in cold storage warehouses would be 
    considered a ``substitute,'' and would therefore be subject to section 
    608(c)(2),1
    
    [[Page 32047]]
    
    because at least some cold storage warehouses have substituted ammonia 
    for CFCs. This would be true even if the ammonia in a given cold 
    storage warehouse were the original refrigerant at that particular 
    site, or if another substitute had first replaced the original CFC 
    refrigerant and ammonia in turn had replaced that substitute.
    ---------------------------------------------------------------------------
    
        \1\ As discussed below, ammonia may nevertheless be exempted 
    from these regulations because EPA is proposing to determine that it 
    is adequately controlled under other authorities.
    ---------------------------------------------------------------------------
    
        Using this criterion, EPA has identified five classes of substitute 
    refrigerants in the sectors covered by the SNAP rule: 
    hydrofluorocarbons (HFCs), perfluorocarbons (PFCs), hydrocarbons (HCs), 
    chemically active common gases, including ammonia and chlorine, and 
    inert atmospheric constituents, including carbon dioxide and water. EPA 
    has divided substitutes into these classes on the basis of the varying 
    environmental impacts of each class and the varying regulatory 
    structures already in place for each class.
        As the second factor in this proposed rulemaking, EPA has made a 
    proposed determination regarding whether or not the release or disposal 
    of a substitute refrigerant during the service or disposal of an 
    appliance poses a threat to the environment. This determination 
    consists of two findings. In the first finding, EPA determines whether 
    release or disposal of a substitute refrigerant could pose a threat to 
    the environment due to the toxicity or other inherent characteristic of 
    the refrigerant. In the second finding, EPA determines whether and to 
    what extent such release or disposal actually takes place during the 
    servicing and disposal of appliances. The release and disposal of many 
    substitute refrigerants are limited and/or controlled by other 
    authorities, such as OSHA regulations and building codes. To the extent 
    that release during the servicing and disposal of appliances is 
    adequately controlled by other authorities, EPA proposes to defer to 
    these authorities rather than set up a second regulatory regime.
        As is discussed in more detail below, EPA recognizes that release 
    of HFCs and PFCs during the servicing and disposal of appliances could 
    pose a threat to the environment due to the global warming potential 
    (GWP) of these refrigerants, that release of hydrocarbons during the 
    servicing and disposal of appliances could pose a threat due to the 
    flammability and smog-forming capability of these refrigerants, and 
    that release of chemically active common gases during the servicing and 
    disposal of appliances could pose a threat due to the toxicity and 
    flammability of these refrigerants. However, EPA is proposing to 
    determine that the release of hydrocarbons and chemically active common 
    gases during the servicing and disposal of appliances is adequately 
    controlled by other authorities, and therefore does not actually pose a 
    threat. EPA is also proposing to determine that the release of inert 
    atmospheric constituents during the servicing and disposal of 
    appliances does not pose a threat to the environment.
        As the third factor in this proposed rulemaking, EPA has considered 
    the availability of technology to control releases, the environmental 
    benefits of controlling releases, and the costs of controlling releases 
    for each class of substitutes. (In proposing new permissible leak rates 
    for certain CFC and HCFC appliances, EPA has considered these factors 
    for CFCs and HCFCs.) In addition, as much as possible, EPA has sought 
    to maintain consistency between the proposed requirements for HFCs and 
    those for CFCs and HCFCs. The Agency considers such consistency 
    important for two reasons. First, it will reduce confusion, simplify 
    the regulatory scheme, and ease compliance both with the requirements 
    applying to substitutes and with those applying to CFCs and HCFCs. 
    Second and more important, the Agency believes that much of the 
    rationale for the recycling program developed for ozone-depleting 
    refrigerants applies to any recycling program for environmentally 
    harmful refrigerants.
    
    C. Public Participation
    
        In developing this proposed rule, EPA has also considered comments 
    received during meetings with industry, government, and environmental 
    representatives. On March 10, 1995, EPA convened a meeting with 20 
    representatives of appliance manufacturers, servicers, and users, 
    recycling and recovery equipment manufacturers, equipment testers, and 
    refrigerant reclaimers and wholesalers, soliciting comment on a range 
    of regulatory options. A summary of this meeting is available in the 
    public docket for this rulemaking. EPA has also met with industry and 
    government representatives to gather data on refrigerant emissions, to 
    better understand current industry practices, and to determine when and 
    how existing regulatory authorities control emissions of substitute 
    refrigerants. Finally, EPA has worked with the air-conditioning and 
    refrigeration industry's primary standards-setting organizations, the 
    Air Conditioning and Refrigeration Institute (ARI) and the American 
    Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc. 
    (ASHRAE), in developing its proposal. Wherever appropriate, EPA has 
    incorporated standards and guidelines from these organizations into the 
    proposed rule.
    
    III. Scope of Statutory and Proposed Regulatory Requirements
    
    A. Overview of Proposed Requirements
    
    1. HFCs and PFCs
        EPA is proposing to extend the regulatory framework for CFCs and 
    HCFCs to HFCs and PFCs, making appropriate adjustments for the varying 
    physical properties and environmental impacts of these refrigerants. 
    Thus, appliances containing HFC or PFC refrigerants would have to be 
    evacuated to established levels; recycling and recovery equipment used 
    with HFCs or PFCs would have to be certified (although existing 
    recovery equipment that met certain minimum standards would be 
    grandfathered); technicians who work with HFCs or PFCs would have to be 
    certified (although technicians who have been certified to work with 
    CFCs and HCFCs would be grandfathered); sales of HFC and PFC 
    refrigerants would be restricted to certified technicians; used HFC and 
    PFC refrigerants sold to a new owner would have to be tested to verify 
    that they meet industry purity standards; refrigerant reclaimers who 
    purify HFCs or PFCs would have to be certified; owners of HFC and PFC 
    appliances above a certain size would have to repair leaks above a 
    certain size; final disposers of small appliances and motor vehicle air 
    conditioners (MVACs) containing HFCs or PFCs would have to ensure that 
    refrigerant was recovered from this equipment before it was disposed 
    of; and manufacturers of HFC and PFC appliances would have to provide a 
    servicing aperture or a ``process stub'' on their equipment in order to 
    facilitate recovery of the refrigerant.
    2. Chemically Active Common Gases
        EPA is proposing to find that for the purposes of section 608, the 
    release and disposal of chlorine and ammonia do not pose a threat to 
    the environment because the release and disposal of these refrigerants 
    during the servicing and disposal of appliances are adequately 
    controlled by other authorities in the air-conditioning and 
    refrigeration applications where these refrigerants are currently used. 
    Therefore, EPA is proposing to find that the venting prohibition does 
    not apply to these substances and the Agency is not proposing recycling 
    requirements for these refrigerants at this time.
    
    [[Page 32048]]
    
    However, these proposed findings apply to currently SNAP-identified end 
    uses only. If ammonia and chlorine are proposed for use in other 
    applications, EPA will evaluate whether the venting prohibition and 
    recycling requirements should apply in those applications.
    3. Hydrocarbons
        EPA is proposing to find that for the purposes of section 608, the 
    release and disposal of hydrocarbons during the servicing and disposal 
    of appliances do not pose a threat to the environment, because they are 
    adequately controlled by other authorities in the industrial process 
    refrigeration applications in which these refrigerants are currently 
    used. Therefore, EPA is proposing to find that the venting prohibition 
    does not apply to these substances and the Agency is not proposing 
    recycling requirements for these refrigerants at this time. However, 
    these proposed findings apply to currently SNAP-identified end uses 
    only. If hydrocarbons are proposed for use in other applications, EPA 
    will evaluate whether the venting prohibition and recycling 
    requirements should apply in those applications.
    4. Proposed Changes to Requirements for CFCs and HCFCs
        In today's document, EPA is also proposing a number of changes to 
    the regulations covering CFC and HCFC refrigerants. Several of these 
    proposed changes are intended to accommodate the growing number of 
    refrigerants (both HFCs and HCFCs) that either are or will be subject 
    to the regulations. Such changes include the adoption of evacuation 
    requirements based solely on the saturation pressures of refrigerants, 
    the use of representative refrigerants from saturation pressure 
    categories for certifying recycling and recovery equipment, and the 
    adoption of the most recent industry purity and analytical standard for 
    refrigerants, ARI 700-1995, which includes a number of refrigerants 
    omitted from its predecessor, ARI 700-1993.
        Based on improvements in equipment design and maintenance that have 
    reduced leak rates over the last five years, EPA is also proposing to 
    reduce the maximum allowable leak rates for appliances containing more 
    than 50 pounds of refrigerant. At the same time, EPA is proposing to 
    make several changes to the leak repair requirements promulgated at 
    Sec. 82.156(i), the associated recordkeeping provisions at 
    Sec. 82.166(n) and (o), and the definition of ``full charge'' at 
    Sec. 82.152. EPA is also proposing to add a definition for ``leak 
    rate'' under Sec. 82.152 for the purposes of Sec. 82.156(i). The need 
    for most of these proposed changes was brought to EPA's attention by 
    industry stakeholders. EPA is also responding to inquiries concerning 
    whether or not leaks that occur after repairs have been completed and 
    all applicable verification tests have been successfully performed are 
    considered new leaks. In addition, the stakeholders suggested several 
    clarifying changes to the recordkeeping provisions.
    
    B. Determination of Whether Release or Disposal Poses a Threat to the 
    Environment
    
    1. Methodology
        In determining whether the release or disposal of a substitute 
    refrigerant during the servicing and disposal of appliances poses a 
    threat to the environment, EPA has examined the potential effects of 
    the refrigerant from the moment of release to its breakdown in the 
    environment, considering possible impacts on workers, building 
    occupants, and the environment as a whole. As noted above, these 
    effects vary among the different classes of refrigerant. EPA has also 
    examined the extent to which the release or disposal of a substitute is 
    already controlled by other authorities. In some cases, such 
    authorities tightly limit the quantity of the substitute emitted or 
    disposed of; in others, they ensure that the substitute is disposed of 
    in a way that will limit its impact on human health and the 
    environment. In still others, existing authorities address some threats 
    (e.g., occupational exposures) but not others (e.g., long-term 
    environmental impacts). The analysis below discusses the potential 
    environmental impacts of and existing controls on each class of 
    refrigerants.
    2. HFCs and PFCs
    a. Potential Environmental Impacts
    i. Toxicity and Flammability
        Most HFCs and PFCs have been classified as A1 refrigerants under 
    ASHRAE Standard 34, indicating that they have low toxicity and no 
    ability to propagate flame under the test conditions of the Standard. 
    (The exception is HFC 152a, which has been classified as an A2 
    refrigerant. This indicates that it may propagate flame under the test 
    conditions, but only at relatively high concentrations and with 
    relatively low heat of combustion.) However, like CFCs and HCFCs, HFCs 
    can have central nervous system depressant and cardiotoxic effects at 
    high concentrations (several thousand ppm) and can displace oxygen at 
    very high concentrations.
    ii. Long-term Environmental Impacts
        Once released into the atmosphere, hydrofluorocarbons (HFCs) and 
    perfluorocarbons (PFCs) have the ability to trap heat that would 
    otherwise be re-radiated from the Earth back to space. This ability, 
    along with the relatively long atmospheric lifetime of these gases 
    (particularly the PFCs), gives both HFCs and PFCs relatively high 
    global warming potentials (GWPs). The GWP of a gas is a measure of the 
    ability of a kilogram of that gas to contribute to global warming 
    compared to the ability of a kilogram of carbon dioxide to contribute 
    to global warming over a given span of time. The 100-year GWPs of HFCs 
    under consideration for use as refrigerants range from 140 (for HFC-
    152a) to 11,700 (for HFC-23), and the GWPs of PFCs under consideration 
    for use as refrigerants range from 8,700 (perfluorocyclo-butane) to 
    9,200 (perfluoroethane). HFC 134a, the most common individual HFC used 
    in air-conditioning and refrigeration equipment, has a global warming 
    potential of 1,300. Thus, the global warming impact of releasing a 
    kilogram of an HFC or PFC ranges from 140 to 11,700 times the impact of 
    releasing a kilogram of CO2.2 (Factoring in the 
    35% uncertainty associated with individual GWPs, this range becomes 90 
    to 15,800.)
    ---------------------------------------------------------------------------
    
        \2\ The CFCs and HCFCs being replaced by the HFCs are also 
    greenhouse gases, though their direct warming effect is counteracted 
    somewhat by the indirect cooling effect caused by their destruction 
    of stratospheric ozone, which is itself a greenhouse gas. The IPCC 
    Second Assessment noted that ``The net GWPs for the ozone-depleting 
    gases, which include the direct ``warming'' and indirect ``cooling'' 
    effects, have now been estimated.* * * The indirect effect reduces 
    their net GWPs: those of the chlorofluorocarbons tend to be 
    positive, while those of the halons tend to be negative'' (IPCC 
    Second Assessment, Working Group I report, p. 73).
    ---------------------------------------------------------------------------
    
        EPA recognizes that the release of refrigerants with high global 
    warming potentials could pose a threat to the environment. 
    Internationally accepted science indicates that increasing 
    concentrations of greenhouse gases, including HFCs and PFCs, will 
    ultimately raise atmospheric and oceanic temperatures. Although the 
    precise timing and extent of likely warming are uncertain, the 
    Intergovernmental Panel on Climate Change (IPCC) 3 concluded 
    in a 1995
    
    [[Page 32049]]
    
    Report that the global mean temperature would probably rise between 1 
    and 3.5 deg.C by 2100. Such a temperature rise would probably be 
    associated with a number of adverse environmental impacts, including 
    increased drought at middle latitudes, increased flood frequency and 
    inundation due to sea level rise, and forest and species loss due to 
    the rapid poleward migration of ideal ranges.
    ---------------------------------------------------------------------------
    
        \3\ The IPCC was jointly established by the World Meteorological 
    Organization and the United Nations Environment Programme in 1988 to 
    assess the scientific information that is related to the various 
    components of the climate change issue, and to formulate realistic 
    response strategies for the management of the climate change issue. 
    The first IPCC report was developed by 170 scientists from 25 
    countries and was peer-reviewed by an additional 200 scientists. 
    Since that time, the number of scientists developing and reviewing 
    the report has grown. This group comprises most of the active 
    scientists working in the field in the world today, and therefore 
    the report is an authoritative statement of the views of the 
    international scientific community at this time.
    ---------------------------------------------------------------------------
    
        It is already well established that naturally occurring greenhouse 
    gases keep the Earth 33 deg.C warmer than it otherwise would be. Since 
    1800, human activities have released additional greenhouse gases to the 
    atmosphere at an exponentially increasing rate. Atmospheric 
    concentrations of carbon dioxide have risen by approximately 30 
    percent; methane concentrations have risen by 145 percent; and nitrous 
    oxide concentrations have risen by 15 percent. In addition, 
    concentrations of man-made fluorocarbons, which have no natural source, 
    have risen quickly over the past 50 years.
        These trends may have already had an influence on global climate. 
    The draft of the most recent report of the IPCC stated that ``emerging 
    evidence points towards a detectable human influence on climate.'' In 
    support of this statement, the draft report notes that the global mean 
    surface temperature has increased by between about 0.3 and 0.6 deg.C 
    since the late 19th century, that the 20th century global mean 
    temperature is at least as high as that of any other century since 1400 
    A.D. (before which data are too sparse to allow reliable estimates), 
    that the years since 1990 have been some of the warmest in the 
    instrumental record (the nine warmest years this century have all 
    occurred since 1980), and that sea levels around the world have risen 
    by between 10 and 25 centimeters over the past 100 years. Moreover, 
    several other events consistent with global warming have been observed, 
    including a decrease in Northern Hemisphere snow cover, a simultaneous 
    decrease in Arctic sea ice, and continued melting of alpine glaciers. 
    The report concludes:
    
        Observed global warming over the past 100 years is larger than 
    our best estimates of the magnitude of natural climate variability 
    over at least the last 600 years. More importantly, there is 
    evidence of an emerging pattern of climate response in the observed 
    climate record to forcings by greenhouse gases and sulphate 
    aerosols. The evidence comes from the geographical, seasonal and 
    vertical patterns of temperature change. Taken together, these 
    results point towards a detectable human influence on global 
    climate.
    
        Because of the large thermal inertia of Earth's climate system 
    (including the atmosphere and the oceans), the full effects of added 
    greenhouse gases are not likely to be felt until many decades after 
    their release into the atmosphere. Once these effects are felt, 
    reversing them will take centuries. Thus, policy decisions in the near 
    term have long-term consequences.
        Global warming is expected to have far-reaching effects both 
    domestically and internationally. Changes in precipitation and 
    increased evaporation from higher temperatures could affect water 
    supplies and water quality, posing threats to hydropower, irrigation, 
    fisheries, and drinking water. In the U.S., floods and droughts will 
    probably occur more often because of an intensification of the 
    hydrologic cycle.
        The IPCC report projects that sea level will rise by about 50 cm by 
    2100, using a mid-range emissions scenario and best-estimate values of 
    climate sensitivity and ice-melt sensitivity to warming. Such a rise 
    could inundate more than 5,000 square miles of land in the U.S. if no 
    protective actions are taken. Low-lying areas on the U.S. Atlantic and 
    Gulf coasts are especially at risk. Internationally, parts of many low-
    lying areas such as parts of the Maldives, Egypt, and Bangladesh could 
    be completely inundated and made uninhabitable by a similar sea level 
    rise.
        Climate change could also have direct impacts on human health. 
    Global warming may shift the range of infectious diseases, increasing 
    the risks of malaria and dengue fever in the United States. Changing 
    temperatures and precipitation patterns may produce new breeding sites 
    for pests and pathogens. In addition, climate change is likely to 
    increase deaths from heat stress.
        Agriculture would also be affected, as large areas of the eastern 
    and central U.S. are expected to become drier as the earth warms. 
    Although changes in management practices and technological advances 
    might reduce many of the potentially negative effects of climate change 
    in agriculture, such changes would be expensive. Agricultural 
    production in developing countries is likely to be more vulnerable to 
    climate change, given that they have fewer economic resources.
        Finally, climate change could profoundly affect natural habitats 
    and wildlife. Temperature changes of the magnitude expected from the 
    enhanced greenhouse effect have occurred in the past, but the previous 
    changes took place over centuries or millennia, whereas those expected 
    from increased greenhouse gases will take place over decades. For 
    example, the ideal range for some North American forest species may 
    shift as much as 300 miles to the north over the next several decades. 
    Rates of natural migration and adaptation of species and communities 
    appear to be much slower than the predicted rate of climate change. As 
    a result, populations of many species and inhabited ranges could change 
    as the climate to which they are adapted effectively shifts northward 
    or to higher elevations.
    b. Current Practices and Controls
        Under the SNAP program, HFCs (either pure or in blends) have been 
    approved for use in almost every major air-conditioning and 
    refrigeration end-use, including household refrigerators, motor vehicle 
    air conditioners, retail food refrigeration, comfort cooling chillers, 
    industrial process refrigeration, and refrigerated transport. HFC 134a 
    in particular has claimed a large share of the market for non-ozone-
    depleting substitutes in these applications. Given this range of 
    applications, HFCs have the potential to come into contact with 
    consumers, workers, the general population, and the environment.
        EPA has approved PFCs for use in relatively few end-uses because of 
    their large global warming potentials and long atmospheric lifetimes. 
    These end-uses include uranium isotope separation, for which no other 
    substitute refrigerant has been found, and some heat-transfer 
    applications. In these applications, PFCs may come into contact with 
    workers, the general population, and the environment.
        Analyses performed for both this rule and the SNAP rule indicate 
    that existing regulatory requirements and industry practices are likely 
    to keep the exposure of consumers, workers, and the general population 
    to HFCs and PFCs below levels of concern (although recycling 
    requirements would reduce still further the probability of significant 
    exposure) (U.S. EPA. 1994. Risk Screen on the Use of Substitutes for 
    Class I Ozone-Depleting Substances: Refrigeration and Air Conditioning, 
    Office of Air and Radiation, March 15, 1994. Office of Air and 
    Radiation, March 15,1994, and Regulatory Impact Analysis for the 
    Substitutes Recycling Rule, Office of Air and Radiation, 1998). 
    However, these requirements and practices do not
    
    [[Page 32050]]
    
    address release of HFCs or PFCs to the wider environment.
        For example, ASHRAE Standard 15 4 requirements for 
    equipment with large charge sizes are likely to limit the exposure of 
    building occupants and workers to HFC and PFC refrigerants, but will 
    not necessarily reduce releases to the outdoors. Under ASHRAE 15, 
    equipment containing large charges of HFCs or PFCs (or HCFCs or CFCs) 
    must be located in a machinery room that meets certain requirements. 
    These include requirements for tight-fitting, outward-opening doors, 
    refrigerant detectors that actuate alarms when refrigerant levels rise 
    above recommended long-term exposure levels, and mechanical ventilation 
    that discharges to the outdoors. However, ASHRAE 15 does not include 
    requirements for refrigerant recycling.5 In general, ASHRAE 
    15 addresses design specifications rather than service and disposal 
    practices such as recycling, and ASHRAE 15 requirements are codified 
    and enforced by state or local building code agencies rather than by 
    contractor or technician licensing boards.
    ---------------------------------------------------------------------------
    
        \4\ ASHRAE 15, Safety Code for Mechanical Refrigeration, is an 
    industry standard developed by the American Society of Heating, 
    Refrigerating, and Air-Conditioning Engineers. ASHRAE 15 forms the 
    basis for state and local building codes throughout the U.S.
        \5\ ASHRAE Guideline 3 recommends recycling of all fluorocarbon 
    refrigerants, but is not codified or enforced by any governmental 
    agency.
    ---------------------------------------------------------------------------
    
        Similarly, the American Industrial Hygiene Association (AIHA) has 
    developed exposure limits for HFCs. These may be referenced by OSHA 
    under its general duty clause to compel employers to protect employees 
    from identified health hazards. However, local exhaust ventilation 
    rather than recycling may be used to minimize exposures during service 
    and disposal operations that involve significant releases of 
    refrigerant. This will reduce worker exposure to the refrigerant, but 
    will not reduce the exposure of the general environment.
        Finally, many of the statutory and regulatory mechanisms that limit 
    release of other substitutes such as ammonia do not apply to HFCs or 
    PFCs. HFCs and PFCs are not listed chemicals for SARA Title III or 
    CERCLA reporting requirements; nor are they listed as EPA section 
    112(r) hazardous air pollutants.
    c. Conclusion
        Given the high global warming potentials of HFCs and PFCs and the 
    fact that no authority other than section 608(c)(2) currently controls 
    their release from appliances into the environment, EPA is not 
    proposing to find that the release of HFCs and PFCs does not pose a 
    threat to the environment. 6
    ---------------------------------------------------------------------------
    
        \6\ In 1995, a modeling study indicated that trifluoroacetic 
    acid (TFA), a breakdown product of HFC 134a, might accumulate and 
    concentrate in urban wetlands with high evaporation rates. EPA is 
    monitoring the research in this area. To the extent that TFA 
    formation and concentration pose a threat to the environment, 
    recycling requirements for HFC 134a will address this threat as well 
    as the threat from global warming related to HFC 134a.
    ---------------------------------------------------------------------------
    
        EPA's consideration of global warming potential in determining 
    whether to exempt refrigerants from the venting prohibition of 
    608(c)(2) is supported by precedent under the Title VI regulatory 
    program, Presidential directive, and the legislative history of section 
    608. First, EPA has specifically considered the global warming 
    potential of substitutes in determining whether they are acceptable for 
    various end uses under the Significant New Alternatives Program (SNAP) 
    that implements section 612.7 As stated in the final SNAP 
    rule (59 FR 13049, March 18, 1994), EPA believes that ``overall risk'' 
    includes global warming potential. Second, in October 1993, the 
    President directed EPA through the Climate Change Action Plan (CCAP) to 
    work with manufacturers, sellers, and users of PFCs and HFCs to 
    minimize emissions of these substances.
    ---------------------------------------------------------------------------
    
        \7\ Note that a finding under section 612 that a substitute is 
    acceptable for use in a closed refrigeration system is different 
    from a finding under section 608(c)(2) that the release of that 
    substitute does not pose a threat to the environment. Thus, 
    substances that have been approved under SNAP for use as 
    refrigerants may nevertheless be subject to the venting prohibition 
    of 608(c)(2).
    ---------------------------------------------------------------------------
    
        Third, the legislative history of section 608(c)(2) indicates that 
    Congress specifically intended that EPA consider the global warming 
    potential of substitute refrigerants in determining whether to exempt 
    them from the venting prohibition. In a statement read into the record 
    shortly before passage of the Clean Air Act Amendments of 1990, 
    Senators Chafee and Baucus, the Senate managers of the bill, stated 
    that ``(section 608(c)(2)) is an important provision because many of 
    the substitutes being developed * * * are `greenhouse gases' and have 
    radiative properties that are expected to exacerbate the problem of 
    global climate change.'' The Senators specifically directed that 
    ``(t)he Administrator shall consider long term threats, such as global 
    warming, as well as acute threats (in making the determination under 
    608(c)(2))'' (Cong. Rec. S 16948 (Oct. 27, 1990)). EPA believes that in 
    light of this legislative history, the precedents cited above, and the 
    expected effects of global warming, it would be very difficult to 
    justify exempting HFCs or PFCs from the venting prohibition of 
    paragraph 608(c)(2) on the basis that their release does not pose a 
    threat to the environment.
    3. Chemically Active Common Gases
        The two chemically active common gases used as refrigerants are 
    ammonia and chlorine.
    a. Potential Environmental Impacts
    i. Toxicity and Flammability
        Ammonia can pose a human health hazard through either inhalation or 
    ingestion. It is irritating at relatively low concentrations, and 
    disabling (and possibly deadly) at higher concentrations. Ammonia can 
    also pose a hazard to aquatic organisms if it is discharged to surface 
    waters at high concentrations.
        Ammonia is classified as a B2 refrigerant under ASHRAE 34, 
    indicating that it is toxic at relatively low concentrations and 
    flammable at relatively high concentrations. Toxicity reference values 
    that have been established for ammonia include a Permissible Exposure 
    Limit (PEL) of 50 ppm, a Threshold-Limit Value (TLV) and a Recommended 
    Exposure Limit (REL) of 25 ppm, a Short-term Exposure Limit (STEL) of 
    35 ppm, and an Immediately Dangerous to Life and Health (IDLH) value of 
    500 ppm.8
    ---------------------------------------------------------------------------
    
        \8\ PELs are established by OSHA, TLVs and STELs by the American 
    Congress of Governmental Industrial Hygienists, and RELs and IDLHs 
    by the National Institute of Occupational Safety and Health (NIOSH). 
    PELs and TLVs are 8=hour time-weighted averages (TWAs).
    ---------------------------------------------------------------------------
    
        Chlorine gas is highly toxic. Inhalation of chlorine gas at high 
    concentrations can cause pulmonary edema, cardiac arrest, and 
    inflammation of the larynx. Exposure to concentrations of chlorine 
    below 5 ppm can irritate mucous membranes, the respiratory tract, and 
    skin, and can cause headaches, nausea, blister formation, vomiting and 
    reduced pulmonary function. Toxicity Reference Values that have been 
    established for chlorine gas include a PEL of 1 ppm, a TLV of 0.5 ppm, 
    a STEL of 1 ppm, and an IDLH of 30 ppm. ASHRAE 34 has not classified 
    chlorine.
        Chlorine is non-combustible in air, but most combustible materials 
    will burn in chlorine as they do in oxygen.
    ii. Long-Term Environmental Impacts
        Ammonia is a naturally occurring compound, and is a central 
    compound in the environmental cycling of nitrogen. In surface water, 
    groundwater, or sediment, ammonia will undergo sequential 
    transformation by two
    
    [[Page 32051]]
    
    processes in the nitrogen cycle, nitrification and denitrification, 
    eventually leading to the production of elemental nitrogen.
        Ammonia can also undergo volatilization or ionization. If released 
    to surface water, ammonia may volatilize to the atmosphere. The rate of 
    volatilization decreases as pH and temperature decrease. The toxicity 
    of ammonia to aquatic organisms (fish are especially vulnerable) also 
    decreases with pH. In addition to its direct effects, ammonia can 
    indirectly cause in-stream toxicity through its contribution to 
    eutrophication and its effect on biological oxygen demand.
        Because chlorine used as a refrigerant is typically recaptured or 
    chemically transformed rather than released, its environmental fate 
    will not be discussed here.
        Ammonia and chlorine have GWPs of 0.
    b. Current Practices and Controls
        When refrigeration technology was first developed, ammonia was one 
    of the first refrigerants to gain acceptance. It is now used almost 
    exclusively in industrial process refrigeration systems in the meat 
    packing, dairy, frozen juice, brewery, cold storage, and other food 
    industries. In these applications, ammonia may come into contact with 
    workers, the general population, and the environment. (Ammonia is also 
    used with water in small absorption refrigeration units. However, while 
    ammonia could conceivably come into contact with consumers in this 
    application, these exposures are likely to be of little concern because 
    the charge is small and is mixed with water, limiting release to the 
    air.) Additional exposures to ammonia may occur from its use in non-
    refrigerant applications, such as fertilizer and common household 
    cleaner, but these exposures will not be discussed here except as a 
    context for refrigerant-related exposures.
        Due to its high toxicity, chlorine has not been submitted or 
    approved for use as a refrigerant except in industrial processes 
    involved in chlorine manufacture. In this application, chlorine could 
    come into contact with workers, the general population, and the 
    environment.
        Analyses performed for both this rule and the SNAP rule (RIA and 
    Risk Screen) indicate that regulatory requirements and industry 
    practices are likely to keep the exposure of workers, the general 
    population, and the environment to ammonia and chlorine below levels of 
    concern.
        Occupational exposure to ammonia is primarily controlled by OSHA 
    requirements and national and local building and fire codes. As 
    mentioned above, OSHA has established a PEL for ammonia of 50 ppm. This 
    is an enforceable standard that can be met through containment, safe 
    disposal, ventilation, and/or use of personal protective equipment. 
    OSHA also has requirements in place to prevent catastrophic releases, 
    including the Hazardous Waste Operations and Emergency Response 
    Standard (HAZWOPER), the Hazard Communication Standard, and Process 
    Safety Management (PSM) regulations. (PSM regulations cover systems 
    containing more than 10,000 pounds of ammonia.) These standards require 
    employee training, emergency response plans, and written standard 
    operating procedures.
        ASHRAE 15 (and state and local codes based on it) imposes strict 
    quantity limits for direct-type ammonia refrigeration systems (which 
    possess no secondary, heat transfer fluid), and prohibits the use of 
    ammonia altogether in direct-type comfort cooling systems. Indirect 
    type ammonia refrigeration and air-conditioning systems (which possess 
    a secondary, heat transfer fluid) must be housed in a separate 
    mechanical equipment room. This equipment room must meet the 
    requirements listed above for HFC equipment rooms and must also meet 
    several fire-proofing requirements.
        Releases of ammonia to the wider environment are addressed by 
    several authorities. CERCLA and SARA require reporting of accidental 
    and intentional releases of ammonia to the atmosphere. (Under CERCLA 
    section 103 and SARA Title III Section 304, releases of more than 100 
    pounds of ammonia must be reported immediately, unless they are 
    ``Federally permitted'' such as through National Pollutant Discharge 
    Elimination System (NPDES), State Implementation Plans (SIPs), etc. In 
    that case, however, they are controlled under the permitting authority.
        The more common method of ammonia disposal is to mix the ammonia 
    into water, which absorbs about a pound of ammonia per gallon of water, 
    and then to dispose of the water/ammonia solution. Releases of ammonia 
    to surface waters are governed by permits issued by states (or, in some 
    cases, by EPA Regional Offices) to publicly owned treatment works 
    (POTWs) under NPDES. NPDES permits must include conditions necessary to 
    meet applicable technology-based standards and water quality standards. 
    Water quality standards established by states consist of a designated 
    use for the waters in question, water quality criteria specifying the 
    amount of various pollutants that may be present in those waters and 
    still allow the waters to meet the designated use, and anti-degradation 
    policies.
        Entities that discharge to a POTW (usually through a municipally-
    owned sewer system) must themselves comply with Clean Water Act pre-
    treatment requirements, which may include categorical pretreatment 
    standards on an industry-by-industry basis as well as local limits 
    designed to prevent interference with the biological processes of the 
    treatment plant (or pass through of pollutants). Notification and 
    approval requirements enable POTWs to manage the treatment process, to 
    avoid ammonia overloading, and to protect the treatment processes, 
    collection systems, and facility workers. The POTW typically considers 
    a number of factors before granting discharge approval for ammonia, 
    including the POTW plant's treatment capacity, existing industry 
    discharge patterns, the impact on the POTW's biological treatment 
    processes, the effect on the sewage collection systems (i.e., sewer 
    lines), and the possible hazards to workers at the plant or in the 
    field. The POTW also considers the possibility that ammonia disposed 
    from refrigeration systems may largely be converted to other forms of 
    nitrogen (e.g., nitrates) before arriving at the POTW facility. In 
    general, ammonia from refrigerant uses makes up a small percentage of 
    the ammonia treated by the POTW.
        Ammonia is also listed as a regulated substance for accidental 
    release prevention in the List of Substances and Thresholds rule (59 FR 
    4478, January 31, 1994) promulgated under section 112(r) of the Act. 
    This rule states that if a stationary source handles more than 10,000 
    pounds of anhydrous ammonia (or 20,000 pounds of 20% or greater aqueous 
    ammonia) in a process, it is subject to chemical accident prevention 
    regulations promulgated under section 112(r). These regulations, which 
    were published on June 20, 1996 (61 FR 31668), require stationary 
    sources to develop and implement a risk management program that 
    includes a hazard assessment, an accident prevention program (including 
    training and the development of standard operating procedures), and an 
    emergency response program. In addition, section 112(r)(1) of the Act 
    states that companies have a general duty to prevent accidental 
    releases of extremely hazardous substances, including ammonia and 
    chlorine.
        Exposures to chlorine are controlled through many of the same 
    regulatory mechanisms that control exposures to ammonia, except 
    enforceable
    
    [[Page 32052]]
    
    concentration and release limits are lower for chlorine than for 
    ammonia. For instance, the OSHA PEL for chlorine is 1 ppm, compared to 
    50 ppm for ammonia. Similarly, the reporting threshold under CERCLA 
    section 103 and SARA Title III for chlorine releases is ten pounds, 
    compared to 100 pounds for ammonia; and the quantity of chlorine that 
    triggers requirements under section 112(r) of the Clean Air Act is 
    2,500 pounds per process.
        In addition to these requirements, chlorine is also subject to 
    restrictions under section 112(b) and 113 of the Clean Air Act (CAA). 
    Chlorine is listed as a Hazardous Air Pollutant (HAP) under section 
    112(b) of the CAA, and under section 113 of the CAA, criminal penalties 
    can be assessed for negligently releasing HAPs into the atmosphere.
        EPA is currently investigating whether there are any chlorine 
    sources that are ``major sources'' under CAA section 112(a). A 
    ``major'' source is one that releases more than 10 tons per year of any 
    given HAP, or 25 tons per year or more of any combination of HAPs. Such 
    sources would be regulated under a National Emissions Standard for 
    Hazardous Air Pollutants (NESHAP). Because chlorine emissions are 
    currently well controlled during chlorine manufacture, no manufacturer 
    emits more than 10 tons per year of chlorine.
        Current industry practices and engineering controls in chlorine 
    manufacture will be applied to the use of chlorine as a refrigerant, 
    minimizing potential releases and exposures. These practices and 
    controls include use of system alarms that activate at chlorine 
    concentrations of 1 ppm, use of self-contained breathing apparatus 
    during servicing, isolation of liquid chlorine in receivers during 
    servicing, and use of a caustic scrubber to neutralize gaseous chlorine 
    during servicing. The anticipated charge sizes in the refrigeration 
    system are several hundred times smaller than the quantity of chlorine 
    in the process stream and bulk storage, and chlorine emissions from the 
    refrigeration system are likely to be significantly smaller than those 
    emanating from the process and storage systems, which are already well 
    controlled for safety and health reasons.
    c. Conclusion
        Because releases of ammonia and chlorine from their currently 
    approved refrigeration applications are adequately addressed by other 
    authorities, EPA is proposing to find that the release of ammonia and 
    chlorine refrigerants during the servicing and disposal of appliances 
    in these applications does not pose a threat to the environment under 
    section 608. EPA requests comment on this proposed finding and on the 
    rationale behind it.
    4. Hydrocarbons
    a. Potential Environmental Impacts
    i. Toxicity and Flammability
        Hydrocarbons, including propane, propylene, and butane, are 
    classified as A3 refrigerants by ASHRAE Standard 34, indicating that 
    they have low toxicity and high flammability. Like CFCs, HCFCs, and 
    HFCs, they can displace oxygen at high concentrations and cause 
    asphyxiation. Toxicity reference values that have been established for 
    hydrocarbons include a PEL for propane of 1,000 ppm, and IDLHs of 
    20,000 ppm and 50,000 ppm for propane and butane respectively.
    ii. Long-Term Environmental Impacts
        Hydrocarbons are volatile organic compounds (VOCs) and therefore 
    contribute to ground-level ozone (smog) formation. Because ozone is a 
    greenhouse gas, hydrocarbons contribute slightly and indirectly to 
    global warming. They do not deplete stratospheric ozone.
    b. Current Practices and Controls
        EPA has approved hydrocarbons under the SNAP program only for use 
    in industrial process refrigeration systems used for hydrocarbon 
    manufacture. In this application, hydrocarbons have the potential to 
    come into contact with workers, the general population, and the 
    environment. However, analyses performed for both this rule and the 
    SNAP rule indicate that existing regulatory requirements and industry 
    practices adequately protect workers, the general population, and the 
    environment from exposure to hydrocarbon refrigerants.
        As is the case for ammonia and chlorine, occupational exposures to 
    hydrocarbons are primarily controlled by OSHA requirements and national 
    and local building and fire codes. As noted above, OSHA has established 
    a PEL for propane of 1,000 ppm, and NIOSH has established IDLHs of 
    20,000 ppm and 50,000 ppm for propane and butane respectively. The PEL 
    is an enforceable standard, and the IDLHs trigger OSHA personal 
    protective equipment requirements. OSHA's Process Safety Management, 
    confined space entry, and HAZWOPER requirements apply to all 
    hydrocarbon refrigerants. These requirements include employee training, 
    emergency response plans, air monitoring, and written standard 
    operating procedures.
        ASHRAE 15 prohibits the use of hydrocarbon refrigerants except in 
    laboratory and industrial process refrigeration applications. 
    Refrigeration machinery must be contained in a separate mechanical 
    equipment room that complies with the requirements for HFC equipment 
    rooms and also complies with several fire-proofing requirements.
        As is the case for ammonia and chlorine, certain hydrocarbons 
    (including butane, cyclopropane, ethane, isobutane, methane, and 
    propane) are listed as regulated substances for accidental release 
    prevention under regulations promulgated under section 112(r) of the 
    Clean Air Act. In addition, hydrocarbons are considered VOCs, and are 
    therefore subject to state VOC regulations implemented in accordance 
    with the Clean Air Act. The regulatory status of new VOC sources is 
    based on area ground-level ozone classifications. Although states and 
    industry have various options regarding the permitting of new VOC 
    sources, industry typically must implement technologies that provide 
    lowest achievable emissions rates, and must offset new VOC 
    contributions through reductions in existing sources.
        According to industry and OSHA representatives, current industry 
    service practices for hydrocarbon refrigeration equipment include 
    monitoring efforts, engineering controls, and operating procedures. 
    System alarms, flame detectors, and fire sprinklers are used to protect 
    process and storage areas. Fugitive emissions monitoring is routinely 
    conducted. If a leak is found, repairs are attempted within five days. 
    If initial repair attempts are unsuccessful, the system is shut down, 
    unless releases from a shutdown are predicted to be greater than 
    allowing a continued leak. During servicing, OSHA confined space 
    requirements are followed, including continuous monitoring of explosive 
    gas concentrations and oxygen levels. Hydrocarbon refrigerants may be 
    returned to the product stream or can be released through a flare 
    during servicing. Due to fire and explosion risks and the economic 
    value of the hydrocarbon, direct venting is not a widely used 
    procedure. In general, hydrocarbon emissions from refrigeration systems 
    are likely to be significantly smaller than those emanating from the 
    process and storage systems, which are already well-controlled for 
    safety reasons.
    
    [[Page 32053]]
    
    c. Conclusion
        Because the release of hydrocarbons from industrial process 
    refrigeration systems appears to be adequately addressed by other 
    authorities, EPA is proposing to find that the release of hydrocarbon 
    refrigerants during the servicing and disposal of such systems does not 
    pose a threat to the environment under section 608. EPA requests 
    comment on this proposed finding and on the rationale behind it.
    5. Inert Atmospheric Constituents
        EPA has approved CO2 under SNAP as a replacement for 
    CFC-13, R-13B1 and R-503 in very low temperature and industrial process 
    refrigeration applications, and as a substitute for CFC-113, CFC-114, 
    and CFC-115 in non-mechanical heat transfer applications. 
    CO2 is a well-known, nontoxic, nonflammable gas. Its GWP is 
    defined as 1, and all other GWPs are indexed to it. EPA's understanding 
    is that CO2 is readily available as a waste gas, and 
    therefore no additional quantity of the chemical needs to be produced 
    for refrigeration applications. Thus, the use of such commercially 
    available CO2 as a refrigerant does not contribute to global 
    warming, and release of such CO2 from appliances has no net 
    contribution to global warming. On this basis, EPA proposes to find 
    that release and disposal of CO2 refrigerant during the 
    servicing and disposal of appliances does not pose a threat to the 
    environment under section 608. EPA requests comment on the factual 
    basis for this proposal.
        EPA has approved direct nitrogen expansion as an alternative 
    technology for many CFCs and HCFCs used in vapor compression systems. 
    Nitrogen is a well-known, nontoxic, nonflammable gas that makes up 78% 
    of Earth's atmosphere. Nitrogen contributes neither to global warming 
    nor to ozone-depletion. EPA therefore proposes to find that the release 
    and disposal of elemental nitrogen during the servicing and disposal of 
    appliances does not pose a threat to the environment.
        EPA has approved evaporative cooling as an alternative technology 
    to motor vehicle air conditioners using CFC-12. Evaporative cooling 
    operates simply through the evaporation of water to the atmosphere. 
    Water released from evaporative cooling is nontoxic and contributes 
    neither to ozone depletion nor to global warming. EPA therefore 
    proposes to find that the release and disposal of water during the 
    servicing and disposal of appliances does not pose a threat to the 
    environment.
    
    IV. The Proposed Rule
    
    A. Definitions
    
    1. Appliance
        EPA is proposing to amend the current definition of ``appliance'' 
    to include air-conditioning and refrigeration equipment that contains 
    substitutes for class I and class II substances, as well as equipment 
    that contains class I and class II substances. This amendment is 
    consistent with the definition of ``appliance'' in section 608(c)(2), 
    which states, ``[f]or purposes of this paragraph, the term 'appliance' 
    includes any device which contains and uses as a refrigerant a 
    substitute substance and which is used for household or commercial 
    purposes, including any air conditioner, refrigerator, chiller, or 
    freezer.'' EPA proposes to continue to interpret ``appliance'' to 
    include all air-conditioning and refrigeration equipment except that 
    designed and used exclusively for military applications. Thus, the term 
    ``appliance'' would include household refrigerators and freezers (which 
    may be used outside the home), other refrigeration appliances, 
    residential and light commercial air conditioning, motor vehicle air 
    conditioners, comfort cooling in vehicles not covered under section 
    609, and industrial process refrigeration.
        a. Inclusion of Heat Transfer Devices in the Term ``Appliance''. A 
    manufacturer of PFCs has submitted comments requesting that EPA exclude 
    non-mechanical heat transfer applications from the definition of 
    appliance. The manufacturer maintained that ``heat transfer does not 
    involve the use of a refrigerant under the accepted technical 
    definitions of this term,'' and cited the technical definition of 
    refrigerant in the ASHRAE handbook as ``the working fluid in a 
    refrigeration cycle, absorbing heat from a reservoir at low temperature 
    and rejecting heat at a higher temperature.'' In addition, the 
    manufacturer stated that heat transfer applications are such a small 
    segment of the ODS replacement market that they should be exempt from 
    regulation on de minimis grounds. Citing the Alabama Power Co. v. 
    Costle decision (636 F.2d 323, DC Cir 1979), the commenter argued that 
    EPA may make such exemptions ``if it finds (1) that Congress was not 
    extraordinarily rigid in drafting section 608, and (2) that the burdens 
    associated with regulating the de minimis categories yield trivial 
    benefits.'' Finally, the manufacturer requested that if EPA does decide 
    to continue to consider heat transfer applications appliances, EPA 
    adopt a unique approach to these systems, as they differ physically 
    from ``traditional'' air-conditioning and refrigeration systems. 
    (``Issues Associated with Extending Regulations Under Section 608 to 
    ODS Substitutes Used in Heat Transfer Applications,'' Michael I. 
    Dougherty and Larry G. Headrick, 3M Specialty Chemicals Division, 
    September 5, 1995).
        In the past, EPA has considered non-mechanical heat transfer 
    applications that use the heat transfer fluid as the primary 
    refrigerant to be appliances. In an applicability determination issued 
    on June 6, 1993, EPA determined that electrical transformers containing 
    CFC-113 were appliances because the 113 ``acts to transport heat out of 
    the transformer.'' The determination stated further that ``(t)he fact 
    that the transport of heat is accomplished without the use of 
    compressors or expansion valves does not alter the role of the CFC-113 
    which acts as a coolant.'' Moreover, under the Significant New 
    Alternatives Program, EPA has classified non-mechanical heat transfer 
    applications as part of the refrigeration and air-conditioning major 
    industrial use sector.
        EPA does not see any legal, technical, or environmental 
    justification for reversing these findings, although EPA is requesting 
    comment on the option of adopting unique requirements under section 608 
    for non-mechanical heat transfer applications. As noted above, the 
    fundamental cooling function of the heat transfer fluid is not changed 
    because a compressor is not involved. While one technical definition of 
    ``refrigerant'' may refer only to moving heat from low-to high-
    temperature regions, commonly accepted dictionary definitions of 
    ``refrigerant'' and ``refrigerate'' refer generally to making or 
    keeping things cool.9 Neither the statute nor its 
    legislative history indicate that Congress intended the term to be more 
    restrictive in the statute than it is in common use.
    ---------------------------------------------------------------------------
    
        \9\ The Random House College Dictionary defines ``refrigerate'' 
    as ``to make or keep cold or cool, as for preservation,'' and 
    ``refrigerant'' as ``a substance used as an agent in cooling or 
    refrigeration.'' Webster's Ninth New Collegiate Dictionary defines 
    ``refrigerate'' as ``to make or keep cold or cool,'' and 
    ``refrigerant'' as ``a substance used in refrigeration.''
    ---------------------------------------------------------------------------
    
        Given that heat transfer applications are appliances, EPA does not 
    believe that it would be appropriate to exempt some or all of these 
    applications from recycling requirements because they consume a small 
    quantity of refrigerant relative to other appliance types. The 
    commenter states that de minimis exemptions are permissible where 
    Congress has not been ``extraordinarily
    
    [[Page 32054]]
    
    rigid,'' and maintains that section 608 gives the Agency flexibility to 
    exercise its discretion in this area. In support of this argument, the 
    commenter cites the explicit exemptions in section 608(c) for (1) de 
    minimis releases associated with good faith attempts to recover and 
    recycle, and (2) releases of ODS substitutes that do not pose a threat 
    to the environment.
        However, the legislative history of section 608 indicates that 
    Congress intended both of these exemptions to be interpreted narrowly. 
    As noted above, the Senate managers of the CAA bill specifically 
    identified releases of substitutes with high global warming potential 
    as a ``threat to the environment,'' and PFCs have among the highest 
    global warming potentials of any refrigerants. The Senate managers also 
    read the following statement into the record regarding the explicit 
    exemption for de minimis releases:
    
        Exceptions to this provision are included for certain de minimis 
    releases. As used in this context, de minimis refers to extremely 
    small amounts. The fact that de minimis, in other contexts under 
    this Act, may be as much as several tons is not relevant nor 
    controlling in this context. Most appliances contain only a few 
    ounces of class I or class II refrigerant. Interpreting de minimis 
    to mean anything other than an extremely small amount would render 
    this provision a nullity. The exception is included to account for 
    the fact that in the course of properly using recapture and 
    recycling equipment, it may not be possible to prevent some small 
    amount of leakage (Cong. Rec. S 16948 (Oct. 27, 1990)).
    
    Thus, both the statute and the legislative history clearly limit the 
    applicability of the de minimis exemption to those releases that 
    unavoidably occur during the course of recycling. The de minimis 
    exemption is not intended to exempt any sector from recycling 
    requirements; indeed, the Senate managers specifically proscribe a 
    broad interpretation of de minimis, noting that it would ``render 
    (section 608(c)) a nullity.''
        Furthermore, Congress' explicit provision of a sharply limited 
    exemption from section 608(c) for de minimis releases associated with 
    good faith efforts to recapture and recycle or safely dispose of a 
    substitute undermines the argument that EPA has an understood authority 
    to grant a much broader de minimis exemption under Alabama Power Co. v. 
    Costle. Congress has specifically addressed the scope of possible 
    exemptions from section 608(c) and declared this scope quite limited. 
    Consequently, EPA has included both small appliances (which 
    individually have very small charge sizes) and very high-pressure 
    appliances (which collectively consume only a small percentage of 
    refrigerants) in the scope of the section 608 recycling requirements.
        Moreover, EPA does not believe that the regulation of releases of 
    PFCs used as heat transfer fluids meets either of the criteria 
    established by the court in Alabama Power for finding an implied 
    authority to allow a de minimis exemption. De minimis authority may be 
    implied where ``the burdens of regulation yield a gain of trivial or no 
    value.'' Alabama Power at 360-61. First, EPA does not consider the 
    benefits of this proposed regulation to be ``trivial.'' The commenter 
    estimates potential annual consumption of PFC heat transfer fluids to 
    be 580,000 pounds, or 264 metric tons. If this consumption is weighted 
    by the average 100-year GWP of the PFCs and compared to the consumption 
    of all other refrigerants weighted by the 100-year GWP of HFC-134a, it 
    makes up 1.5 percent of total refrigerant consumption in the 
    U.S.10 If the PFC consumption and other refrigerant 
    consumption are weighted by their 500-year GWPs, the PFCs make up 7.2 
    percent of total U.S. refrigerant consumption.
    ---------------------------------------------------------------------------
    
        \10\ This figure is based on the commenter's projection of PFC 
    heat transfer fluid consumption and EPA's estimate of U.S. 
    consumption of CFC and HCFC refrigerants in 1992.
    ---------------------------------------------------------------------------
    
        Second, the commenter does not demonstrate that recycling PFC heat 
    transfer fluids would impose significant burdens. While the unique 
    characteristics and applications of heat transfer appliances may 
    warrant specialized recycling requirements, they do not render 
    recycling impracticable or even extraordinarily difficult. Indeed, the 
    commenter notes that PFC heat transfer fluids are already subject to 
    use restrictions under the SNAP program that require recycling during 
    the servicing and disposal of equipment, and observes that total losses 
    from heat transfer equipment are currently less than 10 percent per 
    year. Moreover, heat transfer applications using CFCs and HCFCs have 
    clearly been subject to section 608 requirements since the 
    applicability determination on electrical transformers was issued in 
    June, 1993. Since EPA has not received any information indicating that 
    users of these applications have been unable to comply, and since PFCs 
    were selected as substitutes for CFCs and HCFCs in these applications 
    precisely because they have similar physical characteristics, there is 
    no reason to believe that recycling PFCs in these applications will be 
    difficult. Thus, EPA is not proposing to exempt heat transfer 
    applications from the requirements of this proposed rule.
        b. Coverage of One-Time Expansion Devices. Similarly, EPA believes 
    that one-time expansion devices are appliances, and that the release of 
    refrigerants from one-time expansion devices is prohibited by section 
    608(c)(2), unless EPA finds that the release of these refrigerants does 
    not pose a threat to the environment. One-time expansion devices, which 
    include ``self-chilling cans,'' rely on the release and associated 
    expansion of a compressed refrigerant to cool the contents (e.g., a 
    beverage) of a container.
        EPA considers refrigerant release from such devices to be 
    prohibited by section 608(c). First, the refrigerant in these devices 
    acts as a not-in-kind substitute for CFCs and HCFCs in household and 
    commercial refrigerators. Although the refrigerant in a one-time 
    expansion device is not being used in the same system as CFC-12 in a 
    household or commercial refrigerator, it is providing the same effect 
    of cooling the container. EPA has previously considered not-in-kind 
    technologies, such as evaporative cooling, to be substitutes under 
    SNAP. The SNAP regulation defines ``substitute or alternative'' as 
    ``any chemical, product substitute, or alternative manufacturing 
    process, whether existing or new, intended for use as a replacement for 
    a class I or II compound.'' This approach is consistent with the 
    language of section 612 of the Clean Air Act, in which Congress 
    repeatedly identified ``product substitutes'' as substitutes for class 
    I and class II substances. Section 612(a) states the policy of the 
    section: ``To the maximum extent practicable, class I and class II 
    substances shall be replaced by chemicals, product substitutes, or 
    alternative manufacturing processes that reduce overall risks to human 
    health and the environment'' (emphasis added). 11 As stated 
    in the SNAP regulation, EPA has interpreted the phrase ``substitute 
    substances'' in 612(c) to incorporate the general definition of 
    substitute in 612(a) and 612(b) (3) and (4) (59 FR 13050). As noted 
    above, the proposed definition of ``substitute'' in today's document is 
    very similar to that in the SNAP regulations, except the proposed 
    definition omits the proviso that the substitute be intended for use as
    
    [[Page 32055]]
    
    a replacement for a class I or class II substance. Thus, under the 
    proposed definition in today's document, and consistent with the 
    definition in the SNAP regulations and section 612 of the Act, EPA 
    would consider the refrigerant in a one-time expansion device to be a 
    ``substitute substance'' under section 608(c)(2).
    ---------------------------------------------------------------------------
    
        \11\ Section 612(b)(3) directs EPA to ``specify initiatives * * 
    * to promote the development and use of safe substitutes for class I 
    and class II substances, including alternative chemicals, product 
    substitutes, and alternative manufacturing processes'' (emphasis 
    added). Similarly, section 612(b)(4) requires EPA to ``maintain a 
    public clearinghouse of alternative chemicals, product substitutes, 
    and alternative manufacturing processes'' (emphasis added).
    ---------------------------------------------------------------------------
    
        Second, one-time expansion devices, which rely on the release of 
    compressed gases to cool the contents of containers, are encompassed by 
    the term ``appliance.'' A one-time expansion device is a device that 
    holds and uses a substitute substance to make the contents of the 
    container cool for individual consumption. Thus, it is a ``device which 
    contains or uses'' a ``refrigerant'' ``for household or commercial 
    purposes.'' The operating principle of a one-time expansion device, 
    vapor compression and expansion, is the same as that of a traditional 
    refrigerator. The only technological differences between a one-time 
    expansion device and a traditional refrigerator are that, with a one-
    time expansion device, the compression part of the vapor-compression/
    expansion cycle takes place at the factory, and the refrigerant escapes 
    during expansion instead of being cycled back to a compressor to be 
    recompressed.
        Third, EPA believes that the opening of a one-time expansion device 
    constitutes disposal of the device. This interpretation is consistent 
    with the definition of ``disposal'' included in the recycling 
    regulations for CFCs and HCFCs at Sec. 82.152. ``Disposal'' is the 
    process leading to and including:
        (1) The discharge, deposit, dumping or placing of any discarded 
    appliance into or on any land or water;
        (2) The disassembly of any appliance for discharge, deposit, 
    dumping or placing of its discarded component parts into or on any land 
    or water; or
        (3) The disassembly of any appliance for reuse of its component 
    parts.
        The act of opening a one-time expansion device meets this 
    definition of disposal. Opening the device irreversibly discharges the 
    refrigerant and thereby ends the useful life of the cooling device. 
    Cooling the container is a one-time action that occurs immediately 
    prior to consuming or using its contents, after which the remaining 
    component parts of the appliance will be discarded. In addition, with 
    the irreversible discharge of the critical portion of the cooling 
    device, the appliance has been partially disassembled and one of its 
    component parts has been discharged. Thus, the act of opening the 
    device and cooling the container is a process that leads quickly and 
    inevitably to the final disposal of the appliance, and the act itself 
    includes the permanent disassembly of the appliance and discharge of 
    one of the component parts. Finally, the act of opening the device is a 
    ``knowing'' release of refrigerant, as a person opening the device 
    could not fail to be aware that his or her action is causing release of 
    a gas to the atmosphere.
        Thus, the release occurs in the course of ``maintaining, servicing, 
    repairing, or disposing of an appliance'' and is subject to the venting 
    prohibition. While EPA is proposing to exempt some substitute 
    refrigerants in one-time expansion applications from the section 608 
    requirements because their release does not pose a threat to the 
    environment (see the discussion of CO2 above), EPA does not 
    believe that it can make this finding for the HFC refrigerants that 
    have been suggested for use in one-time expansion devices due to global 
    warming concerns. EPA recognizes that this has the effect of 
    prohibiting the use of HFCs (or other refrigerants whose release EPA 
    does not find does not pose a threat to the environment) in this 
    application. As discussed below, EPA is proposing to use its authority 
    under section 608(c)(2) and section 301(a) to prohibit the manufacture 
    of one-time expansion devices using refrigerants that EPA has not 
    exempted from the venting prohibition.
        c. Secondary Loops. Rather than cooling things or people directly, 
    many refrigeration and air-conditioning systems operate by cooling an 
    intermediate fluid, which is then circulated to the things or people to 
    be cooled. This intermediate fluid (and the structure for transporting 
    it) is referred to as a secondary loop. Secondary loops are commonly 
    used in air conditioners in large buildings,12 in industrial 
    process refrigeration systems, and in some specialty and commercial 
    refrigeration systems.
    ---------------------------------------------------------------------------
    
        \12\ Large building air conditioners are commonly called 
    ``chillers,'' which is short for ``water chillers.'' Most building 
    air conditioners cool water or brine that is then circulated 
    throughout the building.
    ---------------------------------------------------------------------------
    
        There are different types of secondary loops. Interpreted in the 
    broadest sense, secondary loops include, on the one hand, the lower 
    temperature loops of cascade systems, and on the other, the ventilation 
    systems that circulate air that is cooled by an air-conditioner, since 
    both of these types of loops circulate a fluid that is cooled by a 
    primary refrigerant loop. However, these loops differ from each other 
    in a number of ways. The former move heat from cooler to warmer areas, 
    and there is a change of state in the secondary fluid. The latter move 
    heat from warmer to cooler areas (because they return air that is 
    warmed by the inhabitants and equipment in the building), and there is 
    no change of state in the secondary fluid. The type of loop that is 
    most commonly considered a secondary loop falls between these two 
    types, but somewhat closer to air circulation systems: it is a closed 
    loop that circulates a liquid that is cooled by a primary refrigerant 
    loop and that is used to move heat from warmer to cooler areas with no 
    change of state.13
    ---------------------------------------------------------------------------
    
        \13\ The 1997 ASHRAE Handbook, Fundamentals, defines ``secondary 
    coolant'' as ``any liquid cooled by the refrigerant and used to 
    transfer heat without changing state'' (p. 20.1).
    ---------------------------------------------------------------------------
    
        EPA is requesting comment regarding what types of secondary loops 
    should be considered to be part of an ``appliance.'' The definition of 
    ``appliance'' with respect to secondary loops is somewhat ambiguous 
    under Act. Given this ambiguity, Congress has delegated to EPA the 
    authority to interpret ``appliance'' consistent with the language and 
    purpose of section 608. The purpose of section 608 is to reduce 
    emissions of ozone-depleting substances and to ensure that the phaseout 
    of ozone-depleting refrigerants does not result in new environmental 
    problems from emissions of their replacements.
        In defining the boundaries of an appliance, EPA believes that it is 
    appropriate to consider both the proximity of the loop to the primary 
    cooling mechanism and the mode of functioning of the loop (including 
    the direction of heat transfer and whether or not a change of state is 
    involved); otherwise, it may be difficult to draw a clear line between 
    the appliance and its surroundings. For example, a common-sense 
    definition of appliance would probably not include the ventilation 
    system used to circulate cooled air, but, as noted above, such a 
    ventilation system could be considered a secondary loop. In fact, 
    because the transfer of heat from warmer to cooler objects occurs 
    spontaneously, any fluid between the primary loop of an appliance and 
    the things or people cooled could be considered a secondary (or 
    tertiary, etc.) loop. In order to avoid an overly expansive 
    interpretation of ``appliance,'' EPA is proposing to interpret as part 
    of an ``appliance'' refrigerant loops that (1) are primary or (2) move 
    heat from cooler to warmer areas or (3) involve a change of state of 
    the fluid. Under this interpretation, secondary loops that used water, 
    brine, or other materials to transport heat from warmer to cooler areas 
    without a change of state would
    
    [[Page 32056]]
    
    not be considered to be part of an ``appliance.'' On the other hand, 
    cascade system secondary loops that used fluids to transport heat from 
    cooler to warmer areas with a change of state would be considered to be 
    part of an ``appliance.'' EPA believes that this interpretation would 
    cover those secondary loops that are traditionally considered to be 
    part of the air conditioner or refrigerator, while excluding those that 
    are not. In addition, the Agency believes that this interpretation 
    would capture the majority of air-conditioning and refrigerating 
    components that have used ozone-depleting substances in the past.
        This interpretation is also consistent with EPA's decision not to 
    list secondary fluids under SNAP. In that decision, published on March 
    10, 1997, EPA expressed concern that listing secondary fluids could 
    discourage their use and could be very burdensome to the Agency and the 
    regulated community, as the number of secondary fluids is quite large. 
    In addition, the Agency noted that there was little information or data 
    suggesting that the use of these fluids in secondary loops posed an 
    environmental or safety risk (52 FR 10700).
        The Agency requests comment on its interpretation of ``appliance'' 
    as it applies to secondary loops. Specifically, EPA requests comment on 
    whether there are human health or environmental risks that could be 
    significantly reduced by subjecting to the venting prohibition 
    secondary loops that transport heat from warmer to cooler areas without 
    a change of state. Based on information received to date, the Agency 
    believes that most secondary fluids are either environmentally benign 
    or controlled under other authorities. However, if some secondary 
    fluids were neither benign nor adequately controlled under other 
    authorities, EPA could interpret ``appliance'' to include secondary 
    loops and individually exempt fluids whose release did not pose a 
    threat to the environment. In this way, EPA could subject to the 
    venting prohibition only those secondary fluids whose release posed a 
    threat. Given the large number of secondary fluids, however, the Agency 
    is concerned that it would be difficult to identify and list all of the 
    secondary fluids whose release does not pose a threat.
        EPA also requests comment on the extent to which ozone depleting 
    substances such as HCFC-123 are used in secondary loops that transport 
    heat from warmer to cooler areas. EPA believes that such ozone-
    depleting substances should be recovered, given their environmental 
    impact and the availability of equipment and expertise to recover and 
    recycle them. However, to require such recovery, EPA would not 
    necessarily need to define secondary loops as part of an appliance and 
    thereby subject them to the section 608(c) venting prohibition. 
    Instead, the Agency could use its broad authority to minimize emissions 
    and maximize recycling of class I and class II substances under section 
    608(a). EPA requests comment on this approach.
    2. Full Charge
        Compliance with the leak repair requirements requires calculating 
    both the full charge of the appliance and the leak rate. EPA has 
    previously defined full charge at Sec. 82.152 as the amount of 
    refrigerant required for normal operating characteristics and 
    conditions of the appliance as determined by using one or a combination 
    of the four methods specified at Sec. 82.152. Through this action, EPA 
    is proposing to eliminate the phrase ``for the purposes of 
    Sec. 156(i)'' and the word ``all'' from paragraph (2) in the definition 
    of full charge at Sec. 82.152. The definition refers to ``other 
    relevant considerations.'' The term ``all'' is implicit in that 
    language. EPA believes this change will improve the readability of the 
    provision by eliminating redundancy.
    3. High-pressure Appliance
        As discussed below in section IV.B.1.a, EPA is proposing to base 
    evacuation requirements for CFC, HCFC, HFC, and PFC appliances on the 
    saturation pressure of the refrigerant. As part of this approach, EPA 
    is proposing two changes to its definition of high-pressure appliances. 
    One of the changes would modify the system for classifying refrigerants 
    by their saturation pressures. Rather than classifying the refrigerants 
    according to their boiling points at atmospheric pressure, EPA would 
    classify them according to their saturation pressures at 104 degrees F. 
    The other change would split what are currently defined as high-
    pressure appliances into two groups. One group would remain subject to 
    the current requirements for high-pressure CFC and HCFC (except HCFC-
    22) appliances and would continue to be called ``high-pressure 
    appliances.'' The other group would be subject to the current 
    requirements for HCFC-22 appliances and would be called ``higher-
    pressure appliances,'' as described below.
        The proposed revised definition of ``high-pressure appliances'' 
    reads as follows:
        High-pressure appliance means an appliance that uses a refrigerant 
    with a liquid phase 14 saturation pressure between 45 psia 
    and 220 psia at 104 degrees Fahrenheit. This definition includes but is 
    not limited to appliances using R114, R12, R134a, R500, and R401A, B, 
    and C.
    ---------------------------------------------------------------------------
    
        \14\ Zeotropic blends exert different pressures at the same 
    temperature, depending upon the percentage of vapor vs. liquid in 
    the container. For reasons discussed below in section IV.B.1.a., EPA 
    is proposing to classify refrigerants according to their liquid 
    phase saturation pressures at 104 degrees F.
    ---------------------------------------------------------------------------
    
    4. Higher-Pressure Appliance
        As described above, EPA is proposing to create a new category of 
    ``higher-pressure appliances'' whose refrigerants have saturation 
    pressures between 220 psia and 305 psia at 104 degrees F. Appliances in 
    this category would be subject to the current requirements for HCFC-22 
    appliances. The proposed definition of ``higher pressure appliances'' 
    reads as follows:
        Higher-pressure appliance means an appliance that uses a 
    refrigerant with a liquid phase saturation pressure between 220 psia 
    and 305 psia at 104 degrees Fahrenheit. This definition includes but is 
    not limited to appliances using R22, R502, R402A and B, and R407A, B, 
    and C.
    5. Leak Rate
        EPA has not previously promulgated a formal definition for leak 
    rate. Through today's action, EPA is proposing to add a definition for 
    leak rate for the purposes of applying leak repair requirements 
    contained in Sec. 82.156(i). Currently, Sec. 82.156(i) refers to 
    applicable allowable annual leak rates for different appliances. While 
    EPA believes that there is a general understanding on how to calculate 
    leak rates, EPA is proposing to add a specific definition in the 
    regulations for clarity. EPA believes this definition will address some 
    of the issues raised by the Chemical Manufacturers' Association (CMA).
        EPA and CMA jointly issued a compliance guide for leak repair in 
    October 1995. That guide, known as the Compliance Guidance For 
    Industrial Process Refrigeration Leak Repair Regulations Under Section 
    608 of the Clean Air Act (Compliance Guidance), includes a section on 
    calculating leak rates. The Compliance Guidance states that each time 
    the owner or operator adds refrigerant to an appliance normally 
    containing 50 pounds or more of refrigerant, the owner or operator 
    should promptly calculate the leak rate to ensure that the appliance is 
    not leaking at a rate that exceeds the applicable allowable leak rate. 
    If the amount of refrigerant added indicates
    
    [[Page 32057]]
    
    that the leak rate for the appliance is above the applicable allowable 
    leak rate, the owner or operator must perform corrective action by 
    repairing leaks, retrofitting the appliance, or retiring the appliance 
    in accordance with the requirements of Sec. 82.156(i). As noted below, 
    the applicable allowable leak rate for commercial refrigeration and 
    industrial process refrigeration equipment normally containing 50 
    pounds or more of refrigerant is currently 35 percent, but EPA is 
    proposing to lower this for some types of equipment. The applicable 
    allowable annual leak rate for all other appliances normally containing 
    50 pounds or more of refrigerant is currently 15 percent, but again, 
    EPA is proposing to lower this.
        The Compliance Guidance specifically mentions two methods for 
    calculating leak rates. One method for calculating the leak rate is 
    described in the Compliance Guidance as follows:
        (1) Take the number of pounds of refrigerant added to the appliance 
    to return it to a full charge and divide it by the number of pounds of 
    refrigerant the appliance normally contains at full charge;
        (2) Take the number of days that have passed since the last day 
    refrigerant was added and divide by 365 days;
        (3) Take the number calculated in step (1) and divide it by the 
    number calculated in step (2); and
        (4) Multiply the number calculated in step (3) by 100 to calculate 
    a percentage.
        This method is summarized in the following formula:
        [GRAPHIC] [TIFF OMITTED] TP11JN98.000
        
        Because this method takes the quantity of refrigerant (percentage 
    of charge) lost between charges and scales it up or down to calculate 
    the quantity that would be lost over a year-long period, it will be 
    referred to as the ``annualizing method.''
        The second method mentioned in the Compliance Guidance is to 
    calculate the ``rolling average.'' The term ``rolling average'' is not 
    defined in the Compliance Guidance, but EPA believes it is commonly 
    calculated by:
        (1) Summing up the quantity of refrigerant (e.g., pounds) added to 
    the appliance over the previous 365-day period (or over the period that 
    has passed since leaks in the appliance were last repaired, if that 
    period is less than one year),
        (2) Dividing the result of step one by the quantity (e.g., pounds) 
    of refrigerant the appliance normally contains at full charge, and
        (3) Multiplying the result of step two by 100 to obtain a 
    percentage.
        This method is summarized in the following formula:
        [GRAPHIC] [TIFF OMITTED] TP11JN98.001
        
        EPA is considering four options for its formal definition of ``leak 
    rate.'' The first option is to require appliance owners to calculate 
    leak rates using only the ``annualizing'' method. The second option is 
    to require owners to calculate leak rates using only the ``rolling 
    average'' method. The third option is to require owners to calculate 
    leak rates using whichever of the two methods yields the higher 
    calculated leak rate, and the fourth option is to permit owners to 
    calculate leak rates using either method, so long as the same method is 
    always used for the same appliance, facility, or firm.
        EPA believes that there are advantages and disadvantages to each 
    approach. The annualizing method is relatively simple, catches some 
    kinds of leaks more quickly than the rolling average 
    method.15 and does not penalize owners whose appliances leak 
    slowly but show no signs of leakage until a relatively large percentage 
    of the charge has been lost. On the other hand, the annualizing method 
    permits owners whose appliances spring a fast leak after a long period 
    of slow leakage to delay repair, because it permits them to ``dilute'' 
    the true leak rate by averaging the refrigerant loss over more than one 
    year.
    ---------------------------------------------------------------------------
    
        \15\ Suppose a previously leak-tight appliance springs a leak. 
    If the appliance owner is adding less than the applicable allowable 
    percentage of charge and the time since the last recharge is less 
    than one year, the annualizing method will force the owner to repair 
    the leaks before the rolling average method will. If an appliance 
    owner is adding more than the applicable allowable percentage of 
    charge and the time since the last recharge is more than one year, 
    the reverse holds true.
    ---------------------------------------------------------------------------
    
        The rolling average method is relatively simple and catches some 
    kinds of leaks (such as the sudden fast leak described in the previous 
    paragraph) more quickly than the annualizing method. On the other hand, 
    the rolling average method permits owners to delay repair of certain 
    types of leaks longer than the annualizing method, and it may force 
    owners whose appliances actually leak below the applicable leak rate to 
    undertake repair, especially if these owners have no way of recognizing 
    that they have a leak until a relatively large percentage of the charge 
    has been lost.
        Requiring the use of whichever method yields the highest calculated 
    leak rate is a more complicated approach (both for compliance and 
    enforcement) than requiring the use of either method alone, but ensures 
    that leaks are caught as quickly as possible. However, because this 
    approach incorporates the rolling average method, it shares that 
    method's potential to penalize appliance owners whose appliances leak 
    below the applicable leak rate but do not show signs of leakage until 
    they have lost a relatively large percentage of charge.
        Permitting appliance owners to use the method of their choice to 
    calculate leak rates is somewhat more complicated to enforce than 
    requiring either method alone, but could be easier for owners to comply 
    with if they have more experience with one method than the other. It 
    might permit owners to select the method that permits them to perform 
    leak repair less frequently, but both the annualizing and rolling 
    average methods eventually catch all leaks above the maximum allowable 
    rate. Because appliance owners using the rolling average method would 
    be doing so at their discretion, this approach neutralizes any equity 
    concerns associated with that method. However, to implement this 
    approach, EPA would have to resolve two issues. First, the Agency would 
    have to implement some
    
    [[Page 32058]]
    
    type of recordkeeping requirement (1) to ensure that once appliance 
    owners chose a method for calculating leak rates, they used the same 
    method consistently, and (2) to permit EPA inspectors to understand and 
    audit leak repair records. Second, EPA would have to determine whether 
    the same method for calculating leak rates should be used for 
    individual appliances, whole facilities, or entire firms. EPA believes 
    that using different methods for different appliances within the same 
    facility would be excessively confusing and difficult to enforce; the 
    Agency would prefer the same method to be used on a facility or firm 
    basis.
        EPA is proposing the third option, requiring use of whichever 
    method yields the higher calculated leak rate, as its lead option. 
    Specifically, EPA is proposing to define ``leak rate,'' as follows:
        Leak rate means the rate at which an appliance is losing 
    refrigerant, measured between refrigerant charges or over 12 months, 
    whichever is shorter. The leak rate is expressed in terms of the 
    percentage of the appliance's full charge that would be lost over a 12-
    month period if the current rate of loss were to continue over that 
    period. The rate is calculated using the following method:
        (1) Take the number of pounds of refrigerant added to the appliance 
    to return it to a full charge and divide it by the number of pounds of 
    refrigerant the appliance normally contains at full charge;
        (2) Take the shorter of (a) 365 days and (b) the number of days 
    that have passed since the last day refrigerant was added and divide 
    that number by 365 days;
        (3) Take the number calculated in step (1) and divide it by the 
    number calculated in step (2); and
        (4) Multiply the number calculated in step (3) by 100 to calculate 
    a percentage.
        This method is summarized in the following formula:
        [GRAPHIC] [TIFF OMITTED] TP11JN98.002
        
        Note that using this formula is equivalent to using whichever of 
    the two formulas above yields the higher calculated leak rate, since it 
    reduces to the formula for the annualizing method if less than one year 
    has passed since refrigerant was last added, while it reduces to the 
    formula for the rolling average method if more than one year has passed 
    since refrigerant was last added.
        The Agency believes that this approach would require owners to 
    repair leaks quickly without being unduly burdensome. EPA requests 
    comment on this approach and on the other options presented here.
    6. Low-pressure Appliance
        EPA is proposing to revise the definition of ``low-pressure 
    appliance'' to refer to saturation pressures at 104 degrees F rather 
    than boiling points. The proposed revised definition reads: Low 
    pressure appliance means an appliance that uses a refrigerant with a 
    liquid phase saturation pressure below 45 psia at 104 degrees 
    Fahrenheit. This definition includes but is not limited to appliances 
    using R11, R123, and R113.
    7. Opening
        EPA is proposing to amend the definition of ``opening'' to include 
    service, maintenance, or repair on an appliance that would release 
    class I, class II, or substitute refrigerants unless the refrigerant 
    were recovered previously from the appliance.
        EPA is also requesting comment on adding disposal to the definition 
    of ``opening;'' see section IV.F. for a discussion of this option.
    8. Reclaim
        EPA is proposing to amend the definition of ``reclaim'' to reflect 
    the proposed update of the refrigerant purity standards at appendix A 
    from standards based on ARI 700-1993 to standards based on ARI 700-
    1995. In addition, EPA is proposing to slightly reword the definition 
    of ``reclaim'' to remove the reference to a ``purity'' standard and 
    thereby make the definition more consistent with the full range of 
    requirements provided in appendix A. EPA has always interpreted 
    Sec. 82.154(g) and Sec. 82.164 to require that persons who ``reclaim'' 
    refrigerant must reprocess the refrigerant to all of the specifications 
    of appendix A that are applicable to that refrigerant and to verify 
    that the refrigerant meets these specifications using the analytical 
    methodology prescribed in appendix A.
    9. Refrigerant
        Although the regulations currently use the term ``refrigerant'' in 
    several places, EPA has not previously defined this term. EPA is 
    proposing to add a definition of ``refrigerant'' that would include any 
    class I or class II substance used for heat transfer purposes, or any 
    substance used as a substitute for such a class I or class II substance 
    by any user in a given end-use, except for the following substitutes in 
    the following end-uses:
    
    Ammonia in commercial or industrial process refrigeration or in 
    absorption units
    Hydrocarbons in industrial process refrigeration (processing of 
    hydrocarbons)
    Chlorine in industrial process refrigeration (processing of chlorine 
    and chlorine compounds)
    Carbon dioxide in any application
    Nitrogen in any application
    Water in any application
    
        EPA is proposing this definition primarily to simplify the rule. 
    The proposed definition would permit EPA to refer to covered class I, 
    class II, and substitute refrigerants without having to reiterate a 
    list of either included or excepted refrigerants each time. At the same 
    time, EPA believes that the proposed definition would appropriately 
    define ``refrigerant'' for purposes of section 608. The Agency does not 
    intend the definition either to expand or diminish the scope of the 
    section 608 requirements, and believes that the definition is 
    consistent with EPA's past interpretations of the term ``refrigerant.'' 
    In the past, EPA has interpreted ``refrigerants'' to include the fluids 
    in traditional vapor-compression systems, such as refrigerators, air-
    conditioners, and heat pumps, as well as the fluids in heat transfer 
    systems that lack compressors, such as electrical transformers. EPA has 
    adopted this interpretation based on both technical and common 
    definitions of ``refrigerant.'' The Agency believes that the proposed 
    definition would cover the fluids covered by the technical and common 
    definitions. The rationale for the proposed exceptions is discussed 
    above in section III.B.
        As discussed above, EPA is proposing to interpret ``appliance'' to 
    exclude secondary loops that move heat from warmer to cooler areas 
    using a fluid that does not change state. If EPA retains its proposed 
    interpretation of ``appliance,''
    
    [[Page 32059]]
    
    the Agency could add a restriction to the definition of ``refrigerant'' 
    to the same effect, ensuring consistency between the interpretation of 
    ``appliance'' and the definition of ``refrigerant.'' EPA requests 
    comment on this option, and on the proposed definition.
    10. Substitute
        EPA is proposing to define ``substitute'' as any chemical or 
    product substitute, whether existing or new, that is used by any person 
    as a replacement for a class I or II compound in a given end-use. As 
    discussed in section I.B. above, this definition is similar to the 
    definition of ``substitute'' used in the SNAP rule, but it omits the 
    proviso that a substitute be ``intended for use as a replacement for a 
    class I or class II substance.'' Thus, it includes substances that may 
    not have been used to replace class I or class II substances in a given 
    instance, but are used to replace class I or class II substances in 
    other instances of that end-use.
    11. Technician
        EPA is amending the definition of technician to include persons who 
    perform maintenance, service, repair, or disposal that could be 
    reasonably expected to release class I, class II, or substitute 
    refrigerants from appliances into the atmosphere.
    12. Very-High-Pressure Appliance
        EPA is proposing to revise the definition of ``very-high-pressure 
    appliance'' to refer to saturation pressures at 104 degrees Fahrenheit 
    rather than boiling points. Because 104 degrees F is above the critical 
    temperatures of many very-high-pressure refrigerants, meaning that 
    there is no ``saturation pressure'' in the usual sense for those 
    refrigerants at that temperature, EPA is also adding the phrase ``or 
    with a critical temperature below 104 degrees Fahrenheit'' to the 
    definition. The proposed revised definition reads as follows:
        Very-high-pressure appliance means an appliance that uses a 
    refrigerant with a critical temperature below 104 degrees Fahrenheit or 
    with a liquid phase saturation pressure above 305 psia at 104 degrees 
    Fahrenheit. This definition includes but is not limited to appliances 
    using R410A and B, R13, R23, and R503.
    
    B. Required Practices
    
        EPA is proposing to require persons servicing or disposing of air-
    conditioning and refrigeration equipment that contains HFCs and PFCs to 
    observe certain service practices that minimize emissions of these 
    refrigerants. As noted above, these service practices are very similar 
    to those required for the servicing or disposal of CFC and HCFC 
    equipment. The most fundamental of these practices is the requirement 
    to recover HFC and PFC refrigerants rather than vent them to the 
    atmosphere. As noted above, the knowing venting of substitutes for 
    class I and class II refrigerants (except those exempted by the 
    Administrator) during maintenance, service, repair or disposal is 
    expressly prohibited by section 608(c)(1) and (2) of the Act, as of 
    November 15, 1995. Section 608(c)(1) exempts from the prohibition de 
    minimis releases associated with good faith attempts to recapture and 
    recycle or safely dispose of these refrigerants.
        The statutory language of section 608(c)(2) simply extends to 
    substitute refrigerants the section 608(c)(1) prohibition on venting of 
    class I and II substances and its exemption for de minimis releases 
    associated with good faith attempts to recapture and recycle or safely 
    dispose of refrigerant. For releases of class I and II substances, EPA 
    has interpreted as ``de minimis releases associated with good faith 
    attempts to recapture and recycle or safely dispose'' of refrigerants, 
    releases that occur despite compliance with EPA's required practices 
    for recycling and recovery under 40 CFR 82.156, including use of 
    recovery or recycling equipment certified under 40 CFR 82.158. 
    Compliance with the regulations represents ``good faith attempts to 
    recapture and recycle or safely dispose'' of refrigerant, and 
    consequently releases that occur despite such compliance should be 
    considered de minimis releases under section 608(c).16 EPA 
    proposes to interpret the phrase ``good faith attempts to recapture and 
    recycle or safely dispose'' similarly when it applies to section 
    608(c)(2). Thus, ``good faith attempts to recapture and recycle or 
    safely dispose'' of substitute refrigerants are defined by the proposed 
    provisions concerning evacuation of equipment, recycling and recovery, 
    use of certified equipment, and technician certification. EPA believes 
    that these provisions appropriately define good faith attempts to 
    recapture and recycle or safely dispose of substitute refrigerants for 
    the reasons discussed in EPA's justification of each provision. Under 
    this approach, emissions that take place during servicing or disposal 
    when these provisions are not followed would not be de minimis 
    emissions.
    ---------------------------------------------------------------------------
    
        \16\ EPA believes that both the statute and its legislative 
    history support this interpretation of ``de minimis releases 
    associated with good faith attempts to recapture and recycle or 
    safely dispose of any such substance.'' Given the lack of 
    specificity in the statute, Congress clearly intended to give EPA 
    discretion to interpret the meaning of the phrase. Moreover, EPA's 
    interpretation is consistent with the legislative history on the 
    provision. As noted above, the Senate managers explained in their 
    report that the exception for de minimis releases was ``included to 
    account for the fact that in the course of properly using recapture 
    and recycling equipment, it may not be possible to prevent some 
    small amount of leakage'' (Congressional Record S16948, October 26, 
    1990). The Senate managers clearly equated ``properly using 
    recapture and recycling equipment'' with ``good faith attempts to 
    recapture'' refrigerant. EPA believes that the Senate managers' term 
    ``properly using'' implies at least compliance with the requirements 
    to evacuate appliances to certain levels, to use certified recovery 
    equipment, and to become certified as a technician.
    ---------------------------------------------------------------------------
    
        To implement section 608(c)(2) more effectively, EPA proposes not 
    only to define ``good faith attempts to recapture and recycle or safely 
    dispose'' according to the proposed provisions, but also more directly 
    to require compliance with the proposed provisions for substitute 
    refrigerants regarding evacuation of equipment, use of certified 
    equipment, and technician certification in any instance where a person 
    is opening (or otherwise violating the refrigerant circuit) or 
    disposing of an appliance, as defined in 40 CFR 82.152. It is 
    physically impossible to open appliances (or otherwise violate the 
    refrigerant circuit) or dispose of appliances without emitting at least 
    some refrigerant, even if some effort is made to recapture the 
    refrigerant. Even after the appliance has been evacuated, some 
    refrigerant remains, which is released to the environment when the 
    appliance is opened or disposed of. Other activities that fall short of 
    opening but that involve violation of the refrigerant circuit also 
    release refrigerant, albeit very small quantities, because connectors 
    (e.g., between hoses or gauges and the appliance) never join together 
    with no intervening space. Even in the best case in which a good seal 
    is made between a hose and an appliance before the valve between them 
    is opened, some refrigerant will remain in the space between the valve 
    and the outer seal after the former is closed. This refrigerant will be 
    released when the outer seal is broken. Thus, whenever a person opens 
    an appliance (or otherwise violates the refrigerant circuit) or 
    disposes of an appliance, he or she will necessarily violate the 
    venting prohibition unless the exception for de minimis releases 
    applies. Because EPA is proposing to define the exception such that it 
    only applies when the person complies with the proposed provisions 
    related to recapture, recycling and disposal, compliance with the 
    section 608(c)(2)
    
    [[Page 32060]]
    
    venting prohibition would require compliance with the proposed 
    provisions. EPA believes that given this factual context, it has 
    sufficient authority under sections 608(c)(2) and 301(a) to implement 
    section 608(c)(2) by simply requiring compliance with the proposed 
    provisions, as a matter of law, without in each instance first 
    requiring a demonstration that the person's activities have actually 
    released refrigerant.
    1. Evacuation of Appliances
        EPA is proposing that before HFC and PFC appliances are opened for 
    maintenance, service, or repair, the refrigerant in either the entire 
    appliance or the part to be serviced (if the latter can be isolated) 
    must be transferred to a system receiver or to a certified recycling or 
    recovery machine. (As discussed below in the equipment certification 
    discussion, EPA is proposing to permit technicians to recover HFCs or 
    PFCs using equipment certified for use with multiple CFC or HCFC 
    refrigerants of similar saturation pressures.) The same requirements 
    would apply to equipment that is to be disposed of, except for small 
    appliances, MVACs, and MVAC-like appliances, whose disposal is covered 
    under section c. below. EPA is proposing that HFC and PFC appliances be 
    evacuated to established levels that are the same as those for CFCs and 
    HCFCs with similar saturation pressures. At the same time, in order to 
    implement an approach based solely on saturation pressures, EPA is 
    proposing minor changes to the current system for classifying CFC and 
    HCFC appliances. As for CFCs and HCFCs, evacuation levels for HFCs and 
    PFCs would also depend upon the size of the appliance and the date of 
    manufacture of the recycling and recovery equipment.
        Technicians repairing MVAC-like appliances are not subject to the 
    evacuation requirements below, but are subject to a requirement to 
    ``properly use'' (as defined at 40 CFR 82.32(e)) recycling and recovery 
    equipment approved pursuant to Sec. 82.36(a).
        a. Evacuation Requirements for Appliances Other Than Small 
    Appliances, MVACs, and MVAC-like Appliances. Table I lists the proposed 
    levels of evacuation for air-conditioning and refrigeration equipment 
    other than small appliances, MVACs, and MVAC-like appliances. These 
    levels would apply to equipment containing CFCs and HCFCs as well as 
    HFCs and PFCs. The Agency has considered a number of factors in 
    developing these levels, including the technical capabilities, ease of 
    use, and costs of recycling and recovery equipment, the thermodynamic 
    characteristics of the HFC and PFC refrigerants, the need for a 
    relatively simple and consistent regulatory scheme for all 
    refrigerants, the servicing times that would be necessary to achieve 
    different vacuums, and the amounts of refrigerant that would be 
    released under different evacuation requirements and their impact on 
    the environment.
    
                                 Table 1.--Required Levels of Evacuation for Appliances                             
                             [Except for small appliances, MVACs, and MVAC-like appliances]                         
    ----------------------------------------------------------------------------------------------------------------
                                                             Inches of Hg vacuum (relative to standard atmospheric  
                                                                          pressure of 29.9 inches Hg)               
                                                         -----------------------------------------------------------
                      Type of appliance                    Using recovery or recycling   Using recovery or recycling
                                                            equipment manufactured or     equipment manufactured or 
                                                            imported before Nov. 15,      imported on or after Nov. 
                                                                      1993                        15, 1993          
    ----------------------------------------------------------------------------------------------------------------
    Very high-pressure appliance........................  0...........................  0.                          
    Higher-pressure appliance, or isolated component of   0...........................  0.                          
     such appliance, normally containing less than 200                                                              
     pounds of refrigerant.                                                                                         
    Higher-pressure appliance, or isolated component of   4...........................  10.                         
     such appliance, normally containing 200 pounds or                                                              
     more of refrigerant.                                                                                           
    High-pressure appliance, or isolated component of     4...........................  10.                         
     such appliance, normally containing less than 200                                                              
     pounds of refrigerant.                                                                                         
    High-pressure appliance, or isolated component of     4...........................  15.                         
     such appliance, normally containing 200 pounds or                                                              
     more of refrigerant.                                                                                           
    Low-pressure appliance..............................  25..........................  25 mm Hg absolute.          
    ----------------------------------------------------------------------------------------------------------------
    
        As noted above, the evacuation requirements in Table 1 are very 
    similar to those currently in place for CFC and HCFC appliances. The 
    current evacuation requirements for CFC and HCFC appliances are based 
    largely, but not entirely, on their saturation pressures. (Refrigerants 
    are actually classified according to their boiling points at 
    atmospheric pressure, which are generally inversely related to their 
    saturation pressures at higher temperatures.) The current regulation 
    has three saturation pressure categories for appliances: low pressure, 
    high-pressure, and very-high-pressure. Successively deeper vacuums are 
    required for lower pressure appliances.
        EPA adopted this approach because the saturation pressure of a 
    refrigerant is directly related both to the percentage of refrigerant 
    that is recovered at a given vacuum level and to the compression ratio 
    that is necessary to achieve that vacuum.17 A comparison 
    between R502, which has a saturation pressure of 245 psia at 104 deg.F, 
    and R11, which has a saturation pressure of 25.3 psia at 104 deg.F, 
    makes this clear. At an evacuation level of 10 inches of mercury vacuum 
    and an ambient temperature of 104 deg.F, 96
    
    [[Page 32061]]
    
    percent of R502 refrigerant vapor has been recovered, but only 61 
    percent of R11 refrigerant vapor has been recovered. For R502, the 
    compression ratio necessary to achieve this vacuum is about 25 to 1, 
    but for R11 the compression ratio necessary is only about one tenth of 
    that, 2.6 to 1. Most recovery compressors have a compression ratio 
    limit of between 20 and 30 to 1, meaning that it is difficult to 
    achieve an evacuation level much lower than 10 inches of vacuum for 
    R502, but that it is easy to achieve a lower evacuation level for R11. 
    Thus, a refrigerant's saturation pressure directly affects both the 
    technical feasibility and the environmental impact of a given 
    evacuation level.
    ---------------------------------------------------------------------------
    
        \17\ The saturation pressure of a refrigerant is the same as its 
    vapor pressure, that is, the characteristic pressure of the vapor in 
    a vapor/liquid mixture of that refrigerant at equilibrium at a given 
    temperature. A compression ratio `is the ratio of the pressures of a 
    gas on the discharge and suction sides of the compressor.
    ---------------------------------------------------------------------------
    
        However, saturation pressure is not the only factor affecting the 
    feasibility and cost-effectiveness of various evacuation levels for 
    appliances. Other considerations include the discharge temperature of 
    the refrigerant (the temperature of the refrigerant as it emerges from 
    the compressor) and the social value of the refrigerant (which includes 
    both its price and the environmental damage avoided by containing it). 
    Due to these considerations, EPA established a special set of 
    evacuation requirements for R-22 appliances, which would otherwise have 
    been treated as high-pressure appliances. EPA established somewhat less 
    stringent requirements for R22 appliances because (1) R-22 has both a 
    relatively high saturation pressure and a relatively high discharge 
    temperature among high-pressure refrigerants, making it relatively 
    difficult to evacuate deeply, and (2) R-22 has a low ODP compared to 
    R12, R500, and R502, all of which contain CFCs (58 FR 28674).
        When EPA began its evaluation of possible evacuation levels for HFC 
    appliances, the Agency believed that it might be appropriate to 
    establish less stringent levels for these refrigerants than for CFCs of 
    similar saturation pressure, following the precedent established with 
    R22. On a pound-for-pound basis, EPA estimates that HFCs generally 
    cause less environmental harm than the CFCs they replace. However, when 
    EPA performed its analysis of the costs and benefits of attaining 
    various vacuum levels, it found that the social cost of releasing the 
    HFCs and PFCs (which, again, is a combination of the lost private value 
    of the refrigerant and the environmental damage that results from its 
    release) justified reaching vacuum levels only slightly less deep than 
    those for the CFCs being replaced. For instance, EPA found that the 
    socially optimal level of evacuation for R12 appliances containing 50 
    pounds of refrigerant was 15 to 22 inches of vacuum 18, 
    while the socially optimal level of evacuation for R134a appliances 
    containing the same quantity was 8 to 17 inches of vacuum.19 
    Based on these results, the most important factor in determining 
    appropriate evacuation levels for any particular charge size appears to 
    be the saturation pressure of the refrigerant.
    ---------------------------------------------------------------------------
    
        \18\ EPA established a 10-inch vacuum level for equipment 
    containing less than 200 lbs of high-pressure refrigerant in 
    consideration of the fact that this evacuation requirement would 
    apply not only to large R12 appliances, but to smaller R12 
    appliances and to appliances containing somewhat higher pressure 
    refrigerants (e.g., R502). Very deep evacuation requirements were 
    not justified for the last two. In addition, many appliances are 
    likely serviced at higher temperatures than the 70 deg. used in 
    EPA's model, making attainment of deep vacuums more difficult.
        \19\ Calculated optimal vacuums depend upon labor costs, the 
    estimated social cost of releasing the refrigerant, the displacement 
    of the recovery device compressor, and the clearance of the recovery 
    device compressor. The 8-inch optimal vacuum is based on relatively 
    low compressor displacement, relatively high compressor clearance, 
    and the assumption that the release of one kilogram of R134a would 
    cause about 60 cents worth of environmental damage; the 17-inch 
    optimal vacuum is based upon relatively high compressor 
    displacement, relatively low compressor clearance, and the 
    assumption that the release of one kilogram of R134a would cause 
    about six dollars worth of environmental damage. If the R134a is 
    assumed to cause no damage (which, for the reasons discussed in 
    section III.B.2, is an extremely unlikely assumption), the lower-
    bound optimal vacuum rounds to seven inches.
    ---------------------------------------------------------------------------
    
        Moreover, standards set by saturation pressure would be easier for 
    technicians to remember and implement than standards that varied both 
    by saturation pressure and type of refrigerant. The current CFC and 
    HCFC regulations contain 12 categories of evacuation requirements, a 
    number that could conceivably be doubled if EPA established new 
    categories for HFCs. EPA believes that the limited benefit that might 
    be gained by such ``fine-tuning'' is outweighed by the confusion and 
    non-compliance that could result from the proliferation of different 
    requirements. Many participants at the March 10, 1995, industry meeting 
    on substitutes recycling expressed a belief that establishing 
    consistent requirements for CFCs, HCFCs, HFCs, and PFCs would enhance 
    compliance with the recovery requirements for all of these 
    refrigerants.
        EPA is proposing two changes to the current system for classifying 
    appliances in order to implement an approach based solely upon 
    saturation pressure. The first proposed change is to classify 
    refrigerants according to their saturation pressures at 104 degrees F 
    rather than their boiling points. The second proposed change is to 
    eliminate the special category for R22 and to replace it with a new 
    saturation pressure category that includes the ``high-pressure'' 
    refrigerants with the highest saturation pressures.
        EPA is proposing to classify refrigerants according to their 
    saturation pressures at 104 degrees F 20 because many of the 
    refrigerants that have entered the market over the past few years pose 
    two difficulties for the existing system based on boiling points. 
    First, many of the new HFC and HCFC blends do not have precise boiling 
    points. Instead, these refrigerants exhibit ``glide,'' boiling and 
    condensing over a range of temperatures at a given pressure. Second, 
    refrigerants' boiling points have served as a surrogate for their 
    saturation pressures at higher temperatures, but the relationship 
    between boiling point and saturation pressure is not as consistent for 
    the new refrigerants as it is for traditional CFCs and HCFCs. For 
    instance, a lower boiling point has generally indicated a higher 
    saturation pressure at a given temperature. However, R402B, with a 
    boiling point of -53.2 degrees F, actually has a lower saturation 
    pressure at 104 degrees F than R407A, with a boiling point of-49.9 
    degrees. The new approach avoids these difficulties because it links 
    evacuation requirements directly to the refrigerant saturation pressure 
    at a temperature similar to those where recovery typically takes place.
    ---------------------------------------------------------------------------
    
        \20\ Zeotropic blends exert different pressures at the same 
    temperature, depending upon the percentage of vapor vs. liquid in 
    the container. For instance, a container of R407C vapor has a 
    saturation pressure of 223.8 psia at 104 degrees, while a container 
    of R407C liquid has a saturation pressure of 254.5 psia at 104 
    degrees. EPA is proposing to classify refrigerants according to 
    their liquid saturation pressures at 104 degrees F. This is because 
    the vacuum that can be drawn on an appliance is determined by the 
    discharge pressure against which the recovery compressor must pump 
    near the conclusion of the recovery process, and this discharge 
    pressure is that of a recovery tank that is likely to be nearly 
    filled with liquid.
    ---------------------------------------------------------------------------
    
        EPA has attempted to select bracketing saturation pressures for 
    appliance categories so as to maintain as much consistency as possible 
    with the current categories based on boiling points. For instance, 
    because the current definition of ``high-pressure appliances'' includes 
    R114 appliances at the low-pressure end, and the saturation pressure of 
    R114 at 104 degrees F is slightly above 45 psia, EPA is proposing to 
    use a saturation pressure of 45 psia as the lower-bound saturation 
    pressure for high-pressure appliances.
        One issue raised by the proposed approach is how to classify 
    appliances using very high pressure refrigerants such as R13, R23, and 
    R503. These
    
    [[Page 32062]]
    
    refrigerants do not have a saturation pressure in the traditional sense 
    at 104 degrees F because this temperature is above their critical 
    temperatures. (As noted above, the saturation pressure of a refrigerant 
    is the pressure of the vapor in a vapor/liquid mixture, but 
    refrigerants above their critical temperatures cannot exist in a liquid 
    state regardless of the pressure.) To address this concern, EPA is 
    proposing to modify the definition of very high pressure appliances to 
    add the phrase ``or whose critical temperatures fall below 104 degrees 
    F.''
        EPA requests comment on its proposed use of refrigerants' 
    saturation pressures at 104 degrees F rather than boiling points to 
    classify them. An alternative might be to retain the current system 
    based on boiling points, making allowances for temperature glide. For 
    example, in cases where glide caused a refrigerant to straddle the line 
    between two pressure categories, EPA could place the ``straddling'' 
    refrigerant into the category suggested by the lower end of the boiling 
    range (the ``bubble point''). This point is the one typically listed in 
    pressure-temperature charts, and EPA believes that it is the point that 
    would determine the maximum evacuation level (minimum pressure) that is 
    physically possible for the refrigerant.
        Some custom refrigerant blends exhibit very large glides (e.g., 
    over 60 degrees Celsius). For such refrigerants, the appropriate 
    evacuation level may be difficult to predict based on either saturation 
    pressure or a single ``bubble'' or ``dew'' point. EPA has worked and 
    will continue to work with the manufacturers of these refrigerants to 
    determine appropriate evacuation levels on a case-by-case basis.
        The second change that EPA is proposing to the current 
    classification scheme is to eliminate the special category for R22 and 
    to replace it with a new saturation pressure category that includes the 
    ``high-pressure'' refrigerants with the highest saturation pressures 
    (those with boiling points approximately between -40 and -50 degrees C 
    and saturation pressures between 220 psia and 305 psia at 104 degrees 
    F). EPA would designate this as the ``higher-pressure'' refrigerants 
    category. This would enable EPA to tailor requirements to refrigerants 
    with relatively high saturation pressures without increasing the 
    overall number of categories. The new category would include appliances 
    containing R22, R502, R404C, and R407 A, B, and C, and would be subject 
    to the same requirements as R22 appliances. For several of these 
    refrigerants, the combination of a relatively high saturation pressure 
    and high discharge temperature makes recovery into a deep vacuum 
    difficult. On the other hand, these refrigerants have significantly 
    lower saturation pressures than still higher pressure refrigerants, 
    such as R410A and B (with saturation pressures near 350 psia) and R13 
    and R503 (whose critical temperatures fall below 104 degrees F).
        EPA requests comment on the establishment of the ``higher-
    pressure'' saturation pressure category. EPA specifically requests 
    comment on the proposed use of 305 psia as the upper bound saturation 
    pressure for this category. The pressures to which R22 appliances must 
    be evacuated (and therefore to which ``higher-pressure'' appliances 
    would have to be evacuated) are 0 inches of vacuum, or atmospheric 
    pressure, for appliances containing less than 200 pounds of 
    refrigerant, and 10 inches of vacuum, or 9.8 psia, for appliances 
    containing more than 200 pounds of refrigerant. Drawing a 10-inch 
    vacuum on an appliance containing a refrigerant with a saturation 
    pressure of 305 psia would require recovery equipment to attain a 
    compression ratio of 30 to 1. EPA's current understanding is that this 
    is very close to the maximum achievable compression ratio for most 
    recovery compressors, and may even be beyond the abilities of some 
    models. (However, the compression ratio necessary to achieve this 
    vacuum may be lowered by cooling the condenser of the recovery 
    equipment.) Thus, it may be appropriate to establish a different upper-
    bound saturation pressure for this category, such as 265 psia.
        EPA also requests comment on whether it is appropriate to include 
    R502 (which has a relatively low discharge temperature) in this 
    category, or whether the possibility of drawing a deeper vacuum on this 
    refrigerant merits its inclusion in a lower-pressure category despite 
    the confusion that might result.
        One concern raised at the March 10, 1995, meeting was whether the 
    energy consumption associated with lengthy operation of recovery 
    equipment might result in the emission of more global warming gases 
    (CO2) than would be contained through continuing the 
    refrigerant recovery process, removing the justification for deep 
    recovery. To investigate this concern, EPA and a laboratory that tests 
    recovery and recycling equipment compared the rates of power 
    consumption (and resultant emissions of CO2) and refrigerant 
    recovery for both high- and low-pressure recovery equipment. Both the 
    CO2 emissions rate and the refrigerant recovery rate were 
    weighted by the GWPs of the gases being emitted or captured. (Both the 
    EPA and laboratory analyses are included in the docket for this 
    rulemaking.) The conclusion of both EPA and the laboratory was that the 
    rate of CO2 emission resulting from use of recovery 
    equipment was dwarfed by the rate of refrigerant recovery even at the 
    latest (and therefore slowest) stages of recovery. Specifically, the 
    minimum rate of refrigerant recovery for high-pressure recovery 
    equipment was greater than the maximum rate of CO2 emissions 
    attributable to recovery by more than a factor of 2000, and the minimum 
    rate of recovery for low-pressure equipment out paced the rate of 
    CO2 emissions by a factor of over 1000. These large 
    differences are in part attributable to the high global warming 
    potential of most HFC refrigerants compared to CO2.
        b. Evacuation Levels for Small Appliances. EPA is proposing to 
    establish the same evacuation requirements for servicing small 
    appliances charged with HFCs as it has for small appliances charged 
    with CFCs and HCFCs. Technicians opening small appliances for service, 
    maintenance, or repair would be required to use equipment certified 
    either under Appendix B, ARI 740-1993, or under Appendix C, Method for 
    Testing Recovery Devices for Use with Small Appliances, to recover the 
    refrigerant.
        Technicians using equipment certified under Appendix C would have 
    to capture 90 percent of the refrigerant in the appliance if the 
    compressor were operating, and 80 percent of the refrigerant if the 
    compressor were not operating. Because the percentage of refrigerant 
    mass recovered is very difficult to measure on any given job, 
    technicians would have to adhere to the servicing procedure certified 
    for that recovery system under Appendix C to ensure that they achieve 
    the required recovery efficiencies.
        Technicians using equipment certified under Appendix B would have 
    to pull a four-inch vacuum on the small appliance being evacuated.
        c. Evacuation Levels for Disposed MVACs, MVAC-like Appliances, and 
    Small Appliances. EPA is proposing to establish the same evacuation 
    requirements for disposing of small appliances, MVACs, and MVAC-like 
    appliances that are charged with HFCs as it has for these types of 
    appliances charged with CFCs and HCFCs. MVACs and MVAC-like appliances 
    would have to be evacuated to 102 mm (approximately four inches) of 
    mercury vacuum, and small appliances would have to have 80 or 90 
    percent of the
    
    [[Page 32063]]
    
    refrigerant in them recovered (depending on whether or not the 
    compressor was operating) or be evacuated to four inches of mercury 
    vacuum.
        d. Request for Comment on Establishing Special Evacuation 
    Requirements for Heat Transfer Appliances. As noted in section 
    IV.A.1.a. above, EPA received comments from a manufacturer of PFCs that 
    stated that special evacuation requirements may be appropriate for 
    certain types of heat transfer appliances containing PFCs, such as some 
    types of electrical transformers. The commenter specifically noted that 
    evacuating some types of heat transfer systems may result in damage to 
    those systems, that in many cases, parts to be repaired may be isolated 
    from the refrigerant charge, and that many repairs may be performed 
    quickly, releasing little refrigerant even if the system is not 
    evacuated.
        EPA does not currently believe that special evacuation requirements 
    for heat transfer appliances are necessary, for two reasons. First, EPA 
    has not heard from users or servicers of heat transfer appliances that 
    the current requirements regarding the recovery of CFCs and HCFCs from 
    such appliances (which are the same as those for similarly sized 
    appliances containing refrigerants of similar pressure) are difficult 
    to implement. Because PFCs have physical characteristics similar to 
    those of the CFCs that they replace in heat transfer appliances, EPA 
    believes that any potential problems associated with implementing the 
    proposed evacuation requirements for PFCs would have already surfaced 
    with CFCs and HCFCs. Second, the current evacuation provisions appear 
    to adequately address most of the situations that the commenter has 
    identified. Specifically, the current regulations establish an 
    exception to the evacuation requirements for non-major repairs and 
    permit isolation of parts to be repaired. Before non-major repairs, 
    technicians need only evacuate (or pressurize, in the case of low-
    pressure appliances) appliances to atmospheric pressure. If a part can 
    be isolated from the refrigerant charge, technicians may repair the 
    part without recovering the refrigerant into an external container.
        EPA requests comment on the need for special evacuation 
    requirements for heat transfer appliances in light of the arguments 
    presented here.
        e. Proposed Clarifications of Evacuation Requirements. EPA has 
    received a request for two clarifications of the evacuation 
    requirements for appliances. The first request for clarification 
    concerns whether a part of the appliance that is not a separate tank 
    may be considered a ``system receiver,'' in which the system charge may 
    be isolated while another, isolated part of the appliance is opened for 
    repairs. The second request for clarification concerns whether an 
    isolated portion of an appliance that already meets the required level 
    of evacuation due to normal operating characteristics may be opened for 
    repairs without further evacuation. In addition to proposing a minor 
    change to the regulatory language to respond to the first request, EPA 
    is proposing to add language to Sec. 82.156(a) to clarify that, except 
    in the case of non-major repairs to low-pressure appliances, liquid 
    refrigerant must be removed from appliances (or from the isolated parts 
    to be serviced) before they are opened to the atmosphere.
        Regarding the first request for clarification, EPA is today 
    clarifying that, for purposes of complying with Sec. 82.156(a), EPA 
    interprets the term ``system receiver'' to include a part of the 
    appliance that is not a separate tank, if that portion of the appliance 
    can be isolated from the portion of the appliance that is opened for 
    repairs. From an environmental perspective, EPA believes that the 
    critical consideration is whether the part of the appliance to be 
    opened to the atmosphere for repair has had the refrigerant removed and 
    isolated from it, not the configuration of the remaining appliance 
    parts within which the refrigerant is isolated. To clarify this point, 
    EPA is proposing to amend Sec. 82.156(a) by adding the following 
    examples after the term ``system receiver'': ``(e.g., the remaining 
    portions of the appliance, or a specific vessel within the 
    appliance)''. EPA requests comment on this proposed change.
        In addition to clarifying its interpretation of ``system 
    receiver,'' EPA is proposing to add language to Sec. 82.156(a) to 
    ensure that the regulations clearly preclude a possible 
    misinterpretation of these requirements. EPA has always interpreted 
    Sec. 82.156(a) to require that, except in the case of non-major repairs 
    to low-pressure appliances, liquid refrigerant must be removed from 
    appliances (or from the isolated parts to be serviced) before they are 
    opened to the atmosphere. Currently, Sec. 82.156(a) reads (in part) 
    ``all persons disposing of appliances * * * must evacuate the 
    refrigerant in the entire unit to a recovery or recycling machine 
    certified pursuant to Sec. 82.158. All persons opening appliances * * * 
    must evacuate the refrigerant in either the entire unit or the part to 
    be serviced (if the latter can be isolated) to a system receiver or a 
    recovery or recycling machine certified pursuant to Sec. 82.158.'' 
    Sections 82.156(a)(1) through (5) specify pressures to which the 
    appliances must be evacuated.
        It has come to EPA's attention that it may be possible in some 
    cases to briefly attain the required evacuation levels specified in 
    Secs. 82.156(a)(1) through (5) while there is still liquid refrigerant 
    in the appliance or in the isolated part to be serviced. In general, if 
    vapor is removed from a mixture of liquid and vapor refrigerant at 
    equilibrium, reducing the vapor pressure, the liquid will boil until 
    the equilibrium between the vapor and liquid states is restored, 
    returning the vapor pressure to the saturation pressure of the 
    refrigerant. However, heat must flow into the system from the 
    environment for this to occur, and such heat flow takes time. Thus, if 
    an individual quickly recovers vapor from an appliance, permitting no 
    time for the liquid to boil to return the vapor pressure to the 
    equilibrium value, the pressure specified in Sec. 82.156(a) may be 
    attained, albeit only temporarily. If the individual opens the 
    appliance at this point, a great deal of refrigerant will be released 
    to the environment. This is because the density of liquid refrigerant 
    is typically one to two orders of magnitude greater than that of vapor 
    refrigerant, meaning that a large mass of refrigerant may be 
    concentrated in a relatively small volume of liquid, and the liquid 
    will continue to boil off into the atmosphere as long as the appliance 
    is opened.
        EPA believes that the use of the phrase ``evacuate the 
    refrigerant'' in Sec. 82.156(a), as well as the language in 
    Sec. 82.154(a) (the prohibition on venting) already clearly indicate 
    that liquid refrigerant must be removed from the appliance or isolated 
    part before it is opened for servicing. Otherwise, a significant 
    portion of the refrigerant will not be evacuated to a recovery device, 
    a good faith effort to recover and recycle refrigerant will not be 
    made, and releases to the environment will be considerably more than de 
    minimis. Nevertheless, to eliminate any possible ambiguity on this 
    point, the Agency is proposing to add the phrase, ``including all 
    liquid refrigerant,'' after the phrase, ``the refrigerant,'' in both 
    places where it occurs in Sec. 82.156(a). To ensure that the modified 
    language does not implicitly override Sec. 82.156(a)(2)(i)(B), which 
    provides that recovery of liquid is not required in cases of non-major 
    repairs to low-pressure appliances, EPA is proposing to add the 
    parenthetical phrase ``(except as provided at 
    Sec. 82.156(a)(2)(i)(B))'' to the second occurrence of ``including all 
    liquid
    
    [[Page 32064]]
    
    refrigerant.'' EPA requests comment on this proposed change.
        In response to the second request for clarification, EPA believes 
    that if a part of an appliance already meets the required level of 
    evacuation due to normal operating characteristics, it may be isolated 
    and opened for repairs without further evacuation, so long as liquid 
    refrigerant is not present in the isolated part. Again, the purpose of 
    the requirement to evacuate under Sec. 82.156(a) is to minimize 
    refrigerant emissions from the part. If the required level of 
    evacuation has been met, and no liquid is present in the isolated part, 
    only de minimis quantities of refrigerant will be released when the 
    part is opened to the atmosphere. Therefore, this situation meets the 
    requirements to evacuate under Sec. 82.156(a).
    2. Disposition of Recovered Refrigerant
        EPA is proposing to establish purity requirements for HFCs and PFCs 
    very similar to those for CFCs and HCFCs. In addition, the Agency is 
    proposing to update its purity requirements for all refrigerants to 
    reflect the most recent industry standard, ARI 700-1995, Specifications 
    for Fluorocarbon and Other Refrigerants, and is requesting comment on 
    adopting a generic standard of purity for those refrigerants that are 
    not covered by ARI 700-1995.
        a. Background. Currently, before being sold for use as a 
    refrigerant, used CFCs and HCFCs must be reclaimed by a certified 
    reclaimer to the ARI 700-1993 Standard of purity, which is codified as 
    Appendix A to subpart F. In a separate rulemaking, EPA has proposed to 
    add more flexibility to the purity standards for CFC and HCFC 
    refrigerants, permitting contractors to transfer refrigerant from one 
    customer's to another customer's equipment, so long as (1) the 
    refrigerant remains within the contractor's constant custody and 
    control, (2) the refrigerant is returned to the ARI 700 Standard of 
    purity, and (3) this purity is verified through submission of a 
    representative sample to an analytical laboratory certified by an EPA-
    approved laboratory certification program. That proposal would also 
    require third party certification of reclaimers. See 61 FR 7858 
    (February 29, 1996).
        b. Extending Purity Requirements to HFC and PFC Refrigerants. EPA 
    is not today soliciting comment on which refrigerant purity regime is 
    preferable for all refrigerants. Instead, EPA requests comment on 
    whether the purity of HFCs and PFCs should be maintained through a 
    different regulatory approach than the purity of CFCs and HCFCs, and if 
    so, why.
        EPA believes that the rationale for promulgating purity standards 
    for CFCs and HCFCs also applies to HFCs and PFCs 21. EPA 
    discussed the rationale for covering CFCs and HCFCs at length in the 
    May 14, 1993 final rule (58 FR 28678-28679), the March 17, 1995, and 
    February 29, 1996 direct final rules, and the December 27, 1996 final 
    rule extending the reclamation requirement (60 FR 14608, 61 FR 7724, 
    and 61 FR 68506). In summary, the purity requirements are intended to 
    prevent refrigerant releases that would result from refrigerant 
    contamination, particularly releases linked to damage to equipment 
    caused by use of contaminated refrigerant. This damage, including 
    sludging of high-viscosity oils in low temperature systems, freezing of 
    moisture in capillary tubes, corrosion from acids, and high head-
    pressures from noncondensables and refrigerant mixtures, could be 
    caused by contaminated HFCs and PFCs (and their lubricants) as well as 
    by contaminated CFCs and HCFCs. Equipment damage from contaminated 
    refrigerant would result in costs to equipment owners and releases of 
    refrigerant from damaged equipment though increased leakage, servicing, 
    and replacement. In addition, such damage would ultimately lead to a 
    reduction in consumer confidence in the quality of used refrigerant.
    ---------------------------------------------------------------------------
    
        \21\ In finalizing the purity requirements for HFCs and PFCs, 
    EPA will consider comments received on both on the February 29, 
    1996, document (and on any subsequent document related to purity 
    standards for refrigerant) and on this document.
    ---------------------------------------------------------------------------
    
        Given these potential effects, EPA believes that promulgating 
    purity requirements for HFCs and PFCs is vital to implementation and 
    enforcement of section 608(c)(2). Any reduction in consumer confidence 
    in the quality of used refrigerant would undermine a fundamental 
    incentive to comply with the section 608(c)(2) prohibition on venting 
    substitute refrigerants. Without a market for the used refrigerant, 
    there is no economic incentive to recover it; indeed, the costs of 
    recovery and destruction create a significant economic incentive simply 
    to release the substance, in violation of the venting prohibition. 
    Moreover, the removal of economic incentives to comply with the 
    prohibition is particularly deleterious to compliance because direct 
    enforcement of the prohibition is difficult. The prohibition applies to 
    numerous small entities, including over one million technicians, and 
    EPA lacks the resources to monitor their refrigerant-related activities 
    on an individual basis. Under these circumstances, establishing 
    economic incentives for compliance, or at least neutralizing economic 
    disincentives to compliance, is particularly critical to implementing 
    the statutory prohibition on venting.
        The proliferation of refrigerants and lubricants on the market has 
    made efforts to protect refrigerant purity more important than ever. 
    The increasing number of refrigerants increases the probability of 
    refrigerant mixture, particularly if equipment that has been 
    retrofitted with new refrigerant is not properly identified, leading to 
    mixture of a CFC with the HCFC or HFC that replaced it. Requirements to 
    analyze refrigerant before sale to a new owner can prevent mixed 
    refrigerants from being placed into equipment or from contaminating a 
    larger batch of refrigerant.
        Moreover, EPA believes that purity standards must apply to all 
    refrigerants in similar applications in order to ensure purity for any 
    subset of these refrigerants. As noted above, several persons attending 
    the March 10, 1995 public meeting stated that failure to apply 
    standards to HFCs could erode compliance with the standards for CFCs 
    and HCFCs, because technicians would become either confused or 
    skeptical regarding standards that were applied inconsistently. Such 
    standards would also be difficult to enforce. For instance, without 
    purity standards, contractors could sell dirty HFCs on the open market, 
    and it would be relatively easy to hide commerce in dirty CFCs or HCFCs 
    within commerce in dirty HFCs (e.g., through deliberate mislabelling, a 
    tactic that has been used to import CFCs illegally). Thus, purity 
    standards for HFCs are important to prevent damage to CFC and HCFC 
    equipment and subsequent emissions of these refrigerants as well. As a 
    consequence, EPA believes that purity standards for HFCs and PFCs are 
    important to implement the section 608(a)(2) requirement to reduce 
    emissions of CFCs and HCFCs to the lowest achievable level.
        EPA is proposing to extend the purity requirements to HFCs and PFCs 
    by revising prohibitions 82.154(g) and (h) to refer simply to 
    ``refrigerant'' rather than to ``class I and class II substances.'' In 
    addition, EPA is proposing to include purity standards and analytical 
    protocols for HFC refrigerants in Appendix A.
        c. Updating the Purity Standard. EPA is proposing to adopt the most 
    recent version of the industry purity standard and analytical protocol 
    for refrigerants, ARI 700-1995. ARI 700-1995 includes standards for a 
    number of refrigerants that are not addressed by the currently
    
    [[Page 32065]]
    
    codified standard, ARI 700-1993. These refrigerants include R404A, 
    R405A, R406A, R407A, B, and C, R408A, R409A, R410A and B, R411A and B, 
    R412A, R507, R508 and R509. In addition, the Appendix C to ARI Standard 
    700-95 has updated some of the procedures for the analysis of 
    refrigerants in Appendix 93 to ARI 700-1993, which is incorporated by 
    reference into subpart F. First, methods have been added for 
    determining the composition of the zeotropic refrigerant blend families 
    R404, R407, R408, R409, and R410, and of the azeotropic refrigerant 
    blends R507 and R508. These methods will enable laboratories to verify 
    that the blends contain the appropriate percentages of their component 
    materials. Second, a gravimetric test has been added as an alternate 
    method for determining high-boiling residues. The gravimetric test is 
    actually considered to be more accurate than the current volumetric 
    method, and its addition will permit laboratories with the appropriate 
    facilities and expertise to perform more precise measurements of high-
    boiling residues than are permitted by the volumetric method. (The 
    volumetric method is retained as an alternate in ARI 700-95 because it 
    is adequately precise for most applications, and is less expensive to 
    perform than the gravimetric method.) Finally, several typographic and 
    wording changes have been made to improve the clarity of the standard. 
    EPA believes that these changes will make the reclamation requirements 
    more enforceable while decreasing the burden of industry to prove 
    conformance.
        ARI is currently revising ARI Standard 700-95 to reflect further 
    advances in refrigerant analysis and changes in the refrigerant market. 
    Because the next version of the Standard may be completed between the 
    publication of this proposed rule and the final rule, and because EPA 
    believes it is appropriate to adopt the most recent version of the 
    Standard possible, EPA is requesting comment on the changes to the 
    Standard that EPA understands are being considered. These changes 
    include (1) the adoption of a single analysis (for each blend) for 
    determining both the composition of each refrigerant blend and its 
    level of contamination by organic impurities, and (2) the 
    standardization of the presently wide range of equipment, techniques, 
    and calculations used in the current methods for determining the 
    composition of refrigerant blends. Currently, there are no analytical 
    methods for determining blends' levels of contamination by organic 
    impurities, and the adoption of a standardized and consolidated 
    composition/impurity analysis will therefore make the standard more 
    enforceable without significantly increasing the burden on 
    laboratories. These changes are discussed in more detail in a report 
    developed by Integral Sciences Incorporated for the Air-Conditioning 
    and Refrigeration Technology Institute (ARTI). This report is entitled 
    Methods Development for Organic Contaminant Determination in 
    Fluorocarbon Refrigerant Azeotropes and Blends and is included in the 
    docket for this rulemaking.
        d. Generic Standard of Purity. Despite EPA's proposed adoption of 
    the latest industry standard, the Agency's purity standards are likely 
    to be rendered incomplete shortly after their promulgation by the rapid 
    development and introduction of new refrigerants into the market. In 
    general, there is likely to be a delay between the introduction of new 
    refrigerants and the adoption of specific purity standards for them by 
    ARI and EPA. Although EPA plans to consider purity requirements along 
    with recycling requirements for each new refrigerant as it undergoes 
    SNAP review, the Agency is requesting comment on establishing a generic 
    purity standard for refrigerants for which specific purity standards 
    have not yet been codified. The ARI 700 standard includes 
    specifications for boiling points, boiling ranges, isomer contents, 
    noncondensables, water, high-boiling residue, particulates/solids, 
    acidity, and chlorides. Except for boiling points, boiling ranges, and 
    high boiling residues, the specifications for all CFC, HCFC, and HFC 
    refrigerants are identical or vary systematically according to the 
    saturation pressure of the refrigerant. EPA is requesting comment on 
    whether HFCs for which specific standards have not been codified should 
    be subject to the following maximum contaminant levels, which are based 
    on those of ARI 700:
    
                                           Generic Maximum Contaminant Levels                                       
    ----------------------------------------------------------------------------------------------------------------
                Contaminant                      Reporting units         Low pressure refrigs.     Other refrigs.   
    ----------------------------------------------------------------------------------------------------------------
    Non-condensables...................  % by volume @ 25 deg.C........  N/A..................  1.5.                
    Water..............................  ppm by weight.................  20...................  10.                 
    High boiling residue...............  % by volume...................  0.01.................  0.01.               
    Particulates/solids................  Visually clean to pass........  pass.................  pass.               
    Acidity............................  ppm by weight.................  1.0..................  1.0.                
    Chlorides..........................  No visible turbidity..........  pass.................  pass                
    ----------------------------------------------------------------------------------------------------------------
    
        EPA requests comment on the specific contaminant levels presented 
    here.
        Since reclamation requires not only that refrigerant be cleaned to 
    a certain level, but also that it be analyzed to verify that it meets 
    that level, a generic standard of purity should be matched by a generic 
    analytical protocol. General analytical procedures exist to determine 
    the levels of acidity, water, high-boiling residue, chloride, and non-
    condensable gases in refrigerants; these procedures are detailed in 
    parts 1 through 5 of Appendix C to ARI 700-95. However, individual gas 
    chromatography procedures are required for each refrigerant in order to 
    determine the overall purity of that refrigerant. This is because each 
    refrigerant has its own gas chromatogram (profile) and characteristic 
    impurities (other than acid, water, high-boiling residue, chloride, and 
    noncondensable gases). EPA understands that the need to develop gas 
    chromatography procedures is what frequently slows the adoption of 
    reclamation procedures for new refrigerants. Thus, EPA requests comment 
    on whether it would be useful to have generic standards of purity for 
    new refrigerants and analytical protocols for acid, water, high-boiling 
    residues, chloride, and noncondensable gases for these refrigerants in 
    the absence of specific gas chromatography procedures to determine the 
    overall purity of these refrigerants.
        e. Possible Application of Standard of Purity to New Refrigerants. 
    EPA believes
    
    [[Page 32066]]
    
    that the vast majority of new refrigerant sold meets the ARI 700 
    standard. However, the Agency understands that on occasion, used or 
    otherwise contaminated refrigerant has been sold as ``new.'' In order 
    to ensure that the Agency can prevent the sale of contaminated 
    refrigerant that is labeled as ``new,'' EPA is requesting comment on 
    whether it should require new refrigerant to meet the ARI 700-1995 
    specifications. EPA also requests comment on whether producers or 
    sellers of new refrigerant should be required to analyze the 
    refrigerant before its sale, using the protocol set forth in ARI 700-
    1995.
    3. Leak Repair
        EPA is proposing to lower the permissible leak rates for some air-
    conditioning and refrigeration equipment containing more than 50 pounds 
    of CFC \22\ and HCFC refrigerant. EPA is also proposing to extend the 
    leak repair requirements (as they would be amended) to air-conditioning 
    and refrigeration equipment containing more than 50 pounds of HFC and 
    PFC refrigerant. Specifically, EPA is proposing to lower the 
    permissible annual leak rate for new commercial refrigeration equipment 
    to 10 percent of the charge per year, the permissible annual leak rate 
    for older commercial refrigeration equipment to 15 percent per year, 
    the permissible annual leak rate for some industrial process 
    refrigeration equipment to 20 percent of the charge per year, the 
    permissible annual leak rate for other new appliances (e.g., comfort 
    cooling chillers) to five percent of the charge per year, and the 
    permissible annual leak rate for other existing appliances to 10 
    percent of the charge per year. The proposed changes would become 
    effective thirty days after publication of the final rule except for 
    the provisions affecting industrial process refrigeration, which would 
    become effective three years after publication of the final rule. The 
    other aspects of the current leak repair provisions, such as time lines 
    for repair or retrofit, would remain the same.
    ---------------------------------------------------------------------------
    
        \22\ EPA is not aware of any manufacturers of new appliances who 
    are still using CFCs. However, in the event that such appliances 
    were manufactured, they would be subject to the new leak repair 
    requirements.
    ---------------------------------------------------------------------------
    
        The current permissible annual leak rates for commercial and 
    industrial process refrigeration and for other appliances are 35 
    percent per year and 15 percent per year respectively. These limits 
    were set based on information that EPA gathered regarding typical leak 
    rates for these types of equipment in 1991 and 1992. In several recent 
    meetings and conversations with EPA, industry representatives have 
    indicated that air-conditioning and refrigeration equipment 
    manufactured over the past few years has been designed to leak at lower 
    rates than air-conditioning and refrigeration equipment manufactured 
    earlier, and that existing appliances have often been modified with new 
    devices, such as high-efficiency purge devices for low-pressure 
    chillers, that have significantly lowered their leak rates. 
    Manufacturers have made these design changes, and owners have invested 
    in them, in response to growing environmental and economic concerns 
    associated with refrigerant emissions.
        a. Comfort Cooling Chillers. EPA's research indicates that the 
    reduction in leak rates has been most dramatic in comfort cooling 
    chillers, where leak rates have been lowered from between 10 and 15 
    percent per year to less than five percent per year in many cases. 
    Design changes that have contributed to this reduction include the 
    installation of high-efficiency purge devices on low-pressure chillers, 
    the installation of microprocessor-based monitoring systems that can 
    alert system operators to warning signs of leakage (such as excessive 
    purge run time), the use of leak-tight brazed rather than leak-prone 
    flared connections, and the use of isolation valves, which permit 
    technicians to make repairs without evacuating and opening the entire 
    refrigerant circuit. The first two conservation measures can be 
    implemented for existing as well as new equipment; the last two apply 
    primarily to new equipment.
        Manufacturers, servicers, and users of chillers state that, as a 
    result of these modifications, new chillers (those built since 1992) 
    typically leak less than five percent per year, with many new chillers 
    leaking around two percent per year, and some leaking less than one 
    percent. Only one type of new equipment has been reported to have a 
    leak rate above five percent; that is high-pressure chillers with open-
    drive compressors, which have been found to have leak rates ranging 
    from four to seven percent. Older chillers that have been modified with 
    emissions-reduction technologies are reported to leak between one and 
    10 percent per year. Where industry sources have not distinguished 
    between modified and unmodified older equipment, leak rates have been 
    reported to average four percent per year, indicating that most of the 
    chiller fleet has either been modified to leak less or is significantly 
    better maintained than it was five years ago.
        EPA believes that the reported performance of today's chiller fleet 
    argues for lowering the maximum permissible leak rate from 15% per 
    year. The leak repair requirement was promulgated under section 
    608(a)(2), which requires EPA to promulgate regulations regarding the 
    use and disposal of class I and class II substances, including 
    refrigerants, that reduce the use and emission of such substances to 
    the lowest achievable level. EPA believes that the evidence discussed 
    above demonstrates that the current 15-percent-per-year permissible 
    rate is considerably above the ``lowest achievable level of 
    emissions,'' especially for new equipment. (In fact, EPA acknowledged 
    in the May 14, 1993 rule that the 15-percent-per-year leak rate 
    probably was not the lowest achievable level for at least some comfort 
    cooling equipment, but the Agency did not have sufficient information 
    at that time to develop stricter or more refined standards.)
        While section 608(a)(2) does not require EPA to perform a cost-
    benefit analysis to determine what leak rate(s) would constitute the 
    ``lowest achievable level of emissions,'' such cost-benefit analyses 
    support establishing lower leak rates. One such analysis simply deduces 
    from achieved leak rates that a lower permissible leak rate would be 
    publicly cost-effective. The leak rates reported above, which generally 
    fall well below the current regulatory maximum, are clearly being 
    achieved in response to private incentives alone. If maintaining these 
    leak rates is privately cost-effective, it must be publicly cost-
    effective, because the public cost of emissions, which includes both 
    the private value of the refrigerant and the environmental damage it 
    causes, exceeds the private cost of emissions, which includes only the 
    private value of the refrigerant.
        In another analysis, EPA directly examined the public cost-
    effectiveness of certain types of leak repair and equipment 
    modification. First, EPA estimated the public benefits of avoiding 
    emissions of refrigerant on a per kilogram basis. Second, EPA 
    calculated the leak reductions that would have to be achieved through 
    repairs and modifications to produce benefits to offset their costs. In 
    general, EPA found that reductions in leak rates on the order of two to 
    10 percent of the charge per year had to be achieved to justify the 
    cost of the leak repair or equipment modification. These reductions are 
    comparable to those that have already been achieved over the last four 
    years through the implementation of leak repair and equipment
    
    [[Page 32067]]
    
    modification, providing additional evidence that leak rates below the 
    current 15 percent permissible rate can be cost-effectively achieved.
        Because EPA's data indicates that new chillers leak less than 
    existing chillers, and because some leak reduction modifications can be 
    applied to new, but not to existing, equipment, EPA is proposing a more 
    stringent standard for new chillers than for older chillers. For 
    chillers built in 1993 or later, EPA is proposing a maximum permissible 
    leak rate of five percent per year. With one exception, the reported 
    leak rates for new chillers all fall below this rate, and the 
    exception, the open-drive type of high pressure chiller, has leak rates 
    between four and seven percent. EPA believes that with careful 
    maintenance, even these chillers can maintain a leak rate below five 
    percent. However, if they cannot, EPA requests comment on whether EPA 
    should establish a larger maximum leak rate for this type of chiller. 
    EPA is currently disinclined to establish a special, larger rate, 
    because EPA believes that, if necessary, chiller designs with lower 
    inherent leak rates can be substituted for the high-pressure, open-
    drive type at little or no additional cost.
        For chillers built in 1992 or earlier, EPA is proposing a maximum 
    permissible leak rate of 10 percent per year. This rate is consistent 
    with the data provided to EPA for fleets that include modified 
    equipment. While EPA considered setting the leak rate for older 
    equipment equal to that for new equipment, information gathered to date 
    indicates that it may be difficult to reduce the emissions of some 
    older equipment to much below 10 percent of the charge per year without 
    undertaking the wholesale replacement of existing joints and seals, 
    which would prove prohibitively expensive. EPA requests comment on the 
    proposed leak rates for both new and existing equipment.
        Finally, EPA requests comment on whether there are any appliances 
    that would be classified as ``Appliances other than commercial or 
    industrial process refrigeration'' that are not comfort cooling 
    chillers and that could not attain the five and 10 percent per year 
    maximum permissible leak rates that are being proposed for new and 
    existing appliances of this type. EPA currently believes that the vast 
    majority, if not all, of the appliances classified as ``Appliances 
    other than commercial or industrial process refrigeration'' are comfort 
    cooling chillers and can attain the proposed rates.
        b. Commercial Refrigeration. In general, leak rates are higher in 
    the commercial refrigeration sector than in the chiller sector. In 
    large part, this is attributable to the facts that (1) equipment in the 
    commercial refrigeration sector is largely assembled in the field (in 
    the grocery store or food storage warehouse) rather than in the factory 
    and (2) commercial refrigeration equipment generally uses a long single 
    refrigerant loop for cooling rather than a short primary refrigerant 
    loop with a secondary loop containing water or brine. The first fact 
    makes it more difficult for original equipment manufacturers to 
    systematically implement leak reduction technologies for commercial 
    refrigeration equipment than for chillers (in fact, in a sense, each of 
    the hundreds of contractors who install the equipment nationwide is a 
    ``manufacturer''), and the second tends to raise average leak rates, 
    particularly when the refrigerant loop flows through inaccessible 
    spaces, such as underneath floors. In addition to these considerations, 
    the need to operate commercial refrigeration equipment continuously to 
    keep products from spoiling makes leak repair more difficult.
        Nevertheless, data from manufacturers and owners of commercial 
    refrigeration equipment indicates that leak rates considerably lower 
    than 35 percent per year can be achieved cost effectively with this 
    equipment. A study sponsored by EPA's Office of Research and 
    Development analyzed two detailed bodies of data on leakage from 
    commercial refrigeration equipment, one collected by a Midwestern chain 
    of 110 stores and the other gathered by the South Coast Air Quality 
    Management District (SCAQMD), which requires monitoring and reporting 
    of leak rates from large refrigeration systems. The Midwestern chain 
    achieved an average leak rate of 15 percent by establishing written 
    procedures for equipment installation (including a requirement that 
    expansion valves be brazed or ``sweated''), a refrigerant monitoring 
    system, and an equipment inspection protocol. This rate was achieved in 
    1992, before EPA's leak repair requirements were even in effect. The 
    data collected by SCAQMD was based 440 recharging and leak testing 
    events from 56 different stores representing 20 different businesses. 
    The average leak rate achieved by the stores was eight percent of total 
    charge.
        The ORD report also investigated the cost-effectiveness of 
    different strategies and technologies for reducing leak rates, finding 
    that many of these approaches could lower leak rates significantly and 
    thereby pay for themselves. Using a combination of these approaches, a 
    number of chains had significantly reduced both overall refrigerant 
    consumption and leakage from equipment over the previous two to eight 
    years. Some of the most effective approaches included vibration 
    elimination devices, use of high-quality brazed rather than mechanical 
    connections, low emission condensers, stationary leakage monitors, 
    refrigerant tracking and improved preventive maintenance. A few of the 
    approaches, such as installation of low-emission condensers, were more 
    applicable to new than to existing equipment; however, many of the 
    approaches, such as refrigerant monitors, refrigerant tracking systems, 
    and improved preventive maintenance, were applicable to both existing 
    and new equipment. These approaches were individually expected to 
    reduce leak rates from equipment by between five and forty percent of 
    the charge per year.
        In light of this information, EPA is proposing to establish lower 
    permissible leak rates for commercial refrigeration equipment. Although 
    neither the Midwestern chain nor SCAQMD distinguished between new and 
    old equipment in measuring leak rates, equipment manufacturers (ARI) 
    have stated that leak rates in new equipment are likely to be lower 
    than leak rates in old equipment. This statement, along with the fact 
    that some leak reduction technologies are applicable to new but not to 
    older equipment, indicates that it would be appropriate to establish 
    different permissible leak rates for new and old commercial 
    refrigeration equipment. EPA is therefore proposing that the maximum 
    permissible leak rate for new commercial refrigeration equipment 
    (commissioned after 1992) be lowered to 10 percent per year, and that 
    the maximum rate for old commercial refrigeration equipment 
    (commissioned before or during 1992) be lowered to 15 percent per year. 
    EPA believes that these rates are appropriate in view of the average 
    leak rates achieved in the South Coast Air Quality Management District 
    and in the Midwestern chain and in view of the availability of 
    effective leak reduction approaches.
        EPA requests comment on these proposed rates. First, EPA requests 
    comment on whether the relatively low leak rates observed in new 
    equipment are likely to persist throughout its lifetime, or whether 
    those rates are likely to rise over its lifetime to approach the 
    current leak rates of older equipment. In other words, does new 
    equipment leak less simply because it has endured less wear and tear 
    than older equipment, or is new equipment now manufactured and 
    installed in a
    
    [[Page 32068]]
    
    way that will minimize leakage over its entire life? Second, EPA 
    requests comment on whether higher or lower rates might be appropriate 
    for different types of commercial refrigeration equipment, given that 
    compressor rack systems, single compressor systems, and self-contained 
    units may have significantly different average leak rates. For 
    instance, because compressor rack systems may include miles of piping 
    and numerous connections that provide many opportunities for leakage, 
    one might expect them to leak a greater percentage of their charge than 
    self-contained units that include only a few feet of piping. Third, EPA 
    requests comment on whether significant percentages (e.g., 10 percent 
    or more) of the various types of commercial refrigeration equipment 
    might not be able to comply with leak rates of 10 or 15 percent without 
    being totally replaced, and, if this is the case, whether permissible 
    leak rates of 15 and 20 percent might be more achievable.
        c. Industrial Process Refrigeration. As is the case for commercial 
    refrigeration equipment, leak rates in industrial process refrigeration 
    equipment have been falling, but the rates and consistency of decline 
    across equipment types have been lower than for comfort cooling 
    chillers. While some industrial process refrigeration equipment has 
    attained leak rates between five and 10 percent per year, other 
    equipment has continued to leak near the 35-percent-per-year maximum 
    permissible rate despite the growing price of refrigerants over the 
    past five years. The conditions that contribute to a wide range of leak 
    rates in the commercial refrigeration sector apply even more to the 
    industrial process refrigeration sector. Equipment in the industrial 
    process refrigeration sector is not only assembled on site, but is 
    often custom-designed for a wide spectrum of processes and plants, 
    giving the sector an extraordinarily broad range of equipment 
    configurations and designs. Equipment may be high- or low-pressure; may 
    possess hermetic, semi-hermetic, or open-drive compressors; may use one 
    (primary) or two (primary and secondary) refrigerant loops; may be 
    brand new or decades old; and may range in charge size from a few 
    hundred to over 100,000 pounds of refrigerant. All of these factors are 
    important in determining leak rates, leading to the observed range 
    mentioned above.
        Specifically, as is true for chillers, and, to some extent, for 
    retail food refrigeration equipment, industrial process refrigeration 
    equipment built more recently has generally been designed to leak less 
    than equipment built earlier. Similarly, equipment containing hermetic 
    compressors tends to leak less than equipment containing open-drive 
    compressors, because the latter possess openings for their drive 
    shafts, compromising the integrity of the system. Single loop, direct 
    expansion systems tend to leak more than systems possessing a secondary 
    water or brine loop because the former tend to have longer refrigerant 
    loops than the latter, increasing opportunities for leakage. Large 
    equipment may leak more than small equipment for two reasons. First, 
    large equipment tends to be custom-built rather than built on an 
    assembly line in a factory, making it more difficult to regulate 
    manufacturing techniques (joint construction, etc.) that affect 
    leakage. Second, large equipment tends to have more piping and joints 
    than small equipment, increasing the number of potential leak sites.
        EPA believes that it is appropriate to consider the date of 
    manufacture, compressor configuration, and possession (or lack) of a 
    secondary loop in determining maximum allowable leak rates for 
    industrial process refrigeration equipment. However, the Agency is 
    reluctant to permit higher leak rates for equipment with very large 
    charge sizes. This is because a given leak rate in large equipment 
    causes more environmental harm than the same leak rate in small 
    equipment. For example, a 20% per year leak rate in equipment with a 
    10,000 pound charge would result in the release of 2,000 pounds of 
    refrigerant per year, while a 20% per leak rate in equipment with a 
    1,000 pound charge would result in the release of 200 pounds of 
    refrigerant per year. Thus, although it may be more difficult or 
    expensive to achieve a given leak rate in large equipment than in small 
    equipment, EPA believes that these additional efforts are warranted by 
    the larger environmental impact of leaks from large equipment.
        In view of these considerations, EPA is proposing different maximum 
    permissible leak rates based on the equipment's date of manufacture, 
    compressor configuration, and number of refrigerant loops (primary only 
    vs. primary and secondary). EPA thereby expects to increase 
    environmental protection (by lowering the permissible rate where it can 
    be lowered) without imposing undue costs (by accommodating types of 
    equipment for which the rate cannot be lowered). At the same time, 
    however, the Agency wishes to minimize the confusion that might be 
    associated with having multiple permissible rates that are keyed to 
    different combinations of the above criteria. EPA is therefore is 
    proposing a two-rate system for the industrial process sector. As is 
    the case for the comfort cooling and commercial refrigeration sectors, 
    EPA believes that these changes are necessary to carry out section 
    608(a)(2) of the Act.
        Under the proposed approach, industrial process refrigeration 
    equipment would be subject to a 20 percent per year maximum permissible 
    leak rate unless it met all four of the following criteria:
        (1) The refrigeration system is custom-built;
        (2) The refrigeration system has an open-drive compressor;
        (3) The refrigeration system was built in 1992 or before; and
        (4) The system is direct-expansion (contains a single, primary 
    refrigerant loop).
        Systems that met conditions 1, 2, 3, and 4 would continue to be 
    subject to the 35-percent-per-year maximum permissible leak rate.
        The Agency requests comment on the approach, both on the criteria 
    used to sort equipment between the 20% and 35% per year rates, and on 
    the rates themselves. EPA specifically requests comment on whether it 
    might be appropriate to permit a higher leak rate for equipment with a 
    charge size above 10,000 lbs. As noted above, EPA is reluctant to 
    permit higher leak rates for large equipment due to the greater 
    environmental impact of a given leak rate from large equipment; 
    however, if it is demonstrably impossible to reduce the leak rate of 
    such equipment without undertaking a massive overhaul, EPA could 
    consider permitting a higher leak rate for large equipment built before 
    1992. The Agency believes that large equipment built more recently 
    should be able to maintain a leak rate of 20% per year. The Agency also 
    requests comment on whether it would be appropriate to use a measure 
    other than charge size to characterize sprawling, inherently leaky 
    equipment. The Agency is concerned that the proposed characterization 
    might inappropriately permit high leak rates for some large equipment 
    that does not possess an inherently leaky configuration. One 
    alternative would be to use pipe length rather than charge size to 
    characterize equipment as having a leaky configuration.
        In addition, EPA requests comment on the interchangeability of 
    leaky and non-leaky equipment designs. That is, are there compelling 
    reasons why users of industrial process refrigeration must use open-
    drive compressors or direct expansion systems rather than hermetic 
    compressors and secondary loops? The Agency understands that it may be
    
    [[Page 32069]]
    
    difficult to transform an existing direct expansion system into a 
    system with a secondary loop. However, persons installing new systems 
    might be expected to have more flexibility.
        Other possible approaches to leak repair in industrial process 
    refrigeration equipment could be either more or less complex than the 
    one proposed. A simple approach would lower the current permissible 
    leak rate for all industrial process equipment to a single new rate, 
    perhaps to 25 percent per year. While this approach would be 
    administratively simple, however, it could be costly if a significant 
    fraction of existing equipment was not able to meet the new rate 
    without massive overhaul or replacement. Based on its discussions with 
    users of industrial process refrigeration equipment, EPA believes that 
    this is indeed the case. A more complex approach would establish three 
    or more permissible rates for different classes of equipment based on 
    the above criteria. However, although this approach would better tailor 
    permissible leak rates to the inherent leak rates of different types of 
    equipment, the Agency believes that any environmental or economic gains 
    that might be achieved through such an approach would not justify its 
    complexity and associated difficulty of implementation. EPA requests 
    comment on these potential alternative approaches.
        EPA is proposing to make the new leak rates effective for 
    industrial process refrigeration equipment three years after 
    promulgation of this rule. EPA is proposing this delayed effective date 
    for industrial process refrigeration equipment for several reasons. 
    First, the current leak repair requirements for industrial process 
    refrigeration equipment only became effective in September 1995, over 
    two years later than the leak repair requirements for other equipment. 
    Owners and servicers of industrial process refrigeration equipment have 
    therefore had considerably less time than owners and servicers of other 
    types of equipment to learn and implement the existing maximum 
    permissible rates. Thus, promulgating new maximum permissible rates 
    with immediate effective dates would lead to considerable confusion and 
    disruption in this sector, while, inversely, promulgating new rates 
    with delayed effective dates would permit this sector to make an 
    orderly transition between the old and new rates. Second, because it is 
    custom-built, industrial process refrigeration equipment takes longer 
    than other types of equipment to build and to repair. The proposed lead 
    time between promulgation and effective date would permit equipment 
    users sufficient time to order replacement parts or systems that might 
    be necessary to meet the new rates. Finally, industrial processes must 
    be shut down, at considerable expense, before large repairs can be made 
    to their refrigeration systems or before such systems can be replaced. 
    According to industry sources, shutdowns are usually only scheduled to 
    occur every two to five years. Again, this argues for permitting 
    significant lead time between the promulgation and effective date of 
    the new leak rate. EPA requests comment on its proposed three-year 
    delay.
        d. Cross-sector Issues. EPA is also requesting comment on four 
    issues that affect all three sectors covered by the leak repair 
    requirements. First, EPA requests comment on its proposal to 
    distinguish between old and new equipment in establishing maximum 
    allowable leak rates. In general, the Agency believes that equipment 
    manufactured after 1992 is, by a significant margin, inherently more 
    leak-tight than equipment manufactured before that date. This means 
    that significantly lower leak rates can be maintained in new equipment 
    than in old equipment for about the same cost. If EPA were to set a 
    single allowable leak rate for old and new equipment, this rate would 
    probably be either difficult to attain in old equipment, forcing the 
    expensive retrofit or replacement of the equipment, or above the rate 
    achievable by new equipment, permitting emissions significantly above 
    the lowest achievable level. However, EPA recognizes that implementing 
    two leak rates for each type of equipment would be more 
    administratively complex than implementing a single leak rate for each 
    type of equipment. To implement two leak rates, equipment owners, 
    operators, and technicians would have to remember both rates, and they 
    would have to be able to distinguish old from new equipment. Based on 
    current information, EPA does not believe this would constitute an 
    unreasonable burden or lead to excessive confusion. However, the Agency 
    requests comment on whether the environmental and economic benefits of 
    having two leak rates justify the increase in administrative complexity 
    that results from this approach.
        Second, if the final regulations distinguish among appliances based 
    on their dates of manufacture, EPA requests comment on whether the date 
    of ``manufacture'' should be defined as the date that appliance leaves 
    the factory or the date that it is installed. The Agency believes that 
    it may be appropriate to define ``manufacture'' differently for 
    different types of appliances. Appliances that are relatively compact 
    and complete when they leave the factory, such as chillers, could be 
    considered ``manufactured'' when they leave the factory, while 
    appliances that are assembled in the field from numerous components, 
    such as commercial and industrial process refrigeration equipment, 
    could be considered ``manufactured'' (or ``commissioned'') when their 
    installation is complete.
        Third, EPA requests comment on the proposed use of the year 1992 as 
    the dividing line between more and less strictly regulated equipment. 
    EPA's research indicates that by the end of that year, most equipment 
    was being manufactured to leak significantly less than equipment built 
    earlier. However, if a significant fraction of equipment manufactured 
    since 1992 still cannot attain the proposed maximum leak rate, it may 
    be appropriate to make the stricter requirements effective for 
    equipment built after 1999 (or whatever year follows the year of 
    publication of the final rule). This would permit equipment purchasers 
    to consider the leakiness of certain types of equipment in their 
    purchasing decisions from now on, allowing for the lag time between 
    equipment ordering and manufacture.
        Fourth, EPA requests comment on whether it is possible to 
    distinguish between slow leakage, servicing emissions, and catastrophic 
    emissions in establishing and complying with leak rate limits. This 
    question becomes important with a lower permissible leak rate because 
    the percentage of charge lost through servicing and catastrophic 
    emissions may be a significant fraction of the lower rate. The goal of 
    the leak repair provisions has primarily been to reduce emissions from 
    slow leakage, because servicing emissions are addressed by the rule's 
    recycling requirements and catastrophic emissions (such as those 
    resulting from the triggering of a pressure relief valve) are often 
    beyond the control of equipment owners. Thus, if possible, EPA would 
    like to establish a leak rate based on slow leaks alone. Even if it is 
    not possible to isolate slow leaks from all other types of emissions, 
    EPA would like to avoid establishing a relatively high permissible leak 
    rate based in part on servicing or catastrophic emissions if it is 
    possible to distinguish either one of these types of emissions from 
    slow leaks. On the other hand, the Agency would like to avoid 
    establishing an overly stringent leak rate based on
    
    [[Page 32070]]
    
    hypothetical emissions from slow leaks if in practice these cannot be 
    distinguished from other types of emissions.
        Based on information gathered to date, EPA believes that servicing 
    emissions and slow leakage may be difficult to separate, since the 
    precise amount of refrigerant lost from equipment may not be known 
    until the equipment is recharged after servicing. However, EPA believes 
    that it should be possible to distinguish between catastrophic and slow 
    emissions. Catastrophic losses will generally come to the attention of 
    equipment owners very quickly after they occur and will be large (for 
    the piece of equipment that experiences a catastrophic loss) compared 
    to losses from slow emissions. Moreover, because correcting the 
    conditions that led to the catastrophic release (e.g., correcting the 
    conditions that led to an over-pressure situation) would be considered 
    to repair the ``leak,'' catastrophic losses would not be expected to 
    compromise compliance with the permissible leak rate. Based on 
    discussions with persons who maintain chillers, EPA believes that 
    catastrophic losses are greater than servicing losses for these 
    appliances. EPA has less information on the relationship between 
    catastrophic losses and servicing emissions for commercial and 
    industrial process refrigeration equipment.
        EPA requests comment on whether its understanding of the 
    separability and relative significance of the various types of 
    emissions is correct. EPA also requests that, to the extent possible, 
    commenters distinguish between servicing emissions, catastrophic 
    losses, and losses from slow leaks in their comments on what leak rates 
    are achievable.
        e. Coverage of HFC and PFC Appliances. EPA believes that 
    establishing consistent leak repair requirements for CFC, HCFC, HFC, 
    and PFC appliances is necessary to minimize emissions of all four types 
    of refrigerants. As noted above, industry representatives emphasized 
    that exempting HFC and PFC refrigerants from conservation requirements 
    could lead to confusion and skepticism regarding similar requirements 
    for CFCs and HCFCs, which would undermine implementation of the 
    statutory directives to reduce emissions of these substances to the 
    lowest achievable level and to maximize their recapture and recycling. 
    For instance, if owners or operators of refrigeration systems could 
    permit HFC systems to leak, they might fail to establish or maintain 
    leak repair procedures or systems for any of their refrigeration 
    equipment, including CFC or HCFC systems (particularly if these were in 
    the minority at a given site), forgetting or never realizing that the 
    latter were subject to repair requirements. Moreover, in any given 
    application, there is no technological difference between CFC, HCFC and 
    HFC appliances that makes leaks easier to control for one type of 
    refrigerant than the other. Technology and techniques developed to 
    reduce CFC and HCFC emissions can be easily applied to reducing HFC and 
    PFC emissions. Finally, the release of all four types of refrigerants 
    could pose a threat to the environment. EPA is therefore proposing 
    requirements for CFC, HCFC, HFC, and PFC appliances that recognize the 
    design and maintenance advances of the last few years.
        f. Clarification of Current Requirements. i. Compliance Scenarios
        The initial final rule (May 14, 1993, 58 FR 28660) required owners 
    and operators to ``have all leaks repaired'' where an appliance subject 
    to the leak repair requirements was leaking above the applicable 
    allowable annual leak rate (58 FR 28716). In a subsequent rulemaking 
    regarding leak repair requirements published August 8, 1995 (60 FR 
    40420), EPA amended that language to state that ``repairs must bring 
    the annual leak rate to below 35 percent of the total charge during a 
    12-month period'' (60 FR 40440) or where appropriate, to below 15 
    percent. This change in the rule recognizes that appliances without 
    hermetically sealed refrigerant circuits should not be expected to have 
    a ``zero'' leak rate. Moreover, EPA also believes that it is practical 
    to require the owners or operators to maintain a leak rate that is at 
    or below the applicable allowable annual rate, and where this leak rate 
    has been exceeded, to make the necessary repairs to return the 
    appliance's leak rate to or below the applicable allowable leak rate or 
    to retrofit/retire the appliance. Leaving leaks unrepaired does not 
    necessarily equate to non-compliance; however, maintaining a leak rate 
    above the maximum leak rate of either 15 or 35 percent is non-
    compliance.
        For industrial process refrigeration equipment and for federally-
    owned commercial refrigeration equipment and federally-owned comfort 
    cooling appliances located in areas subject to radiological 
    contamination, EPA requires owners and operators to perform 
    verification tests to establish that repairs were successful. EPA 
    recognizes that verification tests indicate the success or failure of 
    the repair effort for a given leak or set of leaks, not the leak rate 
    of an appliance. In the August 8, 1995 rulemaking, EPA stated that it 
    was not the Agency's ``intention to imply that the verification test 
    shows what the leak rate is. However, EPA believes that where the 
    verification test shows that the repairs have been successful, in most 
    cases this will mean that there has been a reduction in the leak rate'' 
    (60 FR 40430). EPA recognizes that knowing a leak has been repaired 
    does not necessarily mean that the owner or operator knows what the 
    current leak rate is. EPA further stated that ``if more than one leak 
    exists, it is possible that the leak rate could remain above acceptable 
    levels. In such cases the owners or operators would be expected to take 
    reasonable actions'' (60 FR 40430). EPA believes that where owners or 
    operators employ sound professional judgement in responding to a leak 
    rate above the applicable allowable annual leak rate they will reduce 
    the appliance's leak rate to below the applicable allowable annual leak 
    rate.
        Section 82.156(i) requires owners or operators to conduct repair 
    efforts to lower an appliance's leak rate to below the applicable 
    allowable annual leak rate. EPA is describing the following scenarios 
    to assist the owners or operators in determining what actions must be 
    taken when an appliance is leaking above the applicable allowable 
    annual leak rate. EPA believes that by describing four likely 
    scenarios, EPA can further clarify for the regulated community how the 
    leak rate and verification tests relate to the repair and/or retrofit/
    retire provisions promulgated at Sec. 82.156(i).
        In the first scenario, the owner or operator discovers that the 
    appliance is leaking above the applicable allowable annual rate. The 
    owner or operator fixes all leaks and verifies that the leaks have been 
    repaired consistent with Sec. 82.156(i). Therefore, where sound 
    professional judgement has been successfully executed, the appliance 
    will have a leak rate below the applicable allowable annual rate. If a 
    leak rate above the applicable allowable annual rate is again suspected 
    a short time after the repairs were completed (perhaps only a few 
    weeks) and leaks are discovered at a new location, these leaks would be 
    considered new leaks. The owner or operator must comply with all 
    applicable requirements promulgated at Sec. 82.156(i) for these new 
    leaks.
        In the second scenario, the owner or operator discovers that the 
    appliance is leaking above the applicable allowable annual leak rate. 
    The owner or operator fixes the leaks and verifies that they
    
    [[Page 32071]]
    
    have been repaired consistent with Sec. 82.156(i). Therefore, the owner 
    or operator believes the appliance is not leaking above the applicable 
    allowable annual leak rate. The next time leaks are suspected, the 
    owner or operator finds leaks have occurred at the same location. Since 
    the initial leaks were repaired and properly verified consistent with 
    the regulation, leaks at the same location would be considered new 
    leaks. If the leak rate is again above the applicable allowable annual 
    leak rate, the owner or operator must repair the leaks and, where 
    appropriate, perform verification tests, retrofit the appliance, or 
    retire the appliance consistent with the requirements promulgated at 
    Sec. 82.156(i). However, if repeated leaks continue to occur at the 
    same location, this ongoing problem may be an indication that 
    appropriate repairs have not actually been conducted. For example, the 
    particular leak point may involve the connection of two parts that 
    appears to have loosened. Rather than repeatedly tightening the 
    connection, the parts may need to be replaced. EPA believes that where 
    leaks at the same location continue to occur, the owner or operator may 
    not have used sound professional judgement in determining what repair 
    efforts are necessary to reduce the leak rate to below the applicable 
    allowable annual leak rate. Thus, the owner or operator would have 
    violated with the requirements in Sec. 82.156(i).
        In the third scenario, the owner or operator discovers that the 
    appliance is leaking above the applicable allowable annual rate and 
    identifies ten different leak sources that are contributing to the high 
    leak rate. The owner or operator determines that repairing six leaks 
    will bring the appliance into compliance by lowering the leak rate to 
    below the applicable allowable annual rate. The owner or operator 
    believes that leaving four leaks unrepaired still will result in a leak 
    rate below the applicable allowable annual rate. The owner or operator 
    fixes and verifies that these six leaks have been repaired consistent 
    with the requirements promulgated at Sec. 82.156(i). The appliance 
    continues to leak, but below the applicable allowable annual rate. In 
    this scenario the owner or operator of the appliance complied with the 
    requirements by actually reducing and maintaining a leak rate that is 
    below the applicable allowable annual rate.
        In the fourth scenario, the owner or operator discovers that the 
    appliance is leaking above the applicable allowable annual rate. The 
    owner or operator identifies ten different leak sources that are 
    contributing to the leak rate. The owner or operator decides that 
    repairing six leaks will bring the appliance into compliance by 
    lowering the leak rate to below the applicable allowable annual rate. 
    The owner or operator fixes and verifies that these leaks have been 
    repaired consistent with the requirements promulgated at 
    Sec. 82.156(i). Upon later inspection, it is discovered that the 
    appliance continued leaking above the applicable allowable annual rate 
    and there are no newly identified leak sources. In this scenario the 
    owner or operator never brought the leak rate below the applicable 
    allowable leak rate, and hence violated Sec. 82.156(i), regardless of 
    whether the owner or operator exercised sound professional judgement in 
    deciding upon the leaks to be repaired.
        EPA views the above scenarios as consistent with the current 
    regulatory requirements. Therefore, today's action does not propose any 
    regulatory changes associated with these scenarios. Nevertheless, EPA 
    requests comment on the guidance presented for these four scenarios.
        ii. Recordkeeping for leak repair. EPA received information from 
    CMA indicating that the recordkeeping and reporting requirements 
    promulgated at Sec. 82.166(n) may be confusing for those subject to the 
    requirements. EPA notes that the structure of these provisions did 
    change between the proposed and final notices (January 19, 1995, 60 FR 
    3992, and August 8, 1995, 60 FR 40420) to ensure that the format was 
    consistent with the requirements established by the Office of the 
    Federal Register. The August 8, 1995 final rule requires the same 
    information to be maintained or submitted as EPA proposed in the 
    January 19, 1995, except as discussed in the preamble to the August 8, 
    1995 final rule.
        CMA and its members requested that EPA consider whether these 
    provisions could be redrafted for clarity. EPA agrees that the 
    readability of these provisions can be improved. Therefore, EPA is 
    proposing to modify the presentation of the requirements to more 
    clearly indicate what records must be kept and what information must be 
    reported. EPA is not proposing any changes in the substance of the 
    requirements. EPA requests comment on these proposed changes and 
    whether they improve readability of the provisions.
        iii. Replacement refrigerants. EPA is proposing to amend 
    Sec. 82.156(i)(6) to incorporate a requirement that was discussed in 
    the preamble to the May 14, 1993 initial final rule (58 FR 28680) but 
    that was inadvertently excluded from the regulatory text. In the 
    preamble, EPA indicated that if the owners or operators elect to 
    retrofit an appliance rather than repair leaks that are above the 
    applicable allowable annual rate, the owners or operators must use a 
    refrigerant with a lower ozone-depleting potential (ODP) than the 
    original refrigerant. Owners and operators would still retain the 
    options of either retiring the appliance or repairing the existing 
    leaks in accordance with the existing requirements. EPA refers readers 
    to the preamble discussion in the May 14, 1993 rule for additional 
    information. EPA believes this proposed change is important to minimize 
    the use of refrigerants that are potentially more harmful to 
    stratospheric ozone. It would be environmentally unsound to exempt 
    owners or operators from repairing leaks on the grounds that they will 
    retrofit or replace the leaky appliance if the replacement refrigerant 
    would pose an equivalent or even greater threat to the stratospheric 
    ozone. Therefore, EPA is today proposing to modify the regulatory text 
    to ensure that only a substitute refrigerant with a lower ODP is used. 
    EPA requests comment on this proposed regulatory change.
        iv. Minor Clarifications. EPA is proposing to modify the text 
    throughout Sec. 82.156(i) and Sec. 82.166(n) and (o) to substitute the 
    word ``retire'' for the word ``replace'' and to add ``operators'' where 
    the regulation inadvertently refers solely to owners. EPA believes 
    these changes are necessary because the term ``retire'' better 
    describes the activities that are discussed and because the 
    requirements are applicable to both owners and operators.
        EPA is also proposing to modify Sec. 82.156(i)(3), which requires 
    owners and operators to exercise sound professional judgement and to 
    perform verification tests, to clarify that it applies to all owners 
    and operators of industrial process refrigeration equipment and not 
    just to those who are granted additional time under paragraph (i)(2). 
    At the same time, EPA is proposing to clarify that the paragraph 
    applies to owners and operators of federally-owned commercial 
    refrigeration equipment and of federally-owned comfort cooling 
    appliances who are granted additional time under paragraphs (i)(1) and 
    (i)(5). In the preamble to the August 8, 1995 rule, EPA stated that 
    initial and follow-up verification tests must be performed even where 
    the repairs are completed within 30 days (60 FR 40430). EPA 
    inadvertently neglected to make the corresponding change to the 
    regulatory text. Therefore, EPA is proposing to change the first 
    sentence in the
    
    [[Page 32072]]
    
    paragraph to the following: ``Owners or operators of federally-owned 
    commercial refrigeration equipment or of federally-owned comfort 
    cooling appliances who are granted additional time under paragraphs 
    (i)(1) or (i)(5) of this section, and owners or operators of industrial 
    process refrigeration equipment, must have repairs performed in a 
    manner that sound professional judgment indicates will bring the leak 
    rate below the applicable allowable leak rate.''
        In addition, EPA is proposing to amend Sec. 82.156(i)(3)(ii) and 
    (i)(6)(i) to provide owners and operators 30 days to prepare and 1 year 
    to execute a retrofit/retirement plan, where the owners or operators 
    have unsuccessfully attempted to repair the appliance and therefore are 
    switching to a retrofit/retirement mode. Section 82.156(i)(3)(ii) 
    permits owners and operators who are unable to verify that repairs have 
    been successful to switch to a retrofit/retirement mode. EPA is 
    proposing to delete from this paragraph the phrase ``* * * of this 
    section within one year after the failure to verify that repairs had 
    been successfully completed.'' This phrase starts the one-year 
    retrofit/retirement implementation clock based on the date of the 
    failed verification test. EPA provided this provision because the 
    Agency believes it is appropriate to permit the owner or operator of 
    industrial process refrigeration equipment that fails a follow-up 
    verification test to complete a retrofit within approximately one year 
    of that failed test in situations where the owner or operator made good 
    faith efforts to repair an appliance before deciding to switch to a 
    retrofit or retirement mode.
        However, in establishing this provision, EPA was concerned with the 
    potential to abuse such a safeguard. Owners and operators who realize 
    that a retrofit or retirement is necessary could attempt to repair the 
    appliance while knowing such efforts were useless, merely to extend the 
    date by which a retrofit or retirement must be completed. In an effort 
    to limit abuse in this situation, the current regulations provide that 
    the one-year time frame to complete a retrofit or retirement is 
    triggered by the date of the failure to verify successful repairs. 
    However, concerns have been raised regarding whether this limited time 
    frame inadvertently increases the burden for those that made good faith 
    efforts to repair the appliances, by lessening the retrofit/retirement 
    clock by up to 30 days. In addition, those who intentionally violate 
    the spirit of this good faith provision still could seek some extra 
    time by pursuing useless repairs, albeit 30 days less than what is 
    potentially available under the current regulations.
        While EPA does not believe this 30-day difference imposes a 
    significant burden under the current regulations, EPA recognizes the 
    need to provide the owners or operators with sufficient time to develop 
    and implement retrofit or retirement plans. Therefore, EPA is proposing 
    to eliminate the reference to the date of the failure to verify that 
    repairs have been successfully completed. By deleting this reference, 
    owners or operators would have 30 days from the failure to verify that 
    the repairs were successful to develop a retrofit/retirement plan, and 
    one year from the plan's date to complete the retrofit or retirement, 
    or such longer time periods as may apply under 82.156(i)(7) and (i)(8). 
    EPA requests comment on these proposed changes.
        EPA is proposing to make several other minor clarifying changes to 
    the regulatory text. EPA is proposing changes at Secs. 82.156(i)(1), 
    (i)(2), (i)(3)(i), (i)(5), (i)(6)(i) and 82.166(o)(10)(i) and (ii). At 
    Secs. 82.156(i)(1), 82.156(i)(2) and 82.156(i)(5) EPA is proposing to 
    express maximum allowable leak rates in terms of the proposed defined 
    term, ``leak rate.'' EPA believes that these changes would make the 
    regulatory text more easily understood. In various sections of the 
    regulations, EPA is proposing a number of minor non-substantive wording 
    changes to make the regulatory text clearer and easier to read. None of 
    these additional modifications should affect the meaning of the 
    regulatory text.
        EPA requests comments on these proposed changes regarding whether 
    the changes will improve the clarity and readability of the regulatory 
    text.
    4. Proposed Changes for Servicing of MVAC-like Appliances
        a. Background. MVAC-like appliances are open-drive compressor 
    appliances used to cool the driver's or passenger's compartment of non-
    road motor vehicles, such as agricultural or construction vehicles. 
    MVAC-like appliances are essentially identical to motor vehicle air 
    conditioners (MVACs), which are subject to regulations promulgated 
    under section 609 of the Act. However, because MVAC-like appliances are 
    contained in non-road vehicles, they are subject to regulations 
    promulgated under section 608 of the Act.
        Due to the similarities between MVACs and MVAC-like appliances in 
    design and servicing patterns, EPA has established requirements 
    regarding the servicing of MVAC-like appliances that are very similar 
    to those for MVACs (58 FR 28686). In fact, many of the section 608 
    requirements for MVAC-like appliances that are published at subpart F 
    simply refer to the section 609 requirements for MVACs that are 
    published at subpart B. For instance, Sec. 82.156(a)(5) states that 
    persons who open MVAC-like appliances for maintenance, service, or 
    repair may do so only while ``properly using,'' as defined at 
    Sec. 82.32(e), recycling or recovery equipment certified pursuant to 
    Sec. 82.158(f) or (g) as applicable. The definition of ``properly 
    using'' appears in the regulations published at subpart B, and the 
    reference therefore subjects MVAC-like appliances to the evacuation and 
    refrigerant purity requirements of subpart B. Similarly, the equipment 
    and technician certification provisions applicable to MVAC-like 
    appliances in subpart F (Secs. 82.158(f) and 82.161(a)(5)) refer to the 
    equipment and technician certification provisions applicable to MVACs 
    in subpart B (Secs. 82.36(a) and 82.40).
        The section 609 and 608 regulations treat MVACs and MVAC-like 
    appliances (and persons servicing them) slightly differently in four 
    areas. First, persons who service MVACs are subject to the section 609 
    equipment and technician certification requirements only if they 
    perform ``service for consideration,'' while persons who service MVAC-
    like appliances are subject to the section 608 equipment and technician 
    certification requirements regardless of whether they are compensated 
    for their work.\23\ Second, persons who service MVACs must have a piece 
    of recovery and recycling equipment available at their place of 
    business, even if they never open the refrigeration circuit of the 
    MVACs (e.g., if they only perform top-offs). In contrast, persons who 
    service MVAC-like appliances are required to have a piece of recovery 
    and recycling equipment available at their place of business only if 
    they open the appliances (i.e., perform work that would release 
    refrigerant to the environment unless the refrigerant were recovered 
    previously). Third, recycling and recovery equipment that is intended 
    for use with MVACs and that was manufactured before the effective date 
    of the section 609 equipment certification provisions must be 
    demonstrated to be ``substantially identical'' to certified recycling 
    equipment, while recycling and recovery equipment that is intended for 
    use with MVAC-like appliances and that was manufactured before the 
    effective
    
    [[Page 32073]]
    
    date of the section 608 equipment certification provisions must simply 
    be able to pull a 4-inch vacuum. Finally, persons servicing MVAC-like 
    appliances have the option of becoming certified as Type II technicians 
    instead of becoming certified as MVAC technicians under subpart B. The 
    first three differences arise from differences between the statutory 
    requirements of sections 608 and 609; the last is intended to give 
    persons who service MVAC-like appliances flexibility in choosing the 
    type of training and testing most appropriate to their work.
    ---------------------------------------------------------------------------
    
        \23\ Note that persons servicing MVACs are subject to the 
    section 608 vending prohibition regardless of whether they are 
    compensated for their work.
    ---------------------------------------------------------------------------
    
        b. Recent Amendments to Subpart B. In a final rule published on 
    December 30, 1997 (62 FR 68025), EPA made several changes to the 
    provisions governing servicing of MVACs and MVAC-like appliances (as 
    they are currently defined) at subpart B. First, EPA extended the 
    regulations to MVACs containing substitutes for CFC and HCFC 
    refrigerants. Second, EPA explicitly allowed mobile servicing of MVACs 
    and MVAC-like appliances. That is, technicians are permitted to 
    transport their recovery or recycling equipment from their place of 
    business in order to recover refrigerant from an MVAC or MVAC-like 
    appliance before servicing it. Third, EPA permitted refrigerant 
    recovered from disposed MVACs or MVAC-like appliances to be reused in 
    MVACS or MVAC-like appliances, as long as the refrigerant was processed 
    through approved refrigerant recycling equipment before being charged 
    into the MVAC to be serviced.
        Fourth, EPA adopted new standards for recycling and recovery 
    equipment intended for use with MVACs. These new standards address HFC-
    134a recover/recycle equipment, HFC-134a recover-only equipment, 
    service procedures for HFC-134a containment, purity of recycled HFC-
    134a, recover/recycle equipment intended for use with both CFC-12 and 
    HFC-134a, and recover-only equipment designed to be used with any motor 
    vehicle refrigerants other than CFC-12 and HFC-134a. Please refer to 
    the December 30, 1997, final rule for a detailed explanation and 
    justification of these changes for MVACs.
        As noted above, these regulations apply both to MVACS containing 
    all types of refrigerant and to MVAC-like appliances containing class I 
    and class II substances. As is discussed at length in the final 
    amendment to subpart B, EPA believes that it is appropriate to cover 
    both MVACs and MVAC-like appliances under the subpart B regulations, 
    although EPA is relying on section 608 authority to cover MVAC-like 
    appliances. In brief, the rationale for this approach is that (1) MVACs 
    and MVAC-like appliance are very similar, and the requirements for 
    MVAC-like appliances under the subpart F regulations have historically 
    referred back to the requirements for MVACs under subpart B, and (2) 
    MVACs and MVAC-like appliances are often serviced by the same group of 
    people, and therefore publishing the requirements for both MVACs and 
    MVAC-like appliances in the same place will minimize confusion within 
    this group. Under this approach, most of the provisions governing MVAC-
    like appliances have been reproduced in the regulations at subpart B 
    and will be removed from the regulations at subpart F; an important 
    exception is the definition of MVAC-like appliance, which will remain 
    in the regulations at subpart F. Thus, the final subpart B rule covers 
    MVAC-like appliances as they are currently defined in the subpart F 
    regulations, which means MVAC-like appliances containing CFCs or HCFCs. 
    (However, the subpart B amendment does not affect the four differences 
    between the treatment of MVACs and MVAC-like appliances identified 
    above.)
        c. Today's Proposal. In this document, EPA is proposing to change 
    the definitions of ``appliance,'' ``MVAC-like appliance'' (which is 
    based on the definition of ``appliance''), and ``opening'' in subpart F 
    to include substitute refrigerants. This would effectively apply the 
    major requirements of the amended subpart B regulations (when this rule 
    was finalized) to MVAC-like appliances containing substitutes for CFCs 
    and HCFCs. EPA is also proposing editorial changes to eliminate 
    redundancy between the subpart B and subpart F rules in their treatment 
    of MVAC-like appliances.
        EPA believes that in order to implement the venting prohibition, it 
    is necessary to apply the major subpart B requirements (including the 
    requirements to properly use recycling and recovery equipment and to 
    certify recycling and recovery equipment and technicians) to MVAC-like 
    appliances containing substitute refrigerants. The basic rationale for 
    applying the subpart B requirements to MVAC-like appliances containing 
    substitute refrigerants is the same as that for applying the equivalent 
    subpart F requirements to other appliances containing substitute 
    refrigerants; this reasoning is presented throughout this document. In 
    the case of MVAC-like appliances, however, the similarities in design 
    and servicing patterns between MVACs and MVAC-like appliances make it 
    appropriate to subject MVAC-like appliances to the required practices 
    and certification programs established for MVACS in subpart B rather 
    than to the required practices and certification programs established 
    for stationary appliances in subpart F. (As noted above, the argument 
    for parallel coverage of MVACs and MVAC-like appliances was discussed 
    at length in the May 14, 1993 rule at 58 FR 28686.) EPA requests 
    comment on the regulatory approach and rationale presented here.
    
    C. Equipment Certification
    
        The final rule published on May 14, 1993 requires that refrigerant 
    recycling and recovery equipment manufactured after November 15, 1993, 
    and used to service appliances containing CFCs or HCFCs be tested by an 
    EPA-approved laboratory to ensure that it meets certain performance 
    standards. These standards vary among equipment used to service MVAC-
    like appliances, small appliances, and other appliances. EPA is 
    proposing to require that equipment used to service appliances 
    containing HFCs and PFCs be tested by an EPA-approved laboratory to the 
    same standards as apply to equipment used to service appliances 
    containing class I and class II refrigerants, as applicable. Because 
    EPA is simultaneously proposing to permit the use of representative 
    refrigerants in equipment testing (as opposed to requiring testing with 
    every refrigerant), equipment models already certified for use with 
    CFCs and HCFCs might not always need additional testing in order to be 
    certified for use with HFCs and PFCs. In addition, as discussed below, 
    EPA is proposing to grandfather existing recovery and recycling 
    equipment that is certified for use with at least two CFCs and HCFCs 
    for use with HFCs and PFCs of similar saturation pressure.
    1. Certification of Recovery and Recycling Equipment Intended for Use 
    with Appliances Except Small Appliances, MVACs, and MVAC-like 
    Appliances
        a. Background. For recovery equipment used with appliances other 
    than small appliances, MVACs and MVAC-like appliances, the laboratory 
    must verify that the equipment is capable of achieving applicable 
    required evacuation levels and that the equipment releases no more than 
    3% of the quantity of refrigerant being recycled through 
    noncondensables purging. In addition, the laboratory must measure the 
    vapor and liquid recovery rates of the equipment. To perform all of 
    these measurements, the
    
    [[Page 32074]]
    
    laboratory must use the test procedure set forth in ARI 740-93, an 
    industry test protocol for recycling and recovery equipment that EPA 
    included in the final rule as Appendix B.
        A proposed rule published on February 29, 1996 requested comment on 
    amending the certification requirements to include a new, more 
    representative method for measuring the equipment's refrigerant 
    recovery rate; requirements to measure the equipment's recovery rate 
    and final vacuum at high temperatures; a limit on the total quantity of 
    refrigerant that may be released from equipment from noncondensables 
    purging, oil draining, and equipment clearing; a requirement to measure 
    the quantity of refrigerant left in the condenser of equipment after 
    clearing has occurred; standards for external hose permeability; and a 
    requirement that equipment be tested with recovery cylinders that are 
    representative of those used with the equipment in the field. In 
    addition, EPA proposed to require that equipment that is advertised as 
    ``recycling equipment'' be capable of cleaning up refrigerants to the 
    contamination levels (except that for ``Other Refrigerants'') set forth 
    in the IRG-2 table of Maximum Contaminant Levels of Recycled 
    Refrigerants in Same Owner's Equipment.
        b. Certification of Recovery/recycling Equipment Used With HFCs and 
    PFCs. EPA is today proposing equipment certification requirements for 
    recovery and recycling equipment used with HFCs and PFCs that are very 
    similar to the requirements for recovery and recycling equipment used 
    with CFCs and HCFCs, as they were proposed to be amended in the 
    February 29, 1996 document. The evacuation requirements would depend 
    upon the saturation pressure of the refrigerant, the size of the 
    appliance in which it is used, and the date of manufacture of the 
    recovery equipment. These standards, which are described in Table 1 and 
    Table 2, are consistent with the proposed evacuation requirements 
    discussed in section IV.B.1.a. above.
    
      Table 1.--Levels of Evacuation Which Must Be Achieved by Recovery or  
    Recycling Equipment Intended for Use With Appliances \1\ Manufactured on
                           or after November 15, 1993                       
    ------------------------------------------------------------------------
                                                                 Inches of  
                                                                  vacuum    
                                                               (relative to 
       Type of appliance with which recovery or recycling        standard   
                 machine is intended to be used.                atmospheric 
                                                                pressure of 
                                                              29.9 inches of
                                                                    Hg)     
    ------------------------------------------------------------------------
    Very high-pressure appliance............................               0
    Higher-pressure appliance or isolated component of such                 
     appliance, normally containing less than 200 pounds of                 
     refrigerant............................................               0
    Higher-pressure appliance, or isolated component of such                
     appliance, normally containing 200 pounds or more of                   
     refrigerant............................................              10
    High-pressure appliance, or isolated component of such                  
     appliance, normally containing less than 200 pounds of                 
     refrigerant............................................              10
    High-pressure appliance, or isolated component of such                  
     appliance, normally containing 200 pounds or more of                   
     refrigerant............................................              15
    Low-pressure appliance..................................         \2\ 25 
    ------------------------------------------------------------------------
    \1\ Except for small appliances, MVACs, and MVAC-like appliances.       
    \2\ mm Hg absolute.                                                     
    
        The vacuums specified in inches of Hg vacuum must be achieved 
    relative to an atmospheric pressure of 29.9 inches of Hg absolute.
    
      Table 2.--Levels of Evacuation Which Must Be Achieved by Recovery or  
      Recycling Equipment Intended for Use With Appliances \1\ Manufactured 
                            Before November 15, 1993                        
    ------------------------------------------------------------------------
                                                                 Inches of  
                                                                  vacuum    
                                                               (relative to 
       Type of appliance with which recovery or recycling        standard   
                 machine is intended to be used.                atmospheric 
                                                                pressure of 
                                                              29.9 inches of
                                                                    Hg)     
    ------------------------------------------------------------------------
    Very high-pressure appliance............................               0
    Higher-pressure appliance or isolated component of such                 
     appliance, normally containing less than 200 pounds of                 
     refrigerant............................................               0
    Higher-pressure appliance, or isolated component of such                
     appliance, normally containing 200 pounds or more of                   
     refrigerant............................................               4
    High-pressure appliance, or isolated component of such                  
     appliance, normally containing less than 200 pounds of                 
     refrigerant............................................               4
    High-pressure appliance, or isolated component of such                  
     appliance, normally containing 200 pounds or more of                   
     refrigerant............................................               4
    Low-pressure appliance..................................             225
    ------------------------------------------------------------------------
    \1\ Except for small appliances, MVACs, and MVAC-like appliances.       
    \2\ mm Hg absolute.                                                     
    
        The other certification requirements, including the requirement to 
    use the more representative method for measuring the equipment's 
    refrigerant recovery rate, the requirement for high-temperature 
    testing, and limits on refrigerant emissions from air purging, oil 
    draining, equipment clearing, and hoses, would be identical to those 
    proposed for CFC and HCFC recovery and recycling equipment in the 
    February 29, 1996 document.
        EPA believes that certification of recovery and recycling equipment 
    used with HFCs and PFCs is necessary to implement and enforce both 
    section 608(c)(2) and section 608(a). In order to comply with the 
    prohibition on venting of substitute refrigerants by making good faith 
    efforts to recover them, technicians must recover the refrigerants 
    using equipment that minimizes refrigerant emissions and mixture, and 
    they must complete the recovery process. Certification of HFC and PFC 
    recovery equipment would permit technicians to achieve all of these 
    goals. First, certification would provide reliable information on the 
    ability of equipment to minimize emissions, measuring and/or 
    establishing standards for recovery efficiency (vacuum level) and 
    emissions from air purging, oil draining, equipment clearing, and hose 
    perme
    
    [[Page 32075]]
    
    ation. Second, certification would provide reliable information on the 
    equipment's ability to clear itself when it was switched between 
    refrigerants. Without sufficient clearing capability, equipment may 
    retain residual refrigerant in its condenser, which will be mixed with 
    the next batch of a different refrigerant recovered by the equipment. 
    Because it is frequently impossible to reclaim and expensive to 
    destroy, such mixed refrigerant is much more likely than unmixed 
    refrigerant to be vented to the atmosphere. Third, certification would 
    provide reliable information on the equipment's recovery speed, without 
    which technicians may purchase equipment that recovers too slowly, 
    tempting them to interrupt recovery before it is complete. As discussed 
    in the May 14, 1993, final rule, EPA believes that the information on 
    equipment performance provided by a disinterested third-party testing 
    organization is more reliable than that provided by other sources, such 
    as equipment manufacturers (58 FR 28686-28687).
        Certification of recovery equipment used with HFCs and PFCs would 
    also maximize recycling and minimize emissions of CFCs and HCFCs. As 
    discussed below, there is no physical difference between ozone-
    depleting refrigerants and their fluorocarbon substitutes that would 
    prevent a technician from purchasing and using HFC recovery equipment 
    on CFCs or HCFCs. At the same time, uncertified recovery and recycling 
    equipment is likely to be less expensive than certified equipment, 
    which must meet standards and undergo testing. Thus, if uncertified HFC 
    or PFC equipment is available on the market, technicians may well 
    decide to purchase and use it with CFCs and HCFCs instead of or in 
    addition to HFCs and PFCs. In this way, failure to require 
    certification for recovery equipment used with HFCs and PFCs would 
    undermine the current certification program for equipment used with 
    CFCs and HCFCs, leading to greater emissions of the latter. These 
    emissions could occur through any of the routes identified above; that 
    is, directly from leaky or inefficient equipment, or indirectly through 
    refrigerant mixture or incomplete recovery.
        c. Use of Representative Refrigerants In Equipment Testing. 
    Currently, equipment certification organizations test recovery and 
    recycling equipment with each of the refrigerants for which the 
    equipment is to be rated. Given the proliferation of new refrigerants 
    and the associated cost of testing equipment with each one, EPA is 
    proposing to permit equipment to be tested with only one or two 
    representative refrigerants from each saturation pressure category for 
    which it is to be rated. At least one of the representative 
    refrigerants would be one that was among the most difficult to recover 
    in its category, that is, a refrigerant whose relatively high 
    saturation pressure and/or discharge temperature made attainment of 
    deep vacuums relatively difficult. This would ensure that equipment 
    that could attain the required vacuums with the representative 
    refrigerant could attain these vacuums with all of the other 
    refrigerants in that category. Other factors that could be considered 
    in the selection of representative refrigerants include moisture 
    affinity, which affects the ease with which refrigerants may be 
    cleaned, materials compatibility, likely popularity, and availability 
    for testing purposes. Different refrigerants might be selected for 
    different testing purposes; for instance, a refrigerant with a high 
    saturation pressure might be selected to test a piece of equipment's 
    ability to draw a vacuum, while a refrigerant with a high moisture 
    affinity might be selected to test the equipment's ability to remove 
    contaminants.
        The Agency believes that the saturation pressure (and to some 
    extent, discharge temperature and moisture affinity) of the refrigerant 
    are more important factors in recovery equipment performance than the 
    chemical identity of the refrigerant; in general, equipment that passes 
    the certification test for CFCs and HCFCs is likely to pass the test 
    for HFCs and PFCs of similar (or lower) saturation pressure, as long as 
    the materials used in the recovery equipment are compatible with all of 
    these refrigerants. The equipment certification programs operated by 
    both UL and ARI have been testing recovery and recycling equipment with 
    HFC-134a for the past few years, and equipment performance (final 
    vacuum) with HFC-134a appears to be comparable to that with R-12. EPA 
    requests comment on whether there are factors other than saturation 
    pressure, discharge temperature, moisture affinity, materials 
    compatibility, popularity, and availability that should be considered 
    in selecting a representative refrigerant or in determining the set of 
    refrigerants for which equipment should be certified.
        The latest version of ARI 740, ARI 740-1995, already includes a 
    test that is performed with one representative refrigerant. That is 
    high-temperature testing, which is performed with R-22. As discussed in 
    the proposed rule to adopt ARI 740-1995, R-22 was selected because it 
    has a relatively high saturation pressure and discharge temperature, 
    making it harder to recover than many other high-pressure refrigerants 
    (61 FR 7867). Although EPA is proposing to place R22 in a separate 
    saturation pressure category from R134a and R12, EPA believes that it 
    may be appropriate to retain R22 as a representative refrigerant for 
    both pressure categories. EPA requests comment on this issue. EPA also 
    requests comment on whether recovery equipment that is to be certified 
    for use with refrigerants whose saturation pressures are higher than 
    that of R22 should have high-temperature testing performed with R22, or 
    with a higher-pressure refrigerant. Because many new refrigerants have 
    significantly higher saturation pressures than R22 (for instance, R407B 
    has a saturation pressure of 281.7 psia at 104 degrees F, while R22 has 
    a saturation pressure of 222.4 psia at that temperature), EPA believes 
    that equipment that is rated for use with these refrigerants should 
    have high-temperature testing performed with a refrigerant whose 
    saturation pressure is closer to theirs.
        In its efforts to revise and update the ARI 740 standard, ARI is 
    currently considering an approach that divides refrigerants into six 
    saturation pressure categories and selects one or two refrigerants for 
    each one. The planned ARI groupings and representative refrigerants for 
    each one are reprinted in Table 3 below.
    
                                                         Table 3.--Proposed ARI Grouping of Refrigerants                                                    
    --------------------------------------------------------------------------------------------------------------------------------------------------------
                                                                                                              PSIA at 104                                   
           Designated group refrigerant                Group No.                   Refrigerant No.           deg.F, liquid    Bubble point,      Critical   
                                                                                                                                  deg.F        temp.,  deg.F
    --------------------------------------------------------------------------------------------------------------------------------------------------------
    R-123....................................  I                                                                                                            
    (3)LOW PRESSURE                                                                                                                                         
                                                                                                                                                            
    R-11.....................................  .........................  R-113                                        18              117.6           417.4
                                               .........................  R-123                                        22.4             82.1           362.6
    
    [[Page 32076]]
    
                                                                                                                                                            
                                               .........................  R-11                                         25.3             74.9           388.4
    R-114....................................  II                                                                                                           
    (3)MEDIUM PRESSURE--LOW MOISTURE                                                                                                                        
                                                                                                                                                            
                                               .........................  R-114                                        48.6             38.8           294.3
    R-134a...................................  III                                                                                                          
    (3)MEDIUM PRESSURE                                                                                                                                      
                                                                                                                                                            
                                               .........................  R-12                                        139.7            -21.6           233.2
                                               .........................  R-134a                                      147.4            -14.9           213.9
                                               .........................  R-401C                                      151.9            -19.0           234.9
                                               .........................  R-406A                                      161.4            -26.2           238.1
                                               .........................  R-500                                       163.7            -28.3           221.9
    R-407C...................................  IV                                                                                                           
    (3)MEDIUM HIGH PRESSURE                                                                                                                                 
                                                                                                                                                            
    R-22.....................................  .........................  R-401A                                      174.9            -27.5           226.4
                                               .........................  R-409A                                      178.6            -29.6           224.6
                                               .........................  R-401B                                      183.5            -30.4           223.0
                                               .........................  R-412A                                      191.8            -37.3           220.6
                                               .........................  R-411A                                      210.8            -37.5           209.5
                                               .........................  R-407D                                      217.8            -39.1           216.3
                                               .........................  R-22                                        222.4            -41.4           205.1
                                               .........................  R-411B                                      225.5            -42.9           205.7
                                               .........................  R-502                                       244.8            -49.7           180.0
                                               .........................  R-407C                                      254.5            -46.4           189.1
                                               .........................  R-402B                                      255              -53.2           180.7
                                               .........................  R-408A                                      255              -46.3           182.3
                                               .........................  R-509                                       256.5            -52.8           188.3
    R-410A...................................  V                                                                                                            
    (3)HIGH PRESSURE                                                                                                                                        
                                                                                                                                                            
                                               .........................  R-407A                                      267.6            -49.9           181.0
                                               .........................  R-404A                                      269.9            -51.6           161.7
                                               .........................  R-402A                                      270.6            -46.5           167.9
                                               .........................  R-507                                       275.5            -52.1           159.6
                                               .........................  R-407B                                      281.7            -53.1           168.4
                                               .........................  R-410A                                      352.8            -62.9           162.5
    R-508A...................................  VI                                                                                                           
    (3)VERY HIGH PRESSURE--HIGH MOISTURE                                                                                                                    
                                                                                                                                                            
                                               .........................  R-13                              supercritical             -114.5            83.8
                                               .........................  R-23                              supercritical             -115.8            78.1
                                               .........................  R-508A                            supercritical             -122.2            73.5
                                               .........................  R-503                             supercritical             -126.0            67.1
                                               .........................  R-508B                            supercritical             -126.9            57.2
    --------------------------------------------------------------------------------------------------------------------------------------------------------
    
        ARI's saturation pressure categories are similar, but not 
    identical, to the saturation pressure categories that EPA is proposing 
    to use as the basis for its evacuation requirements. For instance, both 
    EPA and ARI propose to classify R113, R123, and R11 as low-pressure 
    refrigerants, and R13, R23, R508A, R503, and R508B as very-high 
    pressure refrigerants. However, while EPA is proposing to classify 
    R114, R134a, and R401A as high-pressure refrigerants, ARI is proposing 
    to place these refrigerants into three separate saturation pressure 
    categories. Moreover, EPA's proposed dividing line between high and 
    higher-pressure refrigerants would split ARI's ``medium high-pressure'' 
    category in half, falling between R407D and R22.
        EPA does not believe that using different saturation pressure 
    categories for selecting representative refrigerants and for 
    determining evacuation requirements would be a problem if the 
    categories for selecting representative refrigerants fell entirely 
    within the categories for determining evacuation requirements. Thus, 
    EPA believes it would be quite reasonable to separate EPA's high-
    pressure category into three categories for purposes of selecting 
    representative refrigerants; this would simply mean that recovery and 
    recycling equipment would be tested with more refrigerants. However, if 
    a category for selecting representative refrigerants were split into 
    different categories for determining evacuation requirements, confusion 
    and inefficiency could result. For instance, ARI is considering R22 and 
    R407C as representative refrigerants for its ``medium high-pressure'' 
    category. If EPA were to promulgate the categories for evacuation 
    requirements proposed today, recovery/recycling equipment that was 
    being certified for use with any refrigerant in the ``medium high-
    pressure'' category would have to pull these refrigerants to the 
    relatively deep vacuums required for R12 and R134a, because EPA is 
    proposing to place these refrigerants in the same evacuation category 
    as many of the refrigerants in ARI's ``medium high-pressure category.'' 
    This may be an unnecessarily strict approach, as R22 itself would not 
    need to be drawn to these vacuums in the field. EPA requests comment on 
    this issue.
        Because the current regulations establish less stringent evacuation 
    requirements for R22 appliances than for appliances containing 
    refrigerants with lower saturation pressures, and because EPA wishes to 
    retain as much consistency as possible between the proposed and the 
    existing evacuation requirements, EPA is reluctant to eliminate or move 
    its dividing line between the proposed high-pressure and higher 
    pressure evacuation requirement categories. (Again, the proposed 
    dividing line falls between R407D and R22.) In consideration of this 
    issue and the issues discussed above, the Agency requests comment on 
    whether it should adopt the proposed ARI groupings as is or with some 
    changes. If the latter, the Agency requests comment on what changes 
    would be appropriate.
        ARI selected the proposed representative refrigerants considering
    
    [[Page 32077]]
    
    the saturation pressure, discharge temperature, moisture affinity, 
    materials compatibility, and likely popularity of the refrigerants. ARI 
    is considering using both R11 and R123 as representative refrigerants 
    for the low-pressure category because some equipment uses materials 
    that are compatible with R11 but not with R123, and a requirement for 
    performance testing with R123 may reduce the incidence of equipment 
    failure and refrigerant leakage in the field. ARI is considering a 
    separate grouping for R114 because this refrigerant has a saturation 
    pressure that is significantly higher than lower-pressure refrigerants 
    and significantly lower than higher pressure refrigerants. Although 
    R134a is not the refrigerant with the highest saturation pressure in 
    the next, ``medium pressure'' category, ARI is considering it as the 
    representative refrigerant because it is likely to be used widely and 
    the refrigerants with higher saturation pressures (R401C, R406A, R500) 
    are not. R134a also has a relatively high moisture affinity.
        ARI is considering using both R22 and R407C as representative 
    refrigerants in the ``medium high-pressure'' category because of their 
    popularity, the high discharge temperature of R22, and the high 
    saturation pressure of R407C at 104 F. (R407C has a saturation pressure 
    of 254.5 psia at that temperature, while the highest pressure 
    refrigerant in the category, R509, has a saturation pressure only 2 psi 
    higher, 256.5) R410A is being considered as the representative 
    refrigerant for the next category because its saturation pressure of 
    3.8 psia is the highest in its category, and because it has a high 
    moisture affinity. ARI's tentative choice as the representative 
    refrigerant for the very high pressure category is R508A, which is 
    supercritical at 104 degrees F. R508A's critical temperature of 73.5 is 
    16 degrees higher than that of the highest-pressure refrigerant in the 
    group, R508B, but 10 degrees lower than that of the lowest-pressure 
    refrigerant in the group, R13.
        EPA believes that ARI's tentative choices for representative 
    refrigerants would probably appropriately represent their categories, 
    as those categories are currently defined. However, EPA is requesting 
    comment on a few issues. First, EPA requests comment on whether R134a 
    is an appropriate representative refrigerant for the ``medium 
    pressure'' group, given that its saturation pressure is 16 psi lower 
    than the saturation pressure of the highest-pressure refrigerant in the 
    category, R500. Should the likely popularity of R134a relative to 
    R401C, R406A, and R500 overrule its relatively low saturation pressure? 
    Is equipment that successfully recovers R134a in testing likely to fail 
    to recover refrigerant with a saturation pressure 16 psi higher? EPA 
    requests comment on the same issue as it applies to the use of R508A as 
    the representative refrigerant for ``very high pressure'' refrigerants. 
    Finally, EPA requests comment on what refrigerant should be chosen to 
    represent the category of refrigerants whose saturation pressures fall 
    between those of R401A and R407D, in case this category is split off 
    from the current ``medium high pressure'' category, and what 
    refrigerant should be chosen to represent ``high pressure 
    refrigerants,'' in case R410A is split off from this category. EPA 
    believes that R407D and B, which would become the highest pressure 
    refrigerants in these categories, would be appropriate choices, but 
    recognizes that considerations of moisture affinity and/or refrigerant 
    availability may argue for choices with slightly lower saturation 
    pressures.
        While the proper selection of representative refrigerants would 
    ensure that recovery equipment could achieve the required vacuum for 
    all the refrigerants in a category, some information would be lost. 
    Specifically, the vapor and liquid recovery rates of equipment with 
    each of the refrigerants in a category would no longer be available. 
    However, technicians and contractors would still be able to compare 
    recovery rates across different makes and models for the representative 
    refrigerant. EPA requests comment on whether the information gained 
    through measuring recovery rates for each refrigerant justifies 
    retaining testing with each refrigerant.
        EPA would include representative refrigerants in the equipment 
    testing program by amending Appendix B, the test protocol based on ARI 
    740-1993. If EPA completes the rulemaking adopting the latest version 
    of ARI 740, ARI 740-1995, before this rule is finalized, EPA would 
    amend that protocol rather than the protocol based on ARI 740-1993. 
    Since the use of representative refrigerants amounts to a relaxation of 
    testing requirements, EPA does not anticipate any problems from 
    adopting this approach only shortly after adopting an earlier set of 
    amendments to the testing requirements.
        d. Additional Refrigerants. Industry experts have suggested that a 
    few additional refrigerants could be usefully added to Table 3. These 
    include R124, R125, R403A, R405A, R409B, R410B, and R413B. R124, R125, 
    and R410B are ASHRAE-recognized refrigerants that are included in ARI 
    Standard 700. In addition, R124 and R410B have been determined to be 
    ``acceptable'' for several end-uses under the SNAP program, and R125 is 
    a component of several refrigerant blends that have been determined to 
    be ``acceptable.'' Thus, it appears appropriate to include these in the 
    equipment certification program. Although R403A and R413A have not been 
    submitted for review under SNAP and are not used in the U.S., they are 
    in use overseas. Industry experts believe that certification for these 
    refrigerants could benefit manufacturers who intend to export 
    refrigerant recovery/recycling equipment to Europe and elsewhere. EPA 
    believes that the same logic may apply to R405A, although it has been 
    found to be ``unacceptable'' in the U.S. under SNAP due to its high PFC 
    content. R409B does not yet appear in ARI Standard 700, but R409A, 
    whose composition differs from that of R409B by less than five percent, 
    does. Thus, it also seems reasonable to accommodate this fluid in the 
    equipment certification program. EPA requests comment on these possible 
    additions to the equipment certification program.
    
                                    Refrigerants Recommended for Addition to Table 3                                
    ----------------------------------------------------------------------------------------------------------------
                                                                                               Bubble      Critical 
                       Refrigerant                            Group No.          PSIA at       point,       point,  
                                                                                104  deg.F     deg.F        deg.F   
    ----------------------------------------------------------------------------------------------------------------
    R-124............................................  II                             86.0         10.3        252.4
    R-413A...........................................  III                           167.2        -31.0        198.5
    R-405A...........................................  IV                            177.3        -25.2        223.0
    R-409B...........................................  IV                            186.6        -31.4        221.0
    R-403A...........................................  IV                            244.5        -58.0        199.9
    R-125............................................  V                             290.9        -54.7        151.3
    R-410B...........................................  V                             350.3        -60.3        159.9
    ----------------------------------------------------------------------------------------------------------------
    
    
    [[Page 32078]]
    
        EPA is also requesting comment on how R124 would be integrated into 
    Table 3. The working pressure of R-124 differs sufficiently from R-114 
    that some equipment may not operate correctly with both fluids. For 
    this reason, industry experts recommend that R124 be listed as an 
    additional refrigerant for group II, subject to the following 
    guidelines:
        (a) Equipment that is certified for use in group I may also be 
    certified for group II by testing with R-124. The test for R-114 may be 
    waived as the equipment would be shown to operate correctly for both 
    higher and lower pressure fluids.
        (b) Equipment that is certified for use in group III may also be 
    certified for group II by testing with R-114. The test for R-124 may be 
    waived as the equipment would be shown to operate correctly for both 
    higher and lower pressure fluids.
        (c) Equipment that is not certified in either group I or group III 
    must be tested using both R-114 and R-124 in order to obtain 
    certification for group II.
        (d) Equipment that is not certified in either group I or group III 
    may be certified for a single refrigerant from group II through 
    successful testing with the appropriate refrigerant. EPA requests 
    comment on this approach.
        e. Materials Compatibility. Although EPA's preliminary information 
    indicates that recovery and recycling equipment designed for use with 
    CFCs and HCFCs can be used with HFCs and PFCs, some industry experts 
    have raised concerns that lubricants, elastomers, filter driers, and/or 
    motor materials used in recovery and recycling equipment may not be 
    compatible with the full range of halocarbon (CFC, HCFC, HFC, and PFC) 
    refrigerants coming into use. Use of incompatible lubricants may lead 
    to compressor wear and ultimately to compressor failure; use of 
    incompatible filter driers may lead to declining performance in 
    refrigerant blends; use of incompatible elastomers may lead to the 
    failure of seals and subsequently to refrigerant leakage from the 
    equipment; and use of incompatible motor materials may lead to motor 
    failure.
        Some industry representatives expressed the concern that many 
    models of recycling and recovery equipment have been built and sold 
    with mineral oil, which is not compatible with HFCs. EPA believes that 
    this concern may be addressed by informing equipment manufacturers and 
    users of the need to replace the mineral oil with ester oil if the 
    equipment is used with HFCs, and possibly by requiring equipment 
    manufacturers to use ester lubricants in equipment certified for use 
    with HFCs. EPA understands that ester lubricants work well with all 
    halocarbon refrigerants, and that changing out the oil in recycling and 
    recovery equipment is usually a simple and routine procedure. HCFCs, 
    which dissolve easily into ester oil, may thin it out, necessitating 
    the use of higher viscosity oils, but recycling and recovery equipment 
    manufacturers may address this problem simply by using (or specifying 
    use of) a higher viscosity lubricant. EPA requests comment on whether 
    sufficient mechanisms exist within the industry to ensure that the need 
    and method for changing out lubricants is transmitted to manufacturers 
    and users of recycling and recovery equipment, and whether EPA should 
    require that equipment certified for use with HFCs be sold with ester 
    lubricants.
        In addition, industry sources expressed the concern that filter 
    driers, particularly those containing activated carbon, may react 
    undesirably to certain refrigerant blends. Undesirable reactions might 
    include the selective uptake of refrigerant components, changing the 
    composition of the blend, or extreme heating when a filter drier 
    containing activated carbon is used with blends containing hydrocarbon 
    refrigerants. EPA understands that some types of filter driers absorb 
    some blend components more than others, but that this absorption is 
    usually not sufficiently pronounced to significantly change the 
    performance of the blend. EPA further understands that some heating is 
    inevitable when activated carbon is used, but that this heating may not 
    be very great, and that it is counteracted by the refrigerant's 
    tendency to carry heat away from the drier. EPA requests comment on 
    these issues. If some types of filter driers are incompatible with some 
    types of blends, EPA requests comment on whether the Agency should 
    require the use of other types of filter driers that are compatible 
    with all refrigerants, or whether the Agency should require equipment 
    manufacturers to demonstrate, through testing, that the filter driers 
    used in their equipment are compatible with all of the refrigerants for 
    which the equipment is to be certified.
        Industry experts also expressed the concern that compressor and 
    motor materials may not be compatible with new refrigerant and 
    lubricant combinations. EPA understands that most recycling and 
    recovery compressors and motors that are intended for use with high-
    pressure refrigerants are designed to work with R502 and mineral oil. 
    Because the combination of R22 (a component of R502) and mineral oil is 
    a relatively aggressive one (i.e., is likely to chemically attack 
    compressor components), EPA believes that compressors and motors that 
    are designed to handle this combination are likely to tolerate other 
    refrigerant/lubricant combinations, such as HFCs and ester oils. 
    However, EPA requests comment on this issue. EPA also requests comment 
    on whether compressors and motors that are designed to handle 
    refrigerant/lubricant combinations other than R502 and mineral oil 
    (e.g., R11 and mineral oil) may pose compatibility concerns.
        Finally, some industry sources stated that the elastomers used in 
    O-rings and other types of seals may not be compatible with all types 
    of refrigerants and lubricants. Some of the potential effects of 
    incompatibility include the swelling of O-rings, which would make it 
    difficult to make and break connections without leakage, and the high-
    temperature hardening or ``compression set'' of shaft seals on open-
    drive compressors, which would lead to failure of the seal. EPA 
    understands that no single material is likely to work equally well with 
    all combinations of refrigerants and lubricants, and that similar 
    materials (e.g., two types of neoprene) may not be equally compatible 
    with the same refrigerant/lubricant combinations. Thus, rather than 
    specifying the use of any single material or set of materials, the 
    Agency is considering requiring manufacturers of recovery and recycling 
    equipment to use materials that have been shown to be compatible with 
    the refrigerants for which the equipment is to be rated or certified. 
    The method for demonstrating compatibility might be sealed tube testing 
    under the conditions of ASHRAE 97 or some other standard; manufacturers 
    could use the results of industry-wide testing (e.g., MCLR/ARTI 
    testing) if such testing had been performed for the materials, 
    refrigerants, and lubricants of concern. Another possible means of 
    addressing compatibility concerns would be to require manufacturers to 
    test recovery and recycling equipment with all the major refrigerant 
    groups (CFCs, HCFCs, and HFCs and their associated lubricants); but the 
    duration of equipment testing may not be sufficient to reveal 
    compatibility problems, raising the question of whether the additional 
    testing would be useful or justified. EPA requests comment on the 
    elastomer compatibility issue and on the above approaches for 
    addressing it.
        f. Fractionation. For a number of reasons, some industry experts 
    have expressed concern that recycling and
    
    [[Page 32079]]
    
    recovery equipment, and to some extent, the process of recovery itself, 
    may change the composition of refrigerant blends, affecting their 
    performance. Ways in which recycling and recovery equipment might 
    conceivably change the composition of blends include the selective 
    absorption of certain components by filter driers (discussed above), 
    selective removal of components with higher solubility in oil through 
    oil separation, selective release of certain components during 
    noncondensables purging, and possibly selective diffusion of certain 
    components (those with lower molecular weights) through hoses.
        EPA is aware of two studies that have been performed to ascertain 
    how recovery and recycling may affect the composition of blends \24\. 
    One study, performed by ICI Klea, modeled blend behavior during 
    recovery and recycling based on the thermophysical properties of the 
    refrigerants. The other study, performed by Robinair, examined how 
    blend composition changed during and after repeated recycling using 
    actual recycling equipment. Both studies showed recycling had little 
    impact on blend composition, if the complete charge was removed from 
    the system and recharged back into it at the conclusion of service. 
    However, because different models of recovery and recycling equipment 
    may have different impacts on blend composition, and because few models 
    were actually tested in the studies, EPA is requesting comment on 
    whether the certification program for recycling and recovery equipment 
    should be expanded to test equipment's tendency to change blend 
    composition.
    ---------------------------------------------------------------------------
    
        \24\ Kenneth W. Manz, Robinair Division, SPX Corporation, 
    ``Recycling Alternate Refrigerants R-404a, R-410a, and R507,'' and 
    R.W. Yost, ICI Klea, ``Practical Aspects of Zeotrope Fractionation 
    in Recovery and Recycling,'' both presented at the 1996 ASHRAE 
    Winter Meeting, Atlanta, Georgia, February 19, 1996. Copies of the 
    presentations are available for inspection in the public docket for 
    this rulemaking. A yet-to-be-published study performed by EPA's 
    Office of Research and Development yielded similar results.
    ---------------------------------------------------------------------------
    
        g. Flammability. Some refrigerants that have entered the market 
    over the past few years, such as R406A, may be flammable under some 
    conditions (e.g., after fractionation). EPA requests comment on whether 
    the equipment certification program should test whether equipment that 
    is to be certified for ``flammable'' refrigerants may be used with them 
    safely, and if so, how ``flammable'' refrigerants should be defined for 
    purposes of equipment testing. ARI is currently considering certifying 
    equipment for use with refrigerants classified under ASHRAE Standard 34 
    as ``lower flammability'' (Class 2); no ``higher flammability'' (Class 
    3) refrigerants are included in Table 3. EPA requests comment on 
    whether the recovery and recycling process could lead to refrigerant 
    ignition for the Class 2 refrigerants in Table 3. Could these 
    refrigerants (or a subset of them) be ignited by high motor 
    temperatures or by sparking of switches or other equipment components 
    during recovery and recycling? If so, what kinds of tests would be 
    appropriate to determine whether a model of recovery and recycling 
    equipment could be used with these refrigerants safely? Should the 
    ASHRAE 34 classification system be used for purposes of determining 
    flammability for recovery and recycling equipment certification, or 
    would some other system (e.g., one based on auto-ignition temperature) 
    be more appropriate?
        If equipment's ability to safely process flammable refrigerants 
    should be tested, EPA requests comment on how representative 
    ``flammable'' refrigerants might be chosen. One possible approach would 
    be to establish a separate category for ``flammable'' refrigerants in 
    Table 3, and to test the most flammable among them (using whatever 
    criterion for flammability is ultimately chosen) with the recovery and 
    recycling equipment.
    2. Certification of Recovery and Recycling Equipment Intended for Use 
    With Small Appliances
        Recovery equipment intended for use with small appliances 
    containing CFCs or HCFCs must currently be tested by an EPA-approved 
    testing organization to verify that it meets at least one of two sets 
    of standards. The equipment must either (1) recover 90% of the 
    refrigerant in the small appliance when the compressor is operating and 
    80% of the refrigerant in the small appliance when the compressor is 
    not operating, when tested according to Appendix C, or (2) be able to 
    pull a four-inch vacuum when tested according to Appendix B. Equipment 
    manufactured before November 15, 1993, is grandfathered if it can 
    recover at least 80% of the refrigerant in the small appliance whether 
    or not the compressor is operating. EPA is proposing to extend these 
    requirements to recovery equipment that is intended for use with small 
    appliances containing HFCs or PFCs.
        Appendix C currently requires that recovery equipment be tested 
    using CFC-12. EPA requests comment on whether appendix C should be 
    amended to require testing with substitute refrigerants in addition to 
    or in place of CFC-12. The substitute refrigerant(s) chosen would be 
    one used in small appliances. As discussed above, EPA is proposing to 
    amend Appendix B to permit testing of equipment with a single 
    representative refrigerant from each saturation pressure and moisture 
    affinity category, and a similar approach may be appropriate for 
    Appendix C.
        One factor in addition to saturation pressure that has an impact on 
    recovery efficiencies from small appliances is the miscibility of the 
    refrigerant in the system lubricant. This is especially important in 
    small appliances because there is often as much lubricant in a small 
    appliance as there is refrigerant, and a large percentage of the 
    refrigerant may therefore remain entrained in the lubricant even if the 
    system pressure is relatively low. EPA requests comment on whether its 
    certification requirements for recovery equipment used with small 
    appliances should be amended to account for differences in the 
    miscibilities of CFC-12 and the HFCs in their associated lubricants.
    3. Approval of Equipment Testing Organizations To Test Recovery 
    Equipment With HFC and PFC Refrigerants
        EPA has approved two equipment testing organizations, the Air 
    Conditioning and Refrigeration Institute and Underwriters Laboratories, 
    to certify equipment under the current standards at Sec. 82.158(b) and 
    Appendix B. EPA anticipates that both organizations will apply to 
    certify equipment under the standards based on ARI 740-95 when these 
    are promulgated in the near future. EPA is proposing to require that 
    approved equipment testing organizations would also have to apply to 
    EPA to become approved to certify equipment under the standards 
    described above, once these are promulgated. However, these 
    organizations would not need to resubmit the information on their test 
    facilities, equipment testing expertise, long-term performance 
    verification programs, knowledge of the standards, and objectivity that 
    they submitted to become approved to certify under Sec. 82.158(b) and 
    Appendix B, or under the new standards based on ARI 740-95. Instead, 
    they would have to submit information only in those areas where their 
    certification programs under the standards described above differed 
    from their previously approved programs. Because the standards 
    described above do not require any testing equipment that differs from 
    that required for the standards based on ARI 740-95, EPA expects 
    submissions to focus on the organizations' knowledge of how the new 
    standards differ from the old. EPA
    
    [[Page 32080]]
    
    believes that a one- to two-page letter would suffice.
    4. Use of Existing CFC/HCFC Recovery Equipment With HFC and PFC 
    Refrigerants
        EPA is proposing to permit technicians to use equipment that is 
    certified for use with at least two CFCs and HCFCs to recover HFCs and 
    PFCs of similar saturation pressure. Based on discussions with 
    equipment manufacturers and testing organizations, EPA believes that 
    most recovery and recycling equipment designed for use with multiple 
    CFC or HCFC refrigerants (e.g., R12, R22, R500, and R502) can be 
    adapted for use with HFC and PFC refrigerants with similar saturation 
    pressures, usually by changing the lubricant to POE lubricant. This 
    equipment would have to meet the standards presented in Table 1 and 
    Table 2. In addition, if it was manufactured on or after November 15, 
    1993, it would have to have been certified by an EPA-approved third-
    party certification program (ARI or UL) for at least two refrigerants 
    with saturation pressures similar to the saturation pressure of the 
    refrigerant(s) with which the equipment is to be used. EPA requests 
    comment on this proposal. EPA specifically requests comment on whether 
    and how the Agency should integrate into its grandfathering policy the 
    considerations enumerated above in the discussion of certification of 
    new equipment, including materials compatibility, flammability, and 
    blend fractionation. EPA also requests comment on whether it should 
    permit equipment that was originally designed for use with a single 
    refrigerant to be used with multiple refrigerants. EPA is concerned 
    that equipment designed for use with a single refrigerant may not be 
    equipped with a clearing mechanism to prevent cross-contamination when 
    it is used with a different refrigerant.
    
    D. Technician Certification
    
        Any person doing work that ``could reasonably be expected'' to 
    release refrigerant from CFC and HCFC appliances is required to become 
    certified. In addition, sales of CFCs and HCFCs are restricted to 
    certified technicians. Technicians become certified by passing a test 
    drawn from a question bank developed jointly by EPA and industry 
    educational organizations. The test includes questions on the role of 
    CFCs and HCFCs in ozone depletion, the requirements of the refrigerant 
    recycling rule, and proper techniques for recycling and conserving 
    refrigerant. EPA makes the question bank available to certifying 
    organizations that demonstrate that they can properly generate, track, 
    and grade tests, issue certificates, and keep records.
        EPA is proposing to extend the certification requirements for 
    technicians who work with CFC and HCFC refrigerants to technicians who 
    work with HFCs and PFCs. Technicians who have been certified to work 
    with CFCs and HCFCs would not have to be retested to work with HFCs or 
    PFCs, but new technicians entering the field would have to pass the 
    test to work with CFCs, HCFCs, HFCs, and/or PFCs.
        EPA believes that requiring certification of technicians who work 
    with HFCs and PFCs is necessary to implement and enforce both section 
    608(c) and section 608(a)(2) effectively. As discussed above, section 
    608(c) prohibits the knowing release of substitute refrigerants during 
    the service, maintenance, repair or disposal of appliances, except for 
    de minimis releases associated with ``good faith attempts to recapture 
    and recycle or safely dispose'' of the refrigerants. It is reasonable 
    to interpret ``good faith attempts to recapture and recycle or safely 
    dispose'' as requiring that service, maintenance, repair, or disposal 
    that could release substitute refrigerant be performed by a certified 
    technician. This interpretation is also consistent with EPA's 
    interpretation of the same statutory language as it applies to ozone-
    depleting refrigerants. For the reasons discussed below, persons who 
    are not certified technicians are far more likely to intentionally or 
    inadvertently release refrigerant contrary to the venting prohibition. 
    In addition, consistent application of technician certification 
    requirements and a sales restriction to class I and II refrigerants and 
    their substitutes is necessary to implement the section 608(a) 
    directive to reduce releases and maximize recapture and recycling of 
    class I and II refrigerants. Technician certification requirements for 
    work with substitute refrigerants would directly reduce some releases 
    of class I and II refrigerants. It would also protect against 
    refrigerant mixture, which otherwise is likely to cause more 
    substantial releases of class I and II refrigerants.
        EPA believes that having a certified technician perform the work on 
    an appliance is an important component of good faith recapture and 
    recycling. Certified technicians are much more likely to understand how 
    and why to recover and recycle refrigerants and to have the means to do 
    so. First, technician certification ensures that technicians are 
    trained in refrigerant recovery requirements and techniques. Until 
    recently, technicians in many sectors were not recycling refrigerants 
    at all, and technicians who did recycle were not necessarily minimizing 
    emissions as much as possible. Thus, many technicians lacked expertise 
    that they would need to comply with the recycling and recovery 
    provisions and hence needed training to acquire that expertise. 
    However, while some vocational schools and training programs addressed 
    refrigerant recovery, participation in such programs was low. Given 
    this situation, EPA was concerned that without a testing or training 
    requirement, recovery and recycling often would not occur at all or 
    would occur improperly, leading not only to refrigerant release, but to 
    refrigerant contamination, safety concerns, productivity losses, and 
    equipment damage. EPA discussed at length the benefits of training and 
    certification in the final rule published on May 14, 1993 (58 FR 28691-
    28694) and in the Regulatory Impact Analysis performed for that rule 
    (6-34 through 6-39). The importance of a certification requirement was 
    confirmed when participation in training programs rose in response to 
    reports that certification would be required, and then fell sharply in 
    response to reports that it would not be required. This indicated that 
    service practice requirements were not, by themselves, likely to drive 
    technicians to acquire training in how to comply with such 
    requirements.
        Second, in addition to possessing training in refrigerant recovery, 
    certified individuals are more likely than uncertified individuals to 
    have access to recovery equipment. This is because uncertified 
    individuals, particularly those who work only on their own appliances 
    (e.g., on their own car air conditioners), are unlikely to find it 
    cost-effective to purchase their own recovery equipment. Thus, they are 
    able neither to recover the refrigerant from the appliance before it is 
    serviced nor to recover the ``heel'' of residual refrigerant from the 
    refrigerant container before it is disposed of. Both the refrigerant in 
    the appliance and that in the refrigerant container are therefore 
    released. (The ``heel'' is ultimately released to the atmosphere when 
    the container is crushed or corroded.)
        EPA anticipates that for the next decade, the majority of 
    technicians subject to section 608 requirements will continue to work 
    with and purchase CFCs and HCFCs and will therefore be certified under 
    the current program.25
    
    [[Page 32081]]
    
    However, EPA is concerned that a significant minority could emerge that 
    would work primarily with HFCs, particularly if a lack of certification 
    requirements for work with substitutes created an incentive for doing 
    so. In this case, large numbers of technicians who worked with HFCs 
    might not receive proper training in refrigerant recycling or recovery, 
    leading to release of HFCs. For example, an uncertified person could 
    vent refrigerant before repairing an appliance containing an HFC 
    refrigerant, thereby violating the venting prohibition. Thus, requiring 
    certification for technicians who work with substitute refrigerants is 
    necessary to implement the section 608(c) prohibition.
    ---------------------------------------------------------------------------
    
        \25\ EPA does not anticipate that many homeowners or other 
    consumers would elect to perform their own repairs on household 
    refrigerators and air conditioners. However, based on the past ``Do-
    It-Yourself'' (DIY) market for MVAC refrigerant, EPA expects that 
    many car owners would elect to perform their own repairs on MVACs, 
    if they could obtain refrigerant to do so. Thus, as discussed below, 
    any sales restriction on HFCs would affect both uncertified 608 
    technicians and the MVACs DIY population.
    ---------------------------------------------------------------------------
    
        Requiring certification for technicians who work with substitute 
    refrigerants is also necessary to comply with the section 608(a) 
    requirements for EPA to promulgate regulations that reduce emissions of 
    class I and II refrigerants to the lowest achievable levels and 
    maximize recapture and recycling of such substances. Failure to require 
    technician certification is likely to lead to increased emissions and 
    reduced recycling of ozone-depleting substances under several 
    scenarios. As discussed above, the lack of a technician certification 
    requirement would encourage the emergence of a class of uncertified 
    technicians working primarily with HFCs. However, once such persons 
    were working as professional refrigeration and cooling technicians, 
    there would be strong economic incentives for them to overlook the 
    restrictions on their ability to work with ozone-depleting refrigerants 
    as well. In fact, because of the absence of a certification requirement 
    and their consequent lack of adequate training, they might be unaware 
    of the existence or scope of the restrictions. Thus, they might fail to 
    recycle class I and class II refrigerants properly, and might not 
    recycle them at all. Uncertified technicians would also be likely to 
    perform retrofits using HFCs, which they would be legally entitled to 
    purchase. However, the appliance that they would be retrofitting would 
    contain ozone-depleting substances. Such uncertified technicians would 
    be likely to vent the ozone-depleting substance prior to retrofitting, 
    given their probable lack of training and the fact that return of the 
    substance to a reclaimer would reveal that they were handling it 
    illegally.
        Failure to require technician certification to work with HFCs is 
    also likely to encourage the inappropriate mixture of HFC and ozone-
    depleting refrigerants. In this scenario, refrigerant mixture could 
    occur because uncertified technicians might wish to service CFC or HCFC 
    equipment, but would have access only to HFCs because sales of CFCs and 
    HCFCs are limited to certified technicians. Lacking training, these 
    technicians would probably have a poor understanding of the 
    consequences of mixing refrigerants, and would therefore be more likely 
    than certified technicians to add HFCs to CFC or HCFC systems.
        The consequences of such inappropriate mixture include significant 
    losses in performance and energy efficiency in equipment serviced with 
    mixed refrigerants, damage to equipment, the lost value of the mixed 
    refrigerant (which is at best difficult, and often impossible, to 
    separate), and costs for destroying mixed refrigerants. Refrigerant 
    mixture also leads both directly and indirectly to refrigerant release. 
    Mixture leads directly to release because mixtures of certain 
    refrigerants, such as R12 and R134a, have higher pressures than either 
    component alone. Thus, pressure-sensitive components such as air purge 
    devices on recycling machines and relief devices on appliances may be 
    activated by these mixtures, venting the refrigerant to the atmosphere. 
    Purge devices in particular are often set to open when the pressure of 
    the recovery cylinder's contents rises more than 5-10 psi above the 
    expected saturation pressure for the refrigerant; this margin is 
    exceeded by R12/R134a mixtures containing more than ten percent of the 
    contaminating refrigerant.26 Refrigerant mixture also 
    reduces recycling and leads indirectly to release. First, mixed 
    refrigerants not only lose their value but cost money to reclaim or 
    destroy, encouraging venting. Second, the direct releases and equipment 
    breakdowns caused by contamination lead to increased equipment 
    servicing, which itself leads to unavoidable releases of refrigerant. 
    Thus, whether the refrigerant were vented or mixed, failure to impose a 
    certification requirement on persons working with HFCs would increase 
    the probability of both HFCs and ozone-depleting refrigerants being 
    emitted to the atmosphere.
    ---------------------------------------------------------------------------
    
        \26\ Based on pressure-temperature graphs provided to Debbie 
    Ottinger of the Stratospheric Protection Division, EPA, by Dave 
    Bateman of the DuPont Company, April 29, 1996.
    ---------------------------------------------------------------------------
    
        Evidence collected by EPA indicates that without certification 
    requirements for technicians who work with substitute refrigerants, the 
    emergence of a class of uncertified individuals who are liable to mix 
    refrigerants is likely. Advertisements for one alternative have 
    highlighted the fact that technicians need not be certified to purchase 
    it. These advertisements have also implied, incorrectly, that the 
    substitute may be mixed with R12 without consequence. These 
    advertisements indicate that there is a market for alternatives that 
    can be purchased without certification and that can be used to service 
    CFC and HCFC equipment. At the same time, the advertisements indicate 
    that some parts of the market are transmitting incorrect information 
    that is likely to lead to the inappropriate mixture of the alternatives 
    with CFCs and HCFCs. EPA believes that technicians who have not 
    received training in the need to avoid mixing refrigerants are far more 
    likely to fall prey to such false advertising than certified 
    technicians, who have received training.
        Experience from the sales restriction on small containers, which 
    was mandated under section 609 of the Act before the sales restriction 
    under 608 became effective, also strongly supports EPA's concern that 
    inconsistent imposition of technician certification requirements or 
    sales restrictions will lead to refrigerant mixture. Some industry 
    representatives have reported that when sales of small containers of 
    R12 were restricted to only certified technicians, containers of R22, 
    which could still be sold to the general public, began appearing in 
    stores catering to the automotive DIY consumer. This implies that R22 
    was being used to service R12 equipment. Statistics collected by the 
    Mobile Air Conditioning Society (MACs) indicate that approximately 
    three percent of motor vehicle air conditioners now being serviced are 
    contaminated by mixed refrigerants.
        In addition to concerns related to refrigerant mixture and release, 
    industry representatives at the March 10, 1995 meeting cited the need 
    for fairness and consistency in applying rule provisions to all 
    potentially environmentally damaging refrigerants. The two contractors 
    present voiced the opinion that the imposition of less stringent 
    recovery or certification requirements for HFCs could undermine 
    compliance with recycling requirements for both HFCs and ozone-
    depleting refrigerants by confusing technicians and encouraging a 
    ``cavalier'' attitude toward refrigerant recovery. Other industry 
    representatives noted that due to similar concerns, their organizations
    
    [[Page 32082]]
    
    already required certification for technicians working with HFCs.
        For these reasons, EPA currently believes that it is necessary to 
    impose a technician certification requirement in order to implement 
    sections 608(a) and 608(c), and that EPA has authority under these 
    sections to promulgate a technician certification requirement. EPA 
    requests comment on the likelihood that failure to impose a technician 
    certification requirement on persons working with HFCs and PFCs would 
    lead to release and mixture of both ozone-depleting refrigerants and 
    substitutes.
        As noted above, EPA is not proposing to require that technicians 
    who have been certified to work with CFCs and HCFCs undertake 
    additional training and testing to work with HFCs and PFCs. The 
    techniques and requirements for recycling HFCs and PFCs are very 
    similar to those for CFCs and HCFCs; where there are differences (such 
    as compatibility with different lubricants), these differences have 
    been highlighted by the certification program for CFCs and HCFCs. In 
    addition, based on statements made by industry and educational 
    representatives at the March 10, 1995 industry meeting, EPA believes 
    that more recent information on proper handling of HFCs and PFCs will 
    be disseminated to certified technicians through refrigerant and 
    equipment manufacturers, industry associations, and the trade press. 
    Thus, the benefits of any recertification requirement would probably be 
    small, and would likely be outweighed by the costs of such 
    recertification. Instead, as part of its regular update of the 
    technician certification question bank, EPA is planning to include more 
    questions on handling HFC and PFC refrigerants and on the potential 
    impacts of global warming. EPA requests comment on this approach for 
    already certified technicians.
    
    E. Sales Restriction
    
        Under the current regulations promulgated under sections 608 and 
    609, only certified technicians may purchase CFC and HCFC refrigerants. 
    EPA is proposing to extend this sales restriction to HFC and PFC 
    refrigerants. The sales restriction would apply to HFC and PFC 
    refrigerants sold in all sizes of containers for use in all types of 
    appliances, including motor vehicle air conditioners. EPA considers the 
    sales restriction to be necessary to enforce the technician 
    certification requirements of both the refrigerant recycling 
    regulations promulgated under section 608 and those promulgated under 
    section 609 27 and ultimately, to implement the requirements 
    of sections 608(a) and 608(c)(2).
    ---------------------------------------------------------------------------
    
        \27\ EPA published a final rule under section 609 on December 
    30, 1997 that requires technicians servicing MVACs containing 
    substitute refrigerants to become certified. However, while section 
    609 restricts the sale of small containers of class I or class II 
    refrigerants, it does not restrict the sale of HFC or PFC 
    refrigerants. Thus, any sales restriction on these refrigerants must 
    be promulgated under the authority of section 608.
    ---------------------------------------------------------------------------
    
        In the absence of a sales restriction, the size and mobility of the 
    population that is subject to the technician certification requirements 
    would make compliance monitoring extremely difficult. Approximately 1.4 
    million technicians are employed in the stationary and mobile air-
    conditioning and refrigeration sectors. Many of these technicians, 
    particularly those in the stationary sector, may work out of vans 
    rather than having any fixed place of business. The sales restriction 
    ensures that these technicians are certified by placing monitors on 
    their supply lines. Because inspections can be performed at a 
    relatively small number of centralized retailer and wholesaler 
    locations, the sales restriction itself is relatively easy to enforce.
        Discussions with industry representatives indicate that the sales 
    restriction on CFCs and HCFCs was important in encouraging large 
    numbers of technicians to obtain certification. The largest 
    certification organizations report that the numbers of people 
    interested in obtaining certification rose sharply as the November, 
    1994 effective date of the sales restriction approached. Moreover, the 
    contractors who staff EPA's Stratospheric Ozone Hotline state that 
    during the summer, they receive between 20 and 40 telephone calls per 
    day from individuals who indicate that they are seeking technician 
    certification specifically because they want to be able to purchase 
    refrigerant. This is strong evidence that the sales restriction is 
    critical for ensuring that technicians are certified. As discussed 
    above, EPA believes that technician certification is necessary to meet 
    the requirements of sections 608(a) and (c).
        While there are methods of discouraging refrigerant mixing and 
    release other than technician certification combined with a sales 
    restriction, none of them appear to be sufficiently effective to 
    substitute for a sales restriction. One alternative method for 
    preventing mixture of ozone-depleting and HFC refrigerants might be to 
    require that both HFC containers and HFC appliances be equipped with 
    unique fittings that would prevent them from being connected to CFC or 
    HCFC containers and appliances. Under the SNAP program, HFC-134a 
    containers sold for use in the automotive market and MVACs that use 
    HFC-134a are required to be equipped with such fittings.
        However, while such fittings may be effective in reducing mixture 
    in some sectors, EPA believes that they would be impractical in other 
    sectors and would not necessarily reduce the venting of the CFC or HCFC 
    to be replaced. Only motor vehicle air conditioners (MVACs) containing 
    substitutes currently possess the specialized fittings; other types of 
    air-conditioning and refrigeration equipment containing substitutes, 
    including household, commercial, and industrial refrigerators and air-
    conditioners, do not. Introducing a unique fittings requirement to 
    these stationary sectors would be impractical for several reasons.
        The most fundamental reason is that the wide array of substitute 
    refrigerants available for stationary equipment makes the development 
    of a unique fitting for each one almost impossible. At least 25 
    refrigerants are currently being used in the stationary air-
    conditioning and refrigeration sectors, and more are being developed. 
    Unique fittings are designed by choosing the diameter, turning 
    direction, thread pitch (threads/inch) and shape of threads (normal vs. 
    square, also known as Acme). However, fittings with the same diameter 
    and turning direction can nearly always be connected using a wrench, 
    regardless of thread pitch or shape. Therefore, practically speaking, 
    the number of different fittings is limited to the double the number of 
    different diameters. (Each diameter yields both a clockwise and a 
    counterclockwise fitting.) The number of diameters is itself limited 
    because fittings must differ by at least 0.063 inch in diameter to 
    ensure they will not cross-connect, and the range of diameters is 
    limited by valve core and surrounding space restrictions. (In the MVAC 
    market to date, valve core and surrounding space restrictions have 
    resulted in fittings ranging in diameter from 0.3 inches to 0.625 
    inches.) Thus, the number of unique fittings that can be developed is 
    limited.
        Moreover, even if unique fittings could be found for each of the 
    refrigerants used in the stationary sectors, the logistics of 
    implementing them would be formidable. To begin with, a massive program 
    would be required to retrofit existing stationary appliances and 
    recovery equipment with all of the unique fittings. A great deal of 
    equipment in the stationary
    
    [[Page 32083]]
    
    sector has already been retrofitted to use substitute refrigerants; 
    retrofits would presumably be required not only for all this equipment, 
    but for all of the equipment that uses one of the four traditional 
    high-pressure refrigerants (R12, R22, R502, and R500). Otherwise, 
    technicians who became accustomed to relying on fittings to distinguish 
    among refrigerants might cross-contaminate these four.
        In addition, the large number of fittings in the stationary sectors 
    would make their use as a control on contamination unwieldy. A single 
    piece of recovery equipment intended for use with high-pressure 
    refrigerants might conceivably require over 20 fittings. Given the 
    similar exterior appearances of the fittings, finding the one that 
    matched a particular appliance would be difficult.
        More important, this matching of fittings with appliances is not 
    necessary if the recovery equipment has been properly cleared before 
    use with a new refrigerant. Technicians who work on stationary air-
    conditioning and refrigeration equipment have long worked with multiple 
    refrigerants, and recovery equipment for stationary appliances has been 
    designed for use with multiple refrigerants. Instead of engineering 
    controls, the stationary sectors have relied on training in refrigerant 
    charging and recovery to prevent cross-contamination. Adopting unique 
    fittings in these sectors would represent a fundamental change of 
    approach that would not only be unwieldy but redundant.
        Leaving aside the difficulty of introducing unique fittings to the 
    sectors that do not have them, these fittings may not be sufficient to 
    prevent cross-contamination in those sectors that do have them, such as 
    the automotive sector. Containers of HFCs that are intended for the 
    stationary sector and that therefore possess generic fittings may find 
    their way into the automotive air conditioning sector; industry 
    representatives have stated that this is already occurring to some 
    extent. In addition, equipment is available (e.g., old manifolds with 
    multiple hoses, side can tappers) that permits technicians or DIYers to 
    defeat the specialized fittings when the container is equipped with 
    them. Again, industry representatives indicate that this type of cross 
    contamination is already happening, and the statistics on contaminated 
    refrigerant from the automotive industry support them.
        Finally, there is no reason to believe that specialized fittings 
    would prevent an uncertified person from venting the original CFC or 
    HCFC before attempting to recharge a system with a substitute, because 
    this venting may well take place before the person discovers that he or 
    she cannot recharge the equipment with the purchased substitute. As 
    noted above, such venting prevents the requirements of 608(c) and 
    608(a) from being met.
        One option that would address the first of these three concerns, 
    but not the last two, is a more limited sales restriction. This would 
    restrict to certified technicians the sale of containers of substitute 
    refrigerants that lack specialized fittings, but would permit the sale 
    of containers of substitute refrigerants that contain such fittings to 
    the general public. In this manner, DIY consumers and uncertified 
    technicians would have unlimited access only to containers with 
    fittings, making mixture more difficult. However, EPA is concerned that 
    this approach would still permit mixture through defeat of the fittings 
    and would fail to address venting of the refrigerant previously in the 
    system. EPA requests comment on the potential effectiveness and 
    enforceability of such a restriction.
    
    F. Safe Disposal of Small Appliances, MVACs, and MVAC-like Appliances
    
    1. Coverage of HFCs and PFCs
        EPA is proposing to adopt the same approach to the disposal of 
    small appliances, MVACs and MVAC-like appliances charged with HFCs and 
    PFCs that it has adopted for these types of equipment charged with CFCs 
    and HCFCs. In the May 14, 1993 rule, EPA established specific 
    requirements for the safe disposal of appliances that enter the waste 
    stream with the charge intact, including small appliances, MVACs, and 
    MVAC-like appliances. Persons who take the final step in the disposal 
    process of small appliances, MVACs, and MVAC-like appliances that 
    contain CFCs or HCFCs must either recover any remaining refrigerant in 
    the appliance or verify that the refrigerant has previously been 
    recovered from the appliance or shipment of appliances. If they verify 
    that the refrigerant has been recovered previously, they must retain a 
    signed statement attesting to this. Recovery equipment used to remove 
    the refrigerant must meet certain standards but does not need to be 
    certified by a third party. Similarly, persons recovering the 
    refrigerant need not be certified.
        In addition to the specific safe disposal requirements, refrigerant 
    recovered from disposed small appliances, MVACs, and MVAC-like 
    appliances is subject to the reclamation requirements at Sec. 82.156(g) 
    and (h), which safeguard the purity of refrigerant flowing into the 
    stationary equipment service sectors, and to the reclamation 
    requirement in Appendix A to subpart B, which safeguards the purity of 
    refrigerant flowing into the MVAC and MVAC-like appliance service 
    sectors.
        In recent amendments to the subpart B MVAC recycling regulation, 
    EPA explicitly permitted refrigerant recovered from MVACs and MVAC-like 
    appliances at disposal facilities to be reused in MVACs and MVAC-like 
    appliances without being reclaimed as long as certain other 
    requirements were met. These requirements, which apply to HFCs (in 
    MVACs) in addition to CFCs and HCFCs, include the following: Only 609-
    certified technicians or disposal facility owners or operators may 
    recover the refrigerant; the refrigerant recovered from the MVACs and 
    MVAC-like appliances may not be mixed with refrigerant from any other 
    sources; only section 609-certified recovery equipment may be used to 
    recover the refrigerant; the refrigerant may be reused only in an MVAC 
    or MVAC-like appliance; the refrigerant may be sold only to section 
    609-certified technicians; and section 609-certified technicians must 
    recycle the refrigerant in section 609-certified recycling equipment 
    before charging it into the MVAC or MVAC-like appliance. As discussed 
    in the amendments to the 609 rule, these restrictions are intended to 
    ensure that the exemption from the reclamation requirement for 
    refrigerant removed from and charged into MVACs and MVAC-like 
    appliances does not compromise the purity of refrigerant flowing into 
    the MVAC and MVAC-like appliance service sectors.
        Most of the restrictions (except for the sales restriction and the 
    restrictions as they would apply to MVAC-like appliances) are 
    authorized by section 609, which requires persons servicing motor 
    vehicles for consideration to properly use approved refrigerant 
    recycling equipment and to be properly trained and certified. The 
    statutory definitions of ``properly use,'' ``approved equipment'' and 
    ``properly trained and certified'' all reference SAE standards that 
    include purity requirements for refrigerant used to service MVACs.
        These requirements for reuse of refrigerant from MVACs and MVAC-
    like appliances at disposal facilities apply in addition to the basic 
    safe disposal requirements of the subpart F regulations under section 
    608, particularly the requirement that disposers recover the 
    refrigerant (or ensure that the refrigerant is recovered by others) 
    from the MVAC or MVAC-
    
    [[Page 32084]]
    
    like appliance before the final step in the disposal process. Disposal 
    facilities must also continue to observe the requirement that they 
    retain signed statements attesting to the removal of the refrigerant 
    from the MVAC or MVAC-like appliance, if applicable.
        When refrigerant is recovered from disposed small appliances or 
    when it is recovered from disposed MVACs or MVAC-like appliances and 
    not reused in MVACs and MVAC-like appliances, only the safe disposal 
    and reclamation requirements set forth in the subpart F regulations 
    apply. In today's notice, EPA is proposing to extend these requirements 
    to small appliances, MVACs, and MVAC-like appliances that contain HFCs. 
    These requirements are necessary to implement the 608(c)(2) prohibition 
    on release of substitute refrigerants by defining good faith attempts 
    to recapture and recycle or safely dispose of the refrigerant in the 
    context of the disposal of small appliances, MVACs, and MVAC-like 
    appliances. EPA believes that the rationale for establishing the safe 
    disposal requirements for small appliances, MVACs, and MVAC-like 
    appliances that contain CFCs and HCFCs also applies to these appliances 
    when they contain substitutes for CFCs and HCFCs. As discussed at 
    length in the May 14, 1993 rule, these requirements are designed to 
    ensure that refrigerant is recovered before the appliance is finally 
    disposed of while granting as much flexibility as possible to the 
    disposal facility regarding the manner of its recovery (58 FR 28702). 
    EPA considered such flexibility important for the disposal sector, 
    which is highly diverse and decentralized. Because the disposal 
    infrastructure for appliances charged with HFCs and PFCs is identical 
    to that for appliances charged with CFCs and HCFCs, EPA believes that 
    these considerations apply equally to appliances containing HFCs and 
    PFCs. In addition, applying a consistent set of disposal requirements 
    to appliances containing CFCs, HCFCs, HFCs, and PFCs will reduce 
    confusion and minimize emissions of all four types of refrigerant 
    during the disposal process. Thus, the Agency believes that the 
    regulations regarding the safe disposal of appliances charged with HFCs 
    should be the same as those regarding the safe disposal of appliances 
    charged with CFCs and HCFCs. EPA requests comment on this proposal.
    2. Possible Clarifications
        EPA is also requesting comment on two possible modifications that 
    EPA is considering making to the safe disposal provisions to ensure 
    that EPA's interpretation of the regulation is clear on its face. As 
    stated in Applicability Determination number 59, the Agency interprets 
    the safe disposal provisions to apply to ``the entity which conducted 
    the process where the refrigerant was released if not properly 
    recovered.''
        Together, the possible changes to the regulations would clarify 
    that paragraph 82.156(f) applies to persons who perform disposal-
    related activities where the refrigerant would be released if not 
    properly recovered. One clarification would amend the definition of 
    ``opening'' to include the disposal of appliances. The first sentence 
    of the revised definition of ``opening'' would read, ``Opening an 
    appliance means any service, maintenance, repair, or disposal of an 
    appliance that would release refrigerant from the appliance to the 
    atmosphere unless the refrigerant were recovered previously from the 
    appliance.'' The rest of the definition would remain unchanged.
        The second clarification would add the phrase ``persons who open 
    the appliances in the course of disposing of them'' to the introductory 
    text of Sec. 82.156(f). The revised text would read (in part), 
    ``persons who take the final step in the disposal process of small 
    appliances, MVACs, or MVAC-like appliances (including but not limited 
    to scrap recyclers, landfill operators, and persons who open the 
    appliances in the course of disposing of them) must either: (1) Recover 
    any remaining refrigerant from the appliance in accordance with 
    paragraph (g) or (h) of this section, as applicable; or (2) Verify that 
    the refrigerant has been evacuated from the appliance or shipment of 
    appliances previously.'' The rest of Sec. 82.156(f) would remain 
    unchanged. EPA requests comment on these two possible changes.
    
    G. Certification by Owners of Recycling or Recovery Equipment
    
        EPA currently requires persons who maintain, service, repair, or 
    dispose of appliances containing CFCs or HCFCs to submit a signed 
    statement to the appropriate EPA Regional office stating that they 
    possess recovery and recycling equipment and are complying with the 
    applicable requirements of the rule. EPA is proposing to extend this 
    provision to persons who maintain, service, repair, or dispose of 
    appliances containing HFCs or PFCs. Persons who had already sent a 
    signed statement to EPA for their work on appliances containing CFCs or 
    HCFCs would not need to send a new statement. EPA anticipates, 
    therefore, that only businesses coming into existence after the date of 
    publication of the final rule would potentially be affected by the 
    amended provision.
        EPA believes that the rationale for requiring this report from 
    persons who maintain, service, repair, or dispose of appliances 
    containing HFCs or PFCs is the same as that for requiring it from 
    persons who maintain, service, repair, or dispose of appliances 
    containing CFCs or HCFCs. That is, the requirement would help ensure 
    that persons who opened or disposed of appliances were making a good 
    faith effort to recover and recycle the refrigerant and had the 
    appropriate equipment available to comply with the section 608(c) 
    venting prohibition. EPA would also use this information in conjunction 
    with telephone or other business listings to target its efforts to 
    enforce the venting prohibition. Finally, consistent application of the 
    reporting requirement to businesses that handled appliances containing 
    HFCs and PFCs as well as to businesses that handled appliances 
    containing CFCs and HCFCs would reduce confusion and thereby minimize 
    emissions of all four types of refrigerants.
    
    H. Servicing Apertures
    
        EPA prohibits the sale or distribution of CFC and HCFC appliances 
    that are not equipped either with a process stub (in the case of small 
    appliances) or with a servicing aperture (in the case of all other 
    appliances) to facilitate refrigerant recovery. EPA is today proposing 
    to extend this prohibition to the sale and distribution of appliances 
    containing HFCs or PFCs. EPA believes that the rationale for requiring 
    servicing apertures or process stubs on HFC and PFC appliances is the 
    same as that for requiring these design features on CFC and HCFC 
    appliances. Specifically, these features permit technicians to comply 
    with the venting prohibition by making it much easier for them to 
    attach recovery equipment to the refrigerant circuit and thereby 
    recover the refrigerant properly. Thus, EPA is proposing to require 
    these features in order to implement the venting prohibition.
    
    I. Prohibition on Manufacture of One-Time Expansion Devices That 
    Contain Other Than Exempted Refrigerants
    
        In order to implement the venting prohibition as it applies to one-
    time expansion devices using refrigerants other than nitrogen or carbon 
    dioxide (see discussion in section IV.A.1.b. above), EPA is proposing a 
    provision that would prohibit their manufacture in or import into the 
    U.S. EPA believes that a prohibition on manufacturing or importing the 
    devices (which include
    
    [[Page 32085]]
    
    self-chilling cans) is simultaneously the least burdensome and the most 
    effective, efficient, and equitable way of carrying out the venting 
    prohibition as it applies to them. As discussed earlier in section 
    II.A., EPA believes that section 608(c)(2) implicitly provides the 
    Agency authority to promulgate regulations as necessary to implement 
    and enforce the statutory prohibition, and section 301(a)(1)(a) further 
    supplements that authority. As discussed below, EPA believes that a ban 
    on manufacture and import of the devices is the only practical way to 
    implement the prohibition on venting of section 608(c)(2) of the Act 
    and hence is necessary to implement and enforce that 
    prohibition.28
    ---------------------------------------------------------------------------
    
        \28\ EPA has also proposed to find that self-chilling cans using 
    HFC-152a and HFC-134a are unaccepted under its SNAP program. If EPA 
    promulgates a final rule including this finding, the manufacture of 
    self-chilling cans using HFC-152a and HFC-134a will be prohibited 
    unde SNAP.
    ---------------------------------------------------------------------------
    
        First, a prohibition on manufacturing or importing the devices 
    would not be unreasonably burdensome. One-time expansion devices 
    function only by venting; one-time expansion devices containing other 
    than exempted refrigerants therefore have no legal use, given the self-
    effectuating venting prohibition of 608(c)(2). Thus, a prohibition on 
    manufacture and import would not interfere with any lawful use of the 
    device or can. At the same time, any burden on potential manufacturers 
    of the can either would not exist, because perfect implementation of 
    the venting prohibition would reduce demand for the cans to zero, or, 
    to the extent that it existed, would exist solely as a result of 
    illegal activity on the part of consumers. Thus, any burden placed on 
    the manufacturer by a ban on manufacturing should be discounted. In 
    contrast, as discussed further below, efforts to stop use of the can 
    would place heavy burdens both on consumers and on EPA.
        Second, prohibiting the manufacture or import of cans containing 
    other than exempted refrigerants would be both more effective and more 
    efficient than attempting to prevent the use of such cans by millions 
    of potential consumers. EPA estimates that the total market for canned 
    beverages in the U.S. is 100 billion units per year. Thus, if self-
    chilling cans captured even a small percentage of this market, very 
    large numbers of cans could be used. For instance, if self-chilling 
    cans captured just one percent of the canned beverage market, one 
    billion self-chilling cans per year could be used, potentially 
    violating the venting prohibition one billion times. Potential 
    consumers of the can would include virtually the entire U.S. population 
    of 265 million people. Without a ban on manufacture, the huge number of 
    potential violators and violations would make the venting prohibition 
    extremely difficult to enforce. A massive outreach campaign would be 
    required to inform the public of the environmental and legal 
    implications of using the cans, and such a campaign would still miss 
    some fraction of the population. Of course, such a campaign would also 
    be very expensive. At the same time, enforcement against consumers who 
    either ignored or were ignorant of the campaign would be very 
    difficult, due to the large numbers of potential consumers and the 
    unpredictable and widespread nature of potential violations. In 
    contrast, outreach to and enforcement against potential manufacturers 
    of the can would only have to reach a few targets, interdicting the 
    cans at the top of the distribution pyramid.
        Third, a prohibition on manufacturing or importing cans containing 
    other than exempted refrigerants would be more equitable than an 
    enforcement campaign against consumers who might not recognize the 
    environmental and legal implications of using such cans. While 
    consumers of such cans would be expected to be aware that they were 
    releasing gas to the atmosphere, it might not be reasonable to expect 
    them to be aware that the gas being released contributed significantly 
    to global warming or that its release was illegal, particularly since 
    opening the can and releasing the gas would be the only possible use of 
    a legally purchased product. As noted above, even a massive outreach 
    campaign is likely to miss some fraction of consumers, and given the 
    very large underlying population, even a small fraction would be 
    sizable. However, it is both reasonable and standard practice to hold 
    manufacturers responsible for knowledge of and compliance with the 
    environmental and other laws and regulations applicable to their 
    products.
        Thus, a ban on manufacture and import of cans containing other than 
    exempted refrigerants is the only practical way to implement the 
    venting prohibition as it applies to them. Moreover, there are a number 
    of precedents for prohibiting the manufacture, sale, and/or 
    distribution of appliances, other equipment, and refrigerants under 
    section 608 in order to reduce refrigerant emissions. Sections 82.154 
    (j) and (k) prohibit the sale or distribution of appliances unless they 
    possess servicing apertures or process stubs, and Sec. 82.154(c) 
    prohibits the manufacture or import of recycling or recovery equipment 
    that is not certified. Sections 82.154(g) and (h) prohibit the sale of 
    used ozone-depleting refrigerants that have not been reclaimed (with 
    minor exceptions), and Sec. 82.154(m) prohibits the sale of ozone-
    depleting refrigerants to uncertified individuals (again with minor 
    exceptions). Sales restrictions were more appropriate than 
    manufacturing bans in the latter cases because (1) a manufacturing ban 
    could not apply to used refrigerants, and (2) purchase and use of 
    ozone-depleting refrigerants by some individuals, in this case 
    certified technicians, is legal.
    
    J. Recordkeeping Requirements
    
        EPA currently requires reporting and recordkeeping from the 
    following persons and entities:
    a. Persons Who Sell or Distribute Refrigerant
        Persons who sell or distribute any CFC or HCFC refrigerant must 
    retain invoices that indicate the name of the purchaser, the date of 
    sale, and the quantity of refrigerant purchased. These records help the 
    Agency to track refrigerant use and to verify compliance with the 
    venting prohibition (Sec. 82.166(a)).
    b. Technicians
        Certified technicians must keep a copy of their certificate at 
    their place of business. This permits EPA inspectors to determine 
    whether a technician has been certified, as required by the regulations 
    (Sec. 82.166(l)).
        Technicians servicing equipment containing 50 or more pounds of CFC 
    or HCFC refrigerant must provide the owner or operator of the appliance 
    with an invoice that indicates the amount of refrigerant added to the 
    appliance. These records permit owners or operators of appliances 
    containing 50 or more pounds of refrigerant to determine whether they 
    need to take action to comply with the leak repair provisions 
    (Sec. 82.166(j)).
    c. Appliance Owners
        Owners of appliances containing 50 or more pounds of CFC or HCFC 
    refrigerant must keep servicing records documenting the date and type 
    of service, as well as the quantity of refrigerant added. These 
    requirements ensure that owners can determine when they must take 
    action under the leak repair requirements. In addition, equipment 
    owners who decide not to repair leaks must develop and maintain a 
    record of a plan that states that the equipment will be retired, 
    replaced or retrofitted. The plan permits EPA
    
    [[Page 32086]]
    
    inspectors to ensure that equipment owners intend to take action to 
    reduce emissions and actually take such action (Sec. 82.166(k)).
    d. Owners of Industrial Process Refrigeration
        Owners of industrial process refrigeration equipment who wish to 
    receive an extension or exclusion under the leak repair provisions are 
    subject to the following reporting and recordkeeping requirements.
        i. Those persons wishing to extend leak repair compliance beyond 
    the required 30 days must maintain and submit to EPA information 
    identifying the facility, the leak rate, the method used to determine 
    the leak rate and full charge, the date a leak rate greater than 
    allowable was discovered, the location of the leaks, any repair work 
    completed thus far and date completed, a plan to fix other outstanding 
    leaks to achieve allowable leak rate, reasons why greater than 30 days 
    is needed, and an estimate of when repair work will be completed. Any 
    dates and results of static and dynamic tests must also be maintained 
    and submitted to EPA (Sec. 82.166(n)).
        ii. Those persons wishing to extend retrofit compliance beyond the 
    required one year must maintain and submit to EPA information 
    identifying the facility, the leak rate, the method used to determine 
    the leak rate and full charge, the date a leak rate of greater than the 
    allowable rate was discovered, the location of leaks, any repair work 
    that has been completed thus far and date completed, a plan to complete 
    the retrofit or replacement of the system, the reasons why more than 
    one year is necessary, the date of notification to EPA, an estimate of 
    when retrofit or replacement work will be completed, if time changes 
    for original estimates occur, documentation of the reason why, and the 
    date of notification to EPA regarding a change in the estimate of when 
    the work will be completed (Sec. 82.166(o)).
        iii. Those persons wishing to exclude purged refrigerants that are 
    destroyed from the annual leak rate calculations must maintain records 
    on-site to support the amount of refrigerant claimed sent for 
    destruction. These records must include flow rate, quantity or 
    concentration of the refrigerant in the vent stream, and periods of 
    purge flow (Sec. 82.166(p)).
        iv. Those persons wishing to calculate the full charge of an 
    affected appliance by establishing a range based on the best available 
    data, regarding the normal operating characteristics and conditions for 
    the appliance, must maintain records on-site to support the methodology 
    used in selecting or modifying the particular range (Sec. 82.166(q)).
        These requirements allow EPA to determine whether or not extensions 
    and exclusions requested under the leak repair provisions are 
    warranted.
    e. Refrigerant Reclaimers
        Refrigerant reclaimers must certify to EPA that they will comply 
    with the rule's requirements and must submit lists of the equipment 
    that they use to clean and analyze refrigerants. This information 
    enables EPA to verify reclaimers' compliance with refrigerant purity 
    standards and refrigerant emissions limits. In addition, refrigerant 
    reclaimers must maintain records of the names and addresses of persons 
    sending them material for reclamation and the quantity of material sent 
    to them for reclamation. This information must be maintained on a 
    transactional basis. Within 30 days of the end of the calendar year, 
    reclaimers must report to EPA the total quantity of material sent to 
    them that year for reclamation, the mass of refrigerant reclaimed that 
    year, and the mass of waste products generated that year. These 
    requirements help the Agency to track refrigerant use and to ensure 
    compliance with the venting prohibition by both reclaimers and their 
    customers (Sec. 82.166(g) and (h)).
    f. Equipment Certification Organizations
        Equipment testing organizations must apply to EPA to become 
    approved. This application process is necessary to ensure that all 
    approved testing laboratories have the equipment and expertise to test 
    equipment to the applicable standards. Once approved, equipment testing 
    organizations must maintain records of the tests performed and their 
    results, and must submit a list of all certified equipment to EPA 
    annually. Testing organizations must also notify EPA whenever a new 
    model of equipment is certified or whenever an existing certified model 
    fails a recertification test. This information is required to ensure 
    that recycling and recovery equipment meets the performance standards 
    of the regulation (Secs. 82.160 and 82.166(c), (d), and (e)).
    g. Disposers
        Persons who conduct final disposal of small appliances, room air 
    conditioners, and MVACs and who do not recover the refrigerant 
    themselves must maintain copies of signed statements attesting that the 
    refrigerant has been removed prior to final disposal of each appliance. 
    These records help EPA to verify that refrigerant is recovered at some 
    point during the disposal process even if the final disposer does not 
    have recovery equipment (Sec. 82.166(i)).
    h. Technician Certification Programs
        Organizations operating technician certification programs must 
    apply to EPA to have their programs approved. The application process 
    ensures that the technician certification programs meet minimum 
    standards for generating, tracking, and grading tests, and keeping 
    records. Approved technician certification programs have to maintain 
    records including the names of certified technicians and the unique 
    numbers assigned to each technician certified through their programs. 
    These records allow both the Agency and the certification program to 
    verify certification claims and to monitor the certification process. 
    Approved technician certification programs also have to submit to EPA 
    reports every six months including the pass/fail rate and testing 
    schedules. Such reports give the Agency the ability to evaluate 
    certification programs and modify certification requirements if 
    necessary (Sec. 82.166(f)).
        EPA is proposing to extend all of these requirements, as 
    applicable, to persons who sell or distribute HFC or PFC refrigerants, 
    to technicians who service HFC or PFC appliances, to persons who own 
    HFC or PFC appliances containing more than 50 pounds of refrigerant, to 
    reclaimers that reclaim HFC or PFC refrigerants, to equipment 
    certification organizations that certify recovery or recycling 
    equipment for use with HFCs or PFCs, and to technician certification 
    programs that certify technicians who work with HFCs or PFCs.
        The rationale for requiring these records for persons who handle 
    HFC or PFC refrigerants or equipment is the same as that set forth 
    above for requiring such records for persons who handle CFC or HCFC 
    refrigerants or equipment. In all cases, the records would be necessary 
    to ensure compliance with the regulatory program implementing the 
    section 608(c)(2) prohibition on venting and hence would be necessary 
    to implement and enforce section 608(c)(2) and section 608(a) as well, 
    for the provisions in this proposal that are authorized by that 
    section. The records proposed to be required would make it possible for 
    EPA both to monitor compliance and to enforce against violations.
    
    V. Summary of Supporting Analyses
    
    A. Executive Order 12866
    
        Under Executive Order 12866 (58 FR 51735, October 4, 1993), the 
    Agency
    
    [[Page 32087]]
    
    must determine whether this regulatory action is ``significant'' and 
    therefore subject to OMB review and the requirements of the Executive 
    Order. The Order defines ``significant'' regulatory action as one that 
    is likely to lead to a rule that may:
        (1) Have an annual effect on the economy of $100 million or more, 
    or adversely and materially affect a sector of the economy, 
    productivity, competition, jobs, the environment, public health or 
    safety, or State, local, or tribal governments or communities;
        (2) Create a serious inconsistency or otherwise interfere with an 
    action taken or planned by another agency;
        (3) Materially alter the budgetary impact of entitlement, grants, 
    user fees, or loan programs or the rights and obligations of recipients 
    thereof; or
        (4) Raise novel legal or policy issues arising out of legal 
    mandates, the President's priorities, or the principles set forth in 
    the Executive Order.
        It has been determined by OMB and EPA that this proposed action to 
    amendment to the final rule is not a ``significant regulatory action'' 
    under the terms of Executive Order 12866 and is therefore not subject 
    to OMB review under the Executive Order. Nevertheless, the Agency has 
    performed a cost benefit analysis of this regulation, which is 
    available for review in the public docket for this rulemaking. This 
    analysis is summarized below.
    1. Baseline
        Since these regulations are being promulgated in addition to other 
    provisions that affect the use of substitute refrigerants, the baseline 
    for this analysis must reflect the state of affairs after the 
    implementation of previous provisions and before the implementation of 
    the final rule. The provision of the Clean Air Act that must be 
    considered when defining the baseline for these regulations is the 
    prohibition on venting contained in section 608(c)(2), which is self-
    effectuating. For the purposes of the analysis, EPA chose two variables 
    to describe the effects of this provision: The percentage of the market 
    in which recycling and recovery would occur as a result of the 
    provision (referred to as either market penetration or compliance); and 
    the average recapture efficiency of the recycling or recovery methods 
    that would be employed by the complying population.
        The self-effectuating prohibition on venting in section 608(c)(2) 
    can be considered a minimal requirement to recycle because chemicals 
    must be recycled, or at least stored, if they cannot be vented. 
    However, because the prohibition on venting does not in itself contain 
    standards, maximum recovery efficiency and full compliance would not be 
    expected under the prohibition alone. Instead, recovery efficiency and 
    compliance are likely to vary across sectors depending upon whether 
    recycling is privately cost-effective in that sector. Recycling will be 
    privately cost-effective in a sector when the value of the recovered 
    refrigerant exceeds the labor and equipment costs for the recovery, as 
    it does in sectors with large charge sizes. The cost-benefit analysis 
    assumes that in those sectors where recycling is estimated to be 
    privately cost-effective, compliance with the venting prohibition will 
    be 100 percent, and recovery efficiency will be 95 percent. The figures 
    are assumed to remain the same after imposition of the regulation. In 
    those sectors where recycling is not estimated to be privately cost 
    effective, including the household refrigeration, household air-
    conditioning, other appliance, and refrigerated transport sectors, 
    compliance with the venting prohibition is assumed to be 80 percent, 
    and recovery efficiencies are assumed to be 75 percent. These figures 
    are assumed to rise to 100 percent and 90 percent respectively after 
    imposition of the regulation.
    2. Costs
        The costs of the substitutes recycling rule consist of the costs of 
    increased compliance with the venting prohibition (primarily labor 
    costs), the costs of certifying recycling and recovery equipment, the 
    costs of certifying technicians, the costs of the sales restriction, 
    recordkeeping costs, and refrigerant storage costs. The Agency 
    estimates the cost for this regulatory program over a 29-year period 
    between 1996 and 2025 is $1,619 million using a 2% discount rate, and 
    $782 million using a 7% discount rate.
    3. Benefits
        The benefits of the provisions discussed above consist of (1) 
    avoided damage to air-conditioning and refrigeration equipment that 
    would occur if, without regulation, contaminated refrigerants were 
    charged into equipment, and (2) avoided damage to human health and the 
    environment that would occur if, without regulation, environmentally 
    harmful refrigerants were released rather than recaptured. EPA's 
    estimate of human health and environmental benefits is based on (a) the 
    estimates of the benefits of avoiding emissions of ozone-depleting 
    compounds that were developed for the 1993 RIA, and (b) estimates of 
    the benefits of avoiding emissions of global warming compounds that are 
    derived from a ``The Social Costs of Greenhouse Gas Emissions: An 
    Expected Value Approach.29'' This paper surveyed previous 
    efforts to quantify the effects of global climate change and developed 
    a technique for calculating the marginal impact of emitting a ton of 
    carbon. Benefits quantified include reductions in damages from sea 
    level rise, reduced agricultural yields, reduced water supply, and 
    other impacts. The paper explicitly incorporated many of the 
    uncertainties involved in developing the estimate and thereby developed 
    lower-bound, best-estimate, and upper-bound values for the benefit of 
    avoiding emissions of a ton of carbon. EPA adjusted these estimates to 
    account for the facts that (1) U.S. benefits would only be a fraction 
    of world-wide benefits and (2) on a kilogram-for-kilogram basis, the 
    HFC and PFC refrigerants have many times the global warming potential 
    of carbon.
    ---------------------------------------------------------------------------
    
        \29\ Frankhauser, S. ``The Social Cost of Greenhouse Gas 
    Emissions: An Expected Value Approach,'' Energy Journal 15(2), 1994, 
    pp. 157-183.
    ---------------------------------------------------------------------------
    
        As noted above, the analysis assumes that the rule increases both 
    compliance with the venting prohibition and the efficiency of many 
    recovery jobs. The Agency estimates the range of benefits to be from 
    $1,060 million to $11,188 million, using the lower and upper bound 
    estimates of the benefits of avoided equipment damage and of the 
    domestic benefits of avoiding emission of a kilogram of refrigerant. 
    These benefits were discounted at a 2% discount rate. The benefits 
    range from $475 million to $5,615 million when discounted at a 7% 
    discount rate.
    
    B. Unfunded Mandates Reform Act
    
        Title II of the Unfunded Mandates Reform Act of 1995 (UMRA), P.L. 
    104-4, establishes requirements for Federal agencies to assess the 
    effects of certain regulatory actions on State, local, and tribal 
    governments and the private sector. Under sections 202 and 205 of the 
    UMRA, EPA generally must prepare a written statement of economic and 
    regulatory alternatives analyses for proposed and final rules with 
    Federal mandates, as defined by the UMRA, that may result in 
    expenditures to State, local, and tribal governments, in the aggregate, 
    or to the private sector, of $100 million or more in any one year.
        EPA has determined that this rule does not contain a Federal 
    mandate that may result in expenditures of $100 million or more for 
    State, local, and tribal governments in the aggregate, or
    
    [[Page 32088]]
    
    the private sector, in any one year. As noted above, EPA's cost-benefit 
    analysis concluded that the total annual costs of the rule will be less 
    than $100 million per year. State, local, and tribal governments may 
    have to pay some costs for refrigerant recycling when their air-
    conditioning and refrigeration equipment is serviced or disposed of, 
    but these costs will be small. Moreover, most municipal solid waste 
    facilities do not accept white goods and so will not be affected by the 
    safe disposal provisions of the rule. Thus, today's proposed rule is 
    not subject to the requirements of sections 202 and 205 of the UMRA.
        For the reasons outlined above, EPA has also determined that this 
    rule contains no regulatory requirements that might significantly or 
    uniquely affect small governments. Thus, today's proposed rule is not 
    subject to the requirements of section 203 of the UMRA.
    
    C. Paperwork Reduction Act
    
        This proposed rule has no new information requirements subject to 
    the Paperwork Reduction Act.
    
    D. Regulatory Flexibility
    
        The Regulatory Flexibility Act (RFA) generally requires an agency 
    to conduct a regulatory flexibility analysis of any rule subject to 
    notice and comment rulemaking requirements unless the agency certifies 
    that the rule will not have a significant economic impact on a 
    substantial number of small entities. Small entities include small 
    businesses, small not-for-profit enterprises, and small governmental 
    jurisdictions. EPA has concluded that this proposed rule would not have 
    a significant impact on a substantial number of small entities.
        EPA performed a detailed screening analysis in 1992 of the impact 
    of the recycling regulation for ozone-depleting refrigerants on small 
    entities. The methodology of this analysis is discussed at length in 
    the May 14, 1993 regulation (58 FR 28710). EPA has updated that 
    analysis to examine the impact of the recycling regulation for 
    substitute refrigerants, and has concluded that this regulation will 
    not have a significant impact on a substantial number of small 
    entities. The methodology for the updated analysis is the same as for 
    the initial analysis, except EPA has also considered the changing 
    market share of HFC equipment and compliance with the venting 
    prohibition that would occur in the absence of the rule. This approach 
    makes the screening analysis more consistent with the cost-benefit 
    analysis discussed above. In addition, EPA added an analysis of the 
    potential impact of a sales restriction on HFC refrigerants on auto 
    parts and supply stores that are small businesses.
        In the updated screening analysis, EPA estimates that 118 small 
    businesses may incur compliance costs in excess of 1% of their sales, 
    while 39 small businesses may incur compliance costs in excess of 3% of 
    their sales. These numbers respectively represent 0.1% and 0.03% of the 
    122,416 small businesses that EPA estimates are affected by the rule. 
    Based on this analysis, EPA does not believe that this regulation will 
    have a significant impact on a substantial number of small entities. 
    Consequently, I hereby certify that this proposed rule will not have a 
    significant adverse effect on a substantial number of small entities.
        Although this rule will not have a significant adverse effect on a 
    substantial number of small entities, EPA has made numerous efforts to 
    involve small entities in the rulemaking process and to incorporate 
    flexibility into the proposed rule for small entities, where 
    appropriate. Efforts to involve small entities include the March 10, 
    1995, industry meeting, which included several trade groups 
    representing small businesses, and a number of individual meetings with 
    both small businesses and associations representing small businesses. 
    EPA has also developed outreach materials, including fact sheets and a 
    videotape, to help small businesses to comply with the existing 
    refrigerant recycling regulations and the prohibition on venting of 
    both ozone-depleting refrigerants and their substitutes.
        Moreover, the proposed rule grants to small businesses working with 
    substitute refrigerants the same flexibility that was granted to small 
    businesses working with CFC and HCFC refrigerants (58 FR 28667-28669, 
    28712). Thus, for instance, the proposed rule would permit persons 
    servicing small appliances (frequently small businesses) to use 
    relatively inexpensive recovery equipment, and would establish a 
    flexible program for the safe disposal of small appliances, MVACs, and 
    MVAC-like appliances. In addition, the rule would permit HVAC/R 
    contractors to recover HFCs using recycling and recovery equipment 
    designed for use with CFCs and HCFCs, and would permit technicians 
    certified to work with CFCs and HCFCs to work with HFCs with no further 
    testing.
    
    E. National Technology Transfer and Advancement Act
    
        Section 12(d) of the National Technology Transfer and Advancement 
    Act of 1995 (``NTTAA''), Pub L. 104-113, section 12(d) (15 U.S.C. 272 
    note), directs EPA to use voluntary consensus standards in its 
    regulatory activities unless to do so would be inconsistent with 
    applicable law or otherwise impractical. Voluntary consensus standards 
    are technical standards (e.g., materials specifications, test methods, 
    sampling procedures, business practices, etc.) that are developed or 
    adopted by voluntary consensus standards bodies. The NTTAA requires EPA 
    to provide Congress, through OMB, explanations when the Agency decides 
    not to use available and applicable voluntary consensus standards.
        In this document, EPA is proposing to use voluntary consensus 
    standards in all of the applications covered by the proposed 
    regulations for which there are voluntary consensus standards 
    available. Thus, EPA is proposing to use ARI Standard 740-1995, 
    Standard for Refrigerant Recovery/Recycling Equipment, and ARI Standard 
    700-1995, Standard for Specifications for Fluorocarbon and Other 
    Refrigerants. The first establishes requirements and test methods for 
    refrigerant recovery and recycling equipment; the second establishes 
    specifications and test methods for refrigerants. EPA invites public 
    comment on whether there are other available and applicable voluntary 
    consensus standards that the Agency should apply.
    
    F. Children's Health Protection
    
        This proposed rule is not subject to E.O. 13045, entitled 
    ``Protection of Children from Environmental Health Risks and Safety 
    Risks'' (62 FR 19885, April 23, 1997), because it does not involve 
    decisions on environmental health risks or safety risks that may 
    disproportionately affect children.
    
    List of Subjects in 40 CFR Part 82
    
        Environmental protection, Air pollution control, Contractors, 
    Reclaimers, Reclamation, Recycling, Reporting and recordkeeping 
    requirements, Technician.
    
        Dated: May 28, 1998.
    Carol M. Browner,
    Administrator.
        Title 40 of the Code of Federal Regulations, part 82, is proposed 
    to be amended as follows:
    
    PART 82--[AMENDED]
    
        1. The authority citation for Part 82 continues to read as follows:
        Authority: 42 U.S.C. 7414, 7601, 7671-7671q.
    
        1a. Section 82.150 is amended by revising paragraph (a) to read as 
    follows:
    
    [[Page 32089]]
    
    Sec. 82.150  Purpose and scope.
    
        (a) The purpose of this subpart is to reduce emissions of class I 
    and class II refrigerants to the lowest achievable level during the 
    service, maintenance, repair, and disposal of appliances and to 
    maximize compliance with the prohibition on venting of all refrigerants 
    during the service, maintenance, repair, and disposal of appliances in 
    accordance with section 608 of the Clean Air Act.
    * * * * *
        2. Section 82.152 is amended by adding definitions for ``higher-
    pressure appliance,'' ``leak rate,'' ``one-time expansion device,'' 
    ``refrigerant,'' and ``substitute,'' and by revising the definitions 
    for ``appliance,'' ``full charge,'' ``high-pressure appliance,'' ``low-
    pressure appliance,'' ``opening,'' ``reclaim,'' ``technician,'' and 
    ``very-high-pressure appliance'' to read as follows:
    
    
    Sec. 82.152  Definitions.
    
        Appliance means any device which contains and uses a refrigerant 
    and which is used for household or commercial purposes, including any 
    air conditioner, refrigerator, chiller, or freezer.
    * * * * *
        Full charge means the amount of refrigerant required for normal 
    operating characteristics and conditions of the appliance as determined 
    by using one or a combination of the following four methods:
        (1) Use the equipment manufacturer's determination of the correct 
    full charge for the equipment;
        (2) Determine the full charge by making appropriate calculations 
    based on component sizes, density of refrigerant, volume of piping, and 
    other relevant considerations;
        (3) Use actual measurements of the amount of refrigerant added or 
    evacuated from the appliance; and/or
        (4) Use an established range based on the best available data 
    regarding the normal operating characteristics and conditions for the 
    appliance, where the mid-point of the range will serve as the full 
    charge, and where records are maintained in accordance with 
    Sec. 82.166(q).
    * * * * *
        High-pressure appliance means an appliance that uses a refrigerant 
    with a liquid phase saturation pressure between 45 psia and 220 psia at 
    104 degrees F. This definition includes but is not limited to 
    appliances using R12, R114, R134a, R401A and B, and R500.
    * * * * *
        Higher-pressure appliance means an appliance that uses a 
    refrigerant with a liquid phase saturation pressure between 220 psia 
    and 305 psia at 104 degrees F. This definition includes but is not 
    limited to appliances using R22, R502, R402A and B, and R407A, B, and 
    C.
    * * * * *
        Leak rate means the rate at which an appliance is losing 
    refrigerant, measured between refrigerant charges or over 12 months, 
    whichever is shorter. The leak rate is expressed in terms of the 
    percentage of the appliance's full charge that would be lost over a 12-
    month period if the current rate of loss were to continue over that 
    period. The rate is calculated using the following method:
        (1) Take the number of pounds of refrigerant added to the appliance 
    to return it to a full charge and divide it by the number of pounds of 
    refrigerant the appliance normally contains at full charge;
        (2) Take the shorter of: (a) 365 days, and (b) the number of days 
    that have passed since the last day refrigerant was added and divide 
    that number by 365 days;
        (3) Take the number calculated in step (1) and divide it by the 
    number calculated in step (2); and
        (4) Multiply the number calculated in step (3) by 100 to calculate 
    a percentage.
        This method is summarized in the following formula:
        [GRAPHIC] [TIFF OMITTED] TP11JN98.003
        
    * * * * *
        Low-pressure appliance means an appliance that uses a refrigerant 
    with a liquid phase saturation pressure below 45 psia at 104 degrees 
    Fahrenheit. This definition includes but is not limited to appliances 
    using R11, R123, and R113.
    * * * * *
        One-time expansion device means an appliance that relies on the 
    release of refrigerant to the environment to obtain cooling.
        Opening an appliance means any service, maintenance, or repair on 
    an appliance that would release refrigerant from the appliance to the 
    atmosphere unless the refrigerant were recovered previously from the 
    appliance. Connecting and disconnecting hoses and gauges to and from 
    the appliance to measure pressures within the appliance and to add 
    refrigerant to or recover refrigerant from the appliance shall not be 
    considered ``opening.''
    * * * * *
        Reclaim refrigerant means to reprocess refrigerant to all of the 
    specifications in appendix A to 40 CFR part 82, subpart F (based on ARI 
    Standard 700-1995, Specification for Fluorocarbons and Other 
    Refrigerants) that are applicable to that refrigerant and to verify 
    that the refrigerant meets these specifications using the analytical 
    methodology prescribed in appendix A. In general, reclamation involves 
    the use of processes or procedures available only at a reprocessing or 
    manufacturing facility.
    * * * * *
        Refrigerant means, for purposes of this Subpart, any class I or 
    class II substance used for heat transfer purposes, or any substance 
    used as a substitute for such a class I or class II substance by any 
    user in a given end-use, except for the following substitutes in the 
    following end-uses:
        (1) Ammonia in commercial or industrial process refrigeration or in 
    absorption units
        (2) Hydrocarbons in industrial process refrigeration (processing of 
    hydrocarbons)
        (3) Chlorine in industrial process refrigeration (processing of 
    chlorine and chlorine compounds)
        (4) Carbon dioxide in any application
        (5) Nitrogen in any application
        (6) Water in any application
    * * * * *
        Substitute means any chemical or product substitute, whether 
    existing or new, that is used by any person as a replacement for a 
    class I or II compound in a given end-use.
    * * * * *
        Technician means any person who performs maintenance, service, or 
    repair that could be reasonably expected to release refrigerants from 
    appliances, except for MVACs, into the atmosphere. Technician also 
    means any person who performs disposal of appliances, except for small 
    appliances, MVACs, and MVAC-like appliances, that could be reasonably 
    expected to release refrigerants from the appliances into the 
    atmosphere. Performing maintenance, service, repair, or disposal could 
    be reasonably expected to release
    
    [[Page 32090]]
    
    refrigerants only if the activity is reasonably expected to violate the 
    integrity of the refrigerant circuit. Activities reasonably expected to 
    violate the integrity of the refrigerant circuit include activities 
    such as attaching and detaching hoses and gauges to and from the 
    appliance to add or remove refrigerant or to measure pressure and 
    adding refrigerant to and removing refrigerant from the appliance. 
    Activities such as painting the appliance, re-wiring an external 
    electrical circuit, replacing insulation on a length of pipe, or 
    tightening nuts and bolts on the appliance are not reasonably expected 
    to violate the integrity of the refrigerant circuit. Performing 
    maintenance, service, repair, or disposal of appliances that have been 
    evacuated pursuant to Sec. 82.156 could not be reasonably expected to 
    release refrigerants from the appliance unless the maintenance, 
    service, or repair consists of adding refrigerant to the appliance. 
    Technician includes but is not limited to installers, contractor 
    employees, in-house service personnel, and in some cases, owners.
        Very-high-pressure appliance means an appliance that uses a 
    refrigerant with a critical temperature below 104 degrees Fahrenheit or 
    with a liquid phase saturation pressure above 305 psia at 104 degrees 
    Fahrenheit. This definition includes but is not limited to appliances 
    using R410A and B, R13, R23, and R503.
        3. Section 82.154 is amended by revising paragraphs (a), (b), (c), 
    (g), (h), and (m), and by adding paragraphs (o) and (p) to read as 
    follows:
    
    
    Sec. 82.154  Prohibitions.
    
        (a) Effective (30 days after publication of the final rule), no 
    person maintaining, servicing, repairing, or disposing of appliances 
    may knowingly vent or otherwise release into the environment any 
    refrigerant from such equipment. The knowing release of refrigerant 
    subsequent to its recovery from an appliance shall be considered a 
    violation of this prohibition. De minimis releases associated with good 
    faith attempts to recycle or recover refrigerants are not subject to 
    this prohibition. Releases shall be considered de minimis only if they 
    occur when:
        (1) The required practices set forth in Sec. 82.156 are observed, 
    recovery or recycling machines that meet the requirements set forth in 
    Sec. 82.158 are used, and the technician certification provisions set 
    forth in Sec. 82.161 are observed; or
        (2) The requirements set forth in subpart B of this part are 
    observed.
        (b) No person may open appliances except MVACs and MVAC-like 
    appliances for maintenance, service, or repair, and no person may 
    dispose of appliances except for small appliances, MVACs, and MVAC-like 
    appliances:
    * * * * *
        (c) No person may manufacture or import recycling or recovery 
    equipment for use during the maintenance, service, or repair of 
    appliances except MVACs and MVAC-like appliances, and no person may 
    manufacture or import recycling or recovery equipment for use during 
    the disposal of appliances except small appliances, MVACs, and MVAC-
    like appliances, unless the equipment is certified pursuant to 
    Sec. 82.158 (b) or (d), as applicable.
    * * * * *
        (g) No person may sell or offer for sale refrigerant consisting 
    wholly or in part of used refrigerant unless:
        (1) The refrigerant has been reclaimed as defined at Sec. 82.152;
        (2) The refrigerant was used only in an MVAC or MVAC-like appliance 
    and is to be used only in an MVAC or MVAC-like appliance; or
        (3) The refrigerant is contained in an appliance that is sold or 
    offered for sale together with the refrigerant.
        (h) No person may sell or offer for sale refrigerant consisting 
    wholly or in part of used refrigerant unless:
        (1) The refrigerant has been reclaimed by a person who has been 
    certified as a reclaimer pursuant to Sec. 82.164;
        (2) The refrigerant was used only in an MVAC or MVAC-like appliance 
    and is to be used only in an MVAC or MVAC-like appliance; or
        (3) The refrigerant is contained in an appliance that is sold or 
    offered for sale together with the refrigerant.
    * * * * *
        (m) No person may sell or distribute, or offer for sale or 
    distribution, any refrigerant to any person unless:
    * * * * *
        (o) No person may manufacture or import one-time expansion devices.
        (p) Recovery or recycling equipment certified or rated for use with 
    only one refrigerant may not be used to recover other refrigerants.
        4. Section 82.156 is amended by revising the introductory text of 
    paragraph (a) to read as follows, by removing paragraph (a)(5), by 
    revising Table 1 to read as follows, by revising paragraph (b) to read 
    as follows, and by redesignating paragraphs (i)(1), (i)(1)(i), 
    (i)(1)(ii) and (i)(1)(iii) as (i)(1)(i), (i)(1)(iii), (i)(1)(iv), and 
    (i)(1)(v), by adding a new paragraph (i)(1)(ii), and by revising newly 
    designated paragraphs (i)(1)(i) and (i)(1)(iii) to read as follows, by 
    redesignating paragraphs (i)(2), (i)(2)(i), and (i)(2)(ii) as 
    (i)(2)(i), (i)(2)(iii), and (i)(2)(iv), by adding a new paragraph 
    (i)(2)(ii), and by revising newly designated paragraph (i)(2)(i) to 
    read as follows, by redesignating paragraphs (i)(5), (i)(5)(i), 
    (i)(5)(ii), and (i)(5)(iii), as (i)(5)(i), (i)(5)(iii), (i)(5)(iv), and 
    (i)(5)(v), by adding a new paragraph (i)(5)(ii), and by revising newly 
    designated paragraph (i)(5)(i) to read as follows, by revising 
    paragraphs (i)(3), (i)(3)(i), (i)(3)(ii), and (i)(6) to read as 
    follows, and by replacing the phrase ``annual leak rate'' with ``leak 
    rate'' throughout:
    
    
    Sec. 82.156  Required Practices.
    
        (a) All persons disposing of appliances, except for small 
    appliances, MVACs, and MVAC-like appliances must evacuate the 
    refrigerant, including all the liquid refrigerant, in the entire unit 
    to a recovery or recycling machine certified pursuant to Sec. 82.158. 
    All persons opening appliances except for MVACs and MVAC-like 
    appliances for maintenance, service, or repair must evacuate the 
    refrigerant, including all the liquid refrigerant (except as provided 
    in paragraph (a)(2)(i)(B) of this section), in either the entire unit 
    or the part to be serviced (if the latter can be isolated) to a system 
    receiver (e.g., the remaining portions of the appliance, or a specific 
    vessel within the appliance) or a recovery or recycling machine 
    certified pursuant to Sec. 82.158. Certified technicians must verify 
    that the applicable level of evacuation has been reached in the 
    appliance or the part before it is opened.
    * * * * *
    
    [[Page 32091]]
    
    
    
                                 Table 1.--Required Levels of Evacuation for Appliances                             
                             [Except for small appliances, MVACs, and MVAC-like appliances]                         
    ----------------------------------------------------------------------------------------------------------------
                                                                      Inches of Hg vacuum (relative to standard     
                                                                       atmospheric pressure of 29.9 inches Hg)      
                                                                ----------------------------------------------------
                                                                 Using recovery                                     
                                                                  or recycling                                      
                         Type of appliance                          equipment        Using recovery or recycling    
                                                                  manufactured    equipment manufactured or imported
                                                                   or imported        on or after Nov. 15, 1993     
                                                                   before Nov.                                      
                                                                    15, 1993                                        
    ----------------------------------------------------------------------------------------------------------------
    Very high-pressure appliance...............................               0  0.                                 
    Higher-pressure appliance, or isolated component of such                  0  0.                                 
     appliance, normally containing less than 200 pounds of                                                         
     refrigerant.                                                                                                   
    Higher-pressure appliance, or isolated component of such                  4  10.                                
     appliance, normally containing 200 pounds or more of                                                           
     refrigerant.                                                                                                   
    High-pressure appliance, or isolated component of such                    4  10.                                
     appliance, normally containing less than 200 pounds of                                                         
     refrigerant.                                                                                                   
    High-pressure appliance, or isolated component of such                    4  15.                                
     appliance, normally containing 200 pounds or more of                                                           
     refrigerant.                                                                                                   
    Low-pressure appliance.....................................              25  25 mm Hg absolute.                 
    ----------------------------------------------------------------------------------------------------------------
    
    * * * * *
        (b) All persons opening appliances except for small appliances, 
    MVACs, and MVAC-like appliances for maintenance, service, or repair and 
    all persons disposing of appliances except small appliances, MVACs, and 
    MVAC-like appliances must have at least one piece of certified, self-
    contained recovery or recycling equipment available at their place of 
    business. Persons who maintain, service, repair, or dispose of only 
    appliances that they own and that contain pump-out units are exempt 
    from this requirement. This exemption does not relieve such persons 
    from other applicable requirements of Sec. 82.156.
    * * * * *
        (i)(1)(i) Owners or operators of commercial refrigeration equipment 
    normally containing more than 50 pounds of refrigerant and commissioned 
    before or during 1992 must have leaks repaired in accordance with 
    paragraph (i)(9) of this section if the leak rate of the appliance 
    exceeds 15 percent per year, except as described in paragraphs (i)(6), 
    (i)(8), and (i)(10) of this section and paragraphs (i)(1)(iii), 
    (i)(1)(iv), and (i)(1)(v) of this section. Repairs must bring the leak 
    rate to or below 15 percent per year.
        (ii) Owners or operators of commercial refrigeration equipment 
    normally containing more than 50 pounds of refrigerant and commissioned 
    after 1992 must have leaks repaired in accordance with paragraph (i)(9) 
    of this section if the leak rate of the appliance exceeds 10 percent 
    per year, except as described in paragraphs (i)(6), (i)(8), and (i)(10) 
    of this section and paragraphs (i)(1)(iii), (i)(1)(iv), and (i)(1)(v) 
    of this section. Repairs must bring the leak rate to or below 10 
    percent per year.
        (iii) If the owners or operators of federally-owned commercial 
    refrigeration appliances determine that the leaks cannot be repaired in 
    accordance with paragraph (i)(9) of this section and that an extension 
    in accordance with the requirements discussed in this paragraph 
    (i)(1)(iii) of this section applies, they must document all repair 
    efforts and notify EPA of the reason for their inability to comply 
    within the 30-day repair period in accordance with section 82.166(n). 
    Such notification must be made within 30 days of discovering the leaks. 
    EPA will determine if the extension requested in accordance with the 
    requirements discussed in this paragraph (i)(1)(iii) of this section is 
    justified. If the extension is not justified, EPA will notify the 
    owner/operator within 30 days of receipt of the notification.
    * * * * *
        (2)(i) The owners or operators of industrial process refrigeration 
    equipment normally containing more than 50 pounds of refrigerant must 
    have leaks repaired in accordance with paragraph (i)(9) of this section 
    if the leak rate of the appliance exceeds 20 percent per year, except 
    as described in paragraphs (i)(6), (i)(7), and (i)(10) of this section, 
    and paragraphs (i)(2)(ii), (i)(2)(iii) and (i)(2)(iv) of this section. 
    Repairs must bring the leak rate to or below 20 percent per year. If 
    the owners or operators of the industrial process refrigeration 
    equipment determine that the leak rate cannot be brought to or below 20 
    percent per year within 30 days (or 120 days, where an industrial 
    process shutdown in accordance with paragraph (i)(2)(iv) of this 
    section is required) and in accordance with paragraph (i)(9) of this 
    section, and that an extension in accordance with the requirements 
    discussed in this paragraph applies, the owners or operators of the 
    appliance must document all repair efforts and notify EPA of the reason 
    for the inability in accordance with Sec. 82.166(n). Such notification 
    must be made within 30 days of making the determination. Owners or 
    operators who obtain an extension pursuant to this section or elect to 
    utilize the additional time provided in paragraph (i)(2)(iii) of this 
    section must conduct all necessary leak repairs, if any, that can be 
    performed within 30 days of discovering the leaks.
        (ii) Notwithstanding the provisions of paragraph (i)(2)(i) of this 
    section, a maximum allowable leak rate of 35 percent per year shall 
    apply to industrial process refrigeration systems meeting all of the 
    following conditions:
        (A) The refrigeration system is custom-built;
        (B) The refrigeration system has an open-drive compressor;
        (C) The refrigeration system was built in 1992 or before; and
        (D) The system is direct-expansion (contains a single, primary 
    refrigerant loop).
    * * * * *
        (3) Owners or operators of federally-owned commercial refrigeration
    
    [[Page 32092]]
    
    equipment or of federally-owned comfort cooling appliances who are 
    granted additional time under paragraphs (i)(1) or (i)(5) of this 
    section, and owners or operators of industrial process refrigeration 
    equipment, must have repairs performed in a manner that sound 
    professional judgment indicates will bring the leak rate below the 
    applicable allowable leak rate. When an industrial process shutdown has 
    occurred or when repairs have been made while an appliance is 
    mothballed, the owners or operators shall conduct an initial 
    verification test at the conclusion of the repairs and a follow-up 
    verification test. The follow-up verification test shall be conducted 
    within 30 days of completing the repairs or within 30 days of bringing 
    the appliance back on-line, if taken off-line, but no sooner than when 
    the appliance has achieved normal operating characteristics and 
    conditions. When repairs have been conducted without an industrial 
    process shutdown or system mothballing, an initial verification test 
    shall be conducted at the conclusion of the repairs, and a follow-up 
    verification test shall be conducted within 30 days of the initial 
    verification test. In all cases, the follow-up verification test shall 
    be conducted at normal operating characteristics and conditions, unless 
    sound professional judgment indicates that tests performed at normal 
    operating characteristics and conditions will produce less reliable 
    results, in which case the follow-up verification test shall be 
    conducted at or near the normal operating pressure where practicable, 
    and at or near the normal operating temperature where practicable.
        (i) If the owners or operators of federally-owned commercial 
    refrigeration equipment or of federally-owned comfort cooling 
    appliances who are granted additional time under paragraphs (i)(1) or 
    (i)(5) of this section take the appliances off-line, or if owners or 
    operators of industrial process refrigeration equipment take the 
    appliances off-line, they cannot bring the appliances back on-line 
    until an initial verification test indicates that the repairs 
    undertaken in accordance with paragraphs (i)(1) (i), (ii), (iii), (iv), 
    or (v), or (i)(2) (i), (ii), or (iii) or (5) (i), (ii), and (iii) of 
    this section have been successfully completed, demonstrating the leak 
    or leaks are repaired. The owners or operators of the industrial 
    process refrigeration equipment, federally-owned commercial 
    refrigeration equipment, or federally-owned comfort cooling appliances 
    are exempted from this requirement only where the owners or operators 
    will retrofit or retire the industrial process refrigeration equipment, 
    federally-owned commercial refrigeration equipment, or federally-owned 
    comfort cooling appliances in accordance with paragraph (i)(6) of this 
    section. Under this exemption, the owner or operators may bring the 
    industrial process refrigeration equipment, federally-owned commercial 
    refrigeration equipment, or federally-owned comfort cooling appliances 
    back on-line without successful completion of an initial verification 
    test.
        (ii) If the follow-up verification test indicates that the repairs 
    to industrial process refrigeration equipment, federally-owned 
    commercial refrigeration equipment, or federally-owned comfort cooling 
    appliances have not been successful, the owner must retrofit or retire 
    the equipment in accordance with paragraph (i)(6) and any such longer 
    time period as may apply under paragraphs (i)(7) (i), (ii) and (iii) or 
    (i)(8) (i) and (ii) of this section. The owners and operators of the 
    industrial process refrigeration equipment, federally-owned commercial 
    refrigeration equipment, or federally-owned comfort cooling appliances 
    are relieved of this requirement if the conditions of paragraphs 
    (i)(3)(iv) and/or (i)(3)(v) of this section are met.
    * * * * *
        (5)(i) Owners or operators of appliances normally containing more 
    than 50 pounds of refrigerant, manufactured before or during 1992, and 
    not covered by paragraphs (i)(1) or (i)(2) of this section must have 
    leaks repaired in accordance with paragraph (i)(9) of this section if 
    the leak rate of the appliance exceeds 10 percent per year, except as 
    provided in paragraphs (i)(5)(iii), (i)(5)(iv), and (i)(5)(v) of this 
    section. Repairs must bring the leak rate to or below 10 percent per 
    year.
        (5)(ii) Owners or operators of appliances normally containing more 
    than 50 pounds of refrigerant, manufactured after 1992, and not covered 
    by paragraphs (i)(1) or (i)(2) of this section must have leaks repaired 
    in accordance with paragraph (i)(9) of this section if the leak rate of 
    the appliance exceeds 5 percent per year, except as provided in 
    paragraphs (i)(5)(iii), (i)(5)(iv), and (i)(5)(v) of this section. 
    Repairs must bring the leak rate to or below 5 percent per year.
    * * * * *
        (6) Owners or operators are not required to repair leaks as 
    provided in paragraphs (i)(1), (i)(2), and (i)(5) of this section if, 
    within 30 days of discovering the exceedance of the applicable 
    allowable leak rate, or within 30 days of a failed follow-up 
    verification test, or after making good faith efforts to repair the 
    leaks as described in paragraph (i)(6)(i) of this section, they develop 
    a one-year retrofit or retirement plan for the leaking appliance. 
    Owners or operators who retrofit the appliance must use a refrigerant 
    with a lower ozone-depleting potential than the previous refrigerant 
    and must include such a change in the retrofit plan. Owners or 
    operators who retire and replace the appliance must replace the 
    appliance with an appliance that uses a refrigerant with a lower ozone-
    depleting potential and must include such a change in the retirement 
    plan. The retrofit or retirement plan (or a legible copy) must be kept 
    at the site of the appliance. The original plan must be made available 
    for EPA inspection upon request. The plan must be dated and all work 
    performed in accordance with the plan must be completed within one year 
    of the plan's date, except as described in paragraphs (i)(6)(i), 
    (i)(7), and (i)(8) of this section. Owners or operators are temporarily 
    relieved of this obligation if the appliance has undergone system 
    mothballing as defined in Sec. 82.152.
        (i) If the owner or operator has made good faith efforts to repair 
    leaks from the appliance in accordance with paragraphs (i)(1), (i)(2), 
    or (i)(5) of this section, and has decided, before completing a follow-
    up verification test, to retrofit or retire the appliance in accordance 
    with paragraph (i)(6) of this section, the owner or operator must 
    develop a retrofit or retirement plan within 30 days of the decision to 
    retrofit or retire the appliance. The owner or operator must retrofit 
    or retire the appliance within one year and 30 days of when the owner 
    or operator discovered that the leak rate exceeded the applicable 
    allowable leak rate, except as provided in paragraphs (i)(7) and (i)(8) 
    of this section.
    * * * * *
        5. Section 82.158 is amended by revising Table 2 and Table 3, by 
    removing paragraphs (f) and (g), and by redesignating paragraphs (h) 
    through (m) as (f) through (k) to read as follows:
    
    
    Sec. 82.158  Standards for recycling and recovery equipment.
    
    * * * * *
    
    [[Page 32093]]
    
    
    
      Table 2.--Levels of Evacuation Which Must Be Achieved by Recovery or  
    Recycling Equipment Intended for Use With Appliances \1\ Manufactured on
                           or After November 15, 1993                       
    ------------------------------------------------------------------------
                                                                 Inches of  
                                                                  vacuum    
                                                               (relative to 
       Type of appliance with which recovery or recycling        standard   
                 machine is intended to be used                 atmospheric 
                                                                pressure of 
                                                              29.9 inches of
                                                                    Hg)     
    ------------------------------------------------------------------------
    Very high-pressure appliance............................               0
    Higher-pressure appliance or isolated component of such                 
     appliance, normally containing less than 200 pounds of                 
     refrigerant............................................               0
    Higher-pressure appliance, or isolated component of such                
     appliance, normally containing 200 pounds or more of                   
     refrigerant............................................              10
    High-pressure appliance, or isolated component of such                  
     appliance, normally containing less than 200 pounds of                 
     refrigerant............................................              10
    High-pressure appliance, or isolated component of such                  
     appliance, normally containing 200 pounds or more of                   
     refrigerant............................................              15
    Low-pressure appliance..................................          \2\ 25
    ------------------------------------------------------------------------
    \1\ Except for small appliances, MVACs, and MVAC-like appliances.       
    \2\ mm Hg absolute.                                                     
    
        The vacuums specified in inches of Hg vacuum must be achieved 
    relative to an atmospheric pressure of 29.9 inches of Hg absolute.
    * * * * *
    
      Table 3.--Levels of Evacuation Which Must Be Achieved by Recovery or  
      Recycling Equipment Intended for Use With Appliances \1\ Manufactured 
                            Before November 15, 1993                        
    ------------------------------------------------------------------------
                                                                 Inches of  
                                                                  vacuum    
                                                               (relative to 
       Type of appliance with which recovery or recycling        standard   
                 machine is intended to be used                 atmospheric 
                                                                pressure of 
                                                              29.9 inches of
                                                                    Hg)     
    ------------------------------------------------------------------------
    Very high-pressure appliance............................               0
    Higher-pressure appliance or isolated component of such                 
     appliance, normally containing less than 200 pounds of                 
     refrigerant............................................               0
    Higher-pressure appliance, or isolated component of such                
     appliance, normally containing 200 pounds or more of                   
     refrigerant............................................               4
    High-pressure appliance, or isolated component of such                  
     appliance, normally containing less than 200 pounds of                 
     refrigerant............................................               4
    High-pressure appliance, or isolated component of such                  
     appliance, normally containing 200 pounds or more of                   
     refrigerant............................................               4
    Low-pressure appliance..................................          \2\ 25
    ------------------------------------------------------------------------
    \1\ Except for small appliances, MVACs, and MVAC-like appliances.       
    \2\ mm Hg absolute.                                                     
    
        The vacuums specified in inches of Hg vacuum must be achieved 
    relative to an atmospheric pressure of 29.9 inches of Hg absolute.
    * * * * *
        6. Section 82.161 is amended by revising paragraph (a)(2) as 
    follows:
    
    
    Sec. 82.161  Technician Certification.
    
        (a) * * *
        (2) Technicians who maintain, service, or repair high-, higher-, or 
    very high-pressure appliances, except small appliances, MVACs, and 
    MVAC-like appliances, or dispose of high-, higher-, or very high-
    pressure appliances, except small appliances, MVACs, and MVAC-like 
    appliances, must be properly certified as Type II technicians.
    * * * * *
        7. Section 82.164 is amended by revising the introductory text and 
    paragraphs (a), (b), and (e)(3) to read as follows:
    
    
    Sec. 82.164  Reclaimer Certification.
    
        Effective [INSERT DATE 30 DAYS AFTER PUBLICATION OF THE FINAL RULE] 
    all persons reclaiming used refrigerant for sale to a new owner, except 
    for persons who properly certified under this section prior to [INSERT 
    DATE 30 DAYS AFTER PUBLICATION OF THE FINAL RULE] must certify to the 
    Administrator that such person will:
        (a) Reprocess refrigerant to all of the specifications in appendix 
    A of this Subpart (based on ARI Standard 700-1995, Specification for 
    Fluorocarbons and Other Refrigerants) that are applicable to that 
    refrigerant;
        (b) Verify that the refrigerant meets these specifications using 
    the analytical methodology prescribed in appendix A;
    * * * * *
        (e) * * *
        (3) The owner or a responsible officer of the reclaimer must sign 
    the certification stating that the refrigerant will be reprocessed to 
    all of the specifications in appendix A of this Subpart (based on ARI 
    Standard 700-1995, Specification for Fluorocarbons and Other 
    Refrigerants) that are applicable to that refrigerant, that the 
    refrigerant's conformance to these specifications will be verified 
    using the analytical methodology prescribed in appendix A, that no more 
    than 1.5 percent of the refrigerant will be released during the 
    reclamation process, that wastes from the reclamation process will be 
    properly disposed of, and that the information given is true and 
    correct. The certification should be sent to the following address: 
    Section 608 Recycling Program Manager, Reclaimer Certification, 
    Stratospheric Protection Division (6205J), U.S. Environmental 
    Protection Agency, 401 M Street, SW., Washington, DC 20460.
    * * * * *
        8. Section 82.166 is amended by revising paragraphs (a), (b), (n), 
    (o)(4), (o)(7), (o)(8), and (o)(10) to read as follows:
    
    [[Page 32094]]
    
    Sec. 82.166  Reporting and recordkeeping requirements.
    
        (a) All persons who sell or distribute any refrigerant must retain 
    invoices that indicate the name of the purchaser, the date of sale, and 
    the quantity of refrigerant purchased.
        (b) Purchasers of refrigerant who employ certified technicians may 
    provide evidence that at least one technician is properly certified to 
    the wholesaler who sells them refrigerant; the wholesaler must then 
    keep this information on file and may sell refrigerant to the purchaser 
    or his authorized representative even if such purchaser or authorized 
    representative is not a properly certified technician. In such cases, 
    the purchaser must notify the wholesaler in the event that the 
    purchaser no longer employs at least one properly certified technician. 
    The wholesaler is then prohibited from selling refrigerants to the 
    purchaser until such time as the purchaser employs at least one 
    properly certified technician. At that time, the purchaser must provide 
    new evidence that at least one technician is properly certified.
    * * * * *
        (n) The owners or operators of appliances must maintain on-site and 
    report to EPA at the address listed in Sec. 82.160 the information 
    specified in paragraphs (n)(1), (n)(2), and (n)(3) of this section, 
    within the time lines specified under Sec. 82.156 (i)(1), (i)(2), 
    (i)(3) and (i)(5) where such reporting and recordkeeping is required. 
    This information must be relevant to the affected appliance.
        (1) An initial report to EPA under Sec. 82.156(i)(1)(iii), 
    (i)(2)(i), or (i)(5)(iii) regarding why more than 30 days are needed to 
    complete repairs must include: Identification of the facility; the leak 
    rate; the method used to determine the leak rate and full charge; the 
    date a leak rate above the applicable allowable leak rate was 
    discovered; the location of leaks(s) to the extent determined to date; 
    any repair work that has been completed thus far and the date that work 
    was completed; the reasons why more than 30 days are needed to complete 
    the work and an estimate of when the work will be completed. If changes 
    from the original estimate of when work will be completed result in 
    extending the completion date from the date submitted to EPA, the 
    reasons for these changes must be documented and submitted to EPA 
    within 30 days of discovering the need for such a change.
        (2) If the owners or operators intend to establish that the 
    appliance's leak rate does not exceed the applicable allowable leak 
    rate in accordance with Sec. 82.156(i)(3)(v), the owner or operator 
    must submit a plan to fix other outstanding leaks for which repairs are 
    planned but not yet completed to achieve a rate below the applicable 
    allowable leak rate. A plan to fix other outstanding leaks in 
    accordance with Sec. 82.156(i)(3)(v) must include the following 
    information: the identification of the facility; the leak rate; the 
    method used to determine the leak rate and full charge; the date a leak 
    rate above the applicable allowable leak rate was discovered; the 
    location of leaks(s) to the extent determined to date; and any repair 
    work that has been completed thus far, including the date that work was 
    completed. Upon completion of the repair efforts described in the plan, 
    a second report must be submitted that includes the date the owner or 
    operator submitted the initial report concerning the need for 
    additional time beyond the 30 days and notification of the owner or 
    operator's determination that the leak rate no longer exceeds the 
    applicable allowable leak rate. This second report must be submitted 
    within 30 days of determining that the leak rate no longer exceeds the 
    applicable allowable leak rate.
        (3) Owners or operators must maintain records of the dates and 
    types of all initial and follow-up verification tests performed under 
    Sec. 82.156(i)(3) and the test results for all follow-up verification 
    tests. Owners or operators must submit this information to EPA within 
    30 days after conducting each test where required under Sec. 82.156 
    (i)(1), (i)(2), (i)(3) and (i)(5). These reports must also include: 
    identification of the facility; the leak rate; the method used to 
    determine the leak rate and full charge; the date a leak rate above the 
    applicable allowable leak rate was discovered; the location of leaks(s) 
    to the extent determined to date; and any repair work that has been 
    completed thus far and the date that work was completed.
    * * * * *
        (o) * * *
        (4) The date a leak rate above the applicable allowable rate was 
    discovered.
    * * * * *
        (7) A plan to complete the retrofit or retirement of the system;
        (8) The reasons why more than one year is necessary to retrofit or 
    retire the system;
    * * * * *
        (10) An estimate of when retrofit or retirement work will be 
    completed. If the estimated date of completion changes from the 
    original estimate and results in extending the date of completion, the 
    owner or operator must submit to EPA the new estimated date of 
    completion and documentation of the reason for the change within 30 
    days of discovering the need for the change, and must retain a dated 
    copy of this submission.
    * * * * *
        (q) Owners or operators who choose to determine the full charge, as 
    defined in Sec. 82.152, of an affected appliance by using an 
    established range or by using that method in combination with other 
    methods for determining the full charge must maintain the following 
    information:
    * * * * *
        9. Appendix A to subpart F is revised to read as follows:
    
    Appendix A--Specifications for Fluorocarbons and Other Refrigerants
    
        This appendix is based on Air-Conditioning and Refrigeration 
    Institute Standard 700-1995.
    Section 1. Purpose
        1.1  Purpose. The purpose of this standard is to evaluate and 
    accept/reject refrigerants regardless of source (new, reclaimed and/or 
    repackaged) for use in new and existing refrigeration and air-
    conditioning products.
        1.1.1  Intent. This standard is intended for the guidance of the 
    industry including manufacturers, refrigerant reclaimers, repackagers, 
    distributors, installers, servicemen, contractors and for consumers.
        1.1.2  Review and Amendment. This standard is subject to review and 
    amendment as the technology advances.
    Section 2. Scope
        2.1  Scope. This standard specifies acceptable levels of 
    contaminants (purity requirements) for various fluorocarbon and other 
    refrigerants regardless of source and lists acceptable test methods. 
    These refrigerants are R11; R12; R13; R22; R23; R32; R113; R114; R123; 
    R124; R125; R134a; R143a; R401A; R401B; R402A; R402B; R404A; R405A; 
    R406A; R407A; R407B; R407C; R408A; R409A; R410A; R410B; R411A; R411B; 
    R412A; R500; R502; R503; R507; R508; and R509 as referenced in the 
    ANSI/ASHRAE Standard 34-1992. (American Society of Heating, 
    Refrigerating and Air Conditioning Engineers, Inc., Standard 34-1992). 
    Copies may be obtained from ASHRAE Publications Sales, 1791 Tullie 
    Circle, NE, Atlanta, GA 30329. Copies may also be inspected at Public 
    Docket No. A-92-01, Waterside Mall (Ground Floor) Environmental 
    Protection Agency, 401 M Street, SW, Washington, DC in room M-1500.
    
    [[Page 32095]]
    
    Section 3. Definitions
        3.1  ``Shall,'' ``Should,'' ``Recommended,'' or ``It Is 
    Recommended.'' ``Shall,'' ``should,'' ``recommended,'' or ``it is 
    recommended'' shall be interpreted as follows:
        3.1.1  Shall. Where ``shall'' or ``shall not'' is used for a 
    provision specified, that provision is mandatory if compliance with the 
    standard is claimed.
        3.1.2  Should, Recommended, or It is Recommended. ``Should ``, 
    ``recommended'', or ``it is recommended'' is used to indicate 
    provisions which are not mandatory but which are desirable as good 
    practice.
    Section 4. Characterization of Refrigerants and Contaminants
        4.1  Characterization. Characterization of refrigerants and 
    contaminants addressed are listed in the following general 
    classifications:
        4.1.1  Characterization
        a. Gas Chromatography
        b. Boiling point and boiling point range
        4.1.2  Contaminants
        a. Water
        b. Chloride
        c. Acidity
        d. High boiling residue
        e. Particulates/solids
        f. Non-condensables
        g. Impurities including other refrigerants
    Section 5. Sampling, Summary of Test Methods and Maximum Permissible 
    Contaminant Levels
        5.1  Referee Test. The referee test methods for the various 
    contaminants are summarized in the following paragraphs. Detailed test 
    procedures are included in Appendix-C to ARI Standard 700-95: 
    Analytical Procedures for ARI Standard 700-95, 1995, Air-Conditioning 
    and Refrigeration Institute. Appendix C to ARI Standard 700-95 is 
    incorporated by reference. [This incorporation by reference was 
    approved by the Director of the Federal Register in accordance with 5 
    U.S.C. 552(a) and 1 CFR part 51. Copies may be obtained from the Air-
    Conditioning and Refrigeration Institute, 4301 North Fairfax Drive, 
    Arlington, Virginia 22203. Copies may also be inspected at Public 
    Docket No. A-92-01, Waterside Mall (Ground Floor) Environmental 
    Protection Agency, 401 M Street, SW, Washington, DC in room M-1500 or 
    at the Office of the Federal Register, 800 North Capitol Street, NW, 
    Suite 700, Washington, DC.] If alternative test methods are employed, 
    the user must be able to demonstrate that they produce results 
    equivalent to the specified referee method.
        5.2  Refrigerant Sampling.
        5.2.1  Sampling Precautions. Special precautions should be taken to 
    assure that representative samples are obtained for analysis. Sampling 
    shall be done by trained laboratory personnel following accepted 
    sampling and safety procedures.
        5.2.2  Gas Phase Sample. A gas phase sample shall be obtained for 
    determining the non-condensables. Since non-condensable gases, if 
    present, will concentrate in the vapor phase of the refrigerant, care 
    must be exercised to eliminate introduction of air during the sample 
    transfer. Purging is not an acceptable procedure for a gas phase sample 
    since it may introduce a foreign product. Since R11, R113, and R123 
    have normal boiling points at or above room temperature, non-
    condensable determination is not required for these refrigerants.
        5.2.2.1  Connection. The sample cylinder shall be connected to an 
    evacuated gas sampling bulb by means of a manifold. The manifold should 
    have a valve arrangement that facilitates evacuation of all connecting 
    tubing leading to the sampling bulb.
        5.2.2.2  Equalizing Pressures. After the manifold has been 
    evacuated, close the valve to the pump and open the valve on the 
    system. Allow the pressure to equilibrate and close valves.
        5.2.3  Liquid Phase Sample. A liquid phase sample is required for 
    all tests listed in this standard except the test for non-condensables.
        5.2.3.1  Preparation. Place a clean, empty sample cylinder with the 
    valve open in an oven at 110 deg. C (230 deg. F) for one hour. Remove 
    it from the oven while hot, immediately connect to an evacuation system 
    and evacuate to less than 1 mm mercury (1000 microns). Close the valve 
    and allow it to cool. Weigh the empty cylinder.
        5.2.3.2  Manifolding. The valve and lines from the unit to be 
    sampled shall be clean and dry. The cylinder shall be connected to an 
    evacuated gas sampling cylinder by means of a manifold. The manifold 
    should have a valve arrangement that facilitates evacuation of all 
    connecting tubing leading to the sampling cylinder.
        5.2.3.3  Liquid Sampling. After the manifold has been evacuated, 
    close the valve to the pump and open the valve on the system. Take the 
    sample as a liquid by chilling the sample cylinder slightly. Accurate 
    analysis requires that the sample container be filled to at least 60% 
    by volume, however under no circumstances should the cylinder be filled 
    to more than 80% by volume. This can be accomplished by weighing the 
    empty cylinder and then the cylinder with refrigerant. When the desired 
    amount of refrigerant has been collected, close the valve(s) and 
    disconnect the sample cylinder immediately.
        5.2.3.4  Record Weight. Check the sample cylinder for leaks and 
    record the gross weight.
        5.3  Refrigerant Characterization.
        5.3.1  Primary Method. The primary method shall be gas 
    chromatography (GC) as described in Appendix-C to ARI Standard 700-95. 
    The chromatogram of the sample shall be compared to known standards.
        5.3.2  Alternative Method. Determination of the boiling point and 
    boiling point range is an acceptable alternative test method which can 
    be used to characterize refrigerants. The test method shall be that 
    described in the Federal Specification for ``Fluorocarbon 
    Refrigerants,'' BB-F-1421 B, dated March 5, 1982, section 4.4.3.
        5.3.3  Required Values. The required values for boiling point and 
    boiling point range are given in Table 1A, Physical Properties of 
    Single Component Refrigerants; Table 1B, Physical Properties of 
    Zeotropic Blends (400 Series Refrigerants); and Table 1C, Physical 
    Properties of Azeotropic Blends (500 Series Refrigerants).
        5.4  Water Content.
        5.4.1  Method. The Coulometric Karl Fischer Titration shall be the 
    primary test method for determining the water content of refrigerants. 
    This method is described in Appendix-C to ARI Standard 700-95. This 
    method can be used for refrigerants that are either a liquid or a gas 
    at room temperature, including refrigerants 11, 113, and 123. For all 
    refrigerants, the sample for water analysis shall be taken from the 
    liquid phase of the container to be tested. Proper operation of the 
    analytical method requires special equipment and an experienced 
    operator. The precision of the results is excellent if proper sampling 
    and handling procedures are followed. Refrigerants containing a colored 
    dye can be successfully analyzed for water using this method.
        5.4.2  Limits. The value for water content shall be expressed as 
    parts per million by weight and shall not exceed the maximum specified 
    (see Tables 1A, 1B, and 1C).
        5.5  Chloride. The refrigerant shall be tested for chloride as an 
    indication of the presence of hydrochloric acid and/or metal chlorides. 
    The recommended procedure is intended for use with new or reclaimed 
    refrigerants. Significant
    
    [[Page 32096]]
    
    amounts of oil may interfere with the results by indicating a failure 
    in the absence of chloride.
        5.5.1  Method. The test method shall be that described in Appendix-
    C to ARI Standard 700-95. The test will show noticeable turbidity at 
    chloride levels of about 3 ppm by weight or higher.
        5.5.2  Turbidity. The results of the test shall not exhibit any 
    sign of turbidity. Report the results as ``pass'' or ``fail.''
        5.6  Acidity.
        5.6.1  Method. The acidity test uses the titration principle to 
    detect any compound that is highly soluble in water and ionizes as an 
    acid. The test method shall be that described in Appendix-C to ARI 
    Standard 700-95. This test may not be suitable for determination of 
    high molecular weight organic acids; however these acids will be found 
    in the high boiling residue test outlined in 5.7. The test requires a 
    100 to 120 gram sample and has a detection limit of 0.1 ppm by weight 
    calculated as HCl.
        5.6.2  Limits. The maximum permissible acidity is 1 ppm by weight 
    as HCl.
        5.7  High Boiling Residue.
        5.7.1  Method. High boiling residue shall be determined by 
    measuring the residue of a standard volume of refrigerant after 
    evaporation. The refrigerant sample shall be evaporated at room 
    temperature or at a temperature 45 deg.C (115 deg.F) for all 
    refrigerants, except R113 which shall be evaporated at 60 deg.C 
    (140 deg.F), using a Goetz bulb as specified in Appendix-C to ARI 
    Standard 700-95. Oils and/or organic acids will be captured by this 
    method.
        5.7.2  Limits. The value for high boiling residue shall be 
    expressed as a percentage by volume and shall not exceed the maximum 
    percent specified (see Tables 1A, 1B, and 1C). An alternative 
    gravimetric method is described in Appendix-C to ARI Standard 700-95.
        5.8  Method of Tests for Particulates and Solids.
        5.8.1  Method. A measured amount of sample is evaporated from a 
    Goetz bulb under controlled temperature conditions. The particulates/
    solids shall be determined by visual examination of the Goetz bulb 
    prior to the evaporation of refrigerant. Presence of dirt, rust or 
    other particulate contamination is reported as ``fail.'' For details of 
    this test method, refer to Part 3 of Appendix-C to ARI Standard 700-95.
        5.9  Non-Condensables.
        5.9.1  Sample. A vapor phase sample shall be used for determination 
    of non-condensables. Non-condensable gases consist primarily of air 
    accumulated in the vapor phase of refrigerants. The solubility of air 
    in the refrigerants liquid phase is extremely low and air is not 
    significant as a liquid phase contaminant. The presence of non-
    condensable gases may reflect poor quality control in transferring 
    refrigerants to storage tanks and cylinders.
        5.9.2  Method. The test method shall be gas chromatography with a 
    thermal conductivity detector as described in Appendix-C to ARI 
    Standard 700-95.
        5.9.3  Limit. The maximum level of non-condensables in the vapor 
    phase of a refrigerant in a container shall not exceed 1.5% by volume 
    (see Tables 1A, 1B, and 1C).
        5.10  Impurities, including Other Refrigerants.
        5.10.1  Method. The amount of other impurities including other 
    refrigerants in the subject refrigerant shall be determined by gas 
    chromatography as described in Appendix-C to ARI Standard 700-95.
        5.10.2  Limit. The subject refrigerant shall not contain more than 
    0.5% by weight of impurities including other refrigerants (see Tables 
    1A, 1B, and 1C).
    Section 6. Reporting Procedure
        6.1  Reporting Procedure. The source (manufacturer, reclaimer or 
    repackager) of the packaged refrigerant shall be identified. The 
    refrigerant shall be identified by its accepted refrigerant number and/
    or its chemical name. Maximum permissible levels of contaminants are 
    shown in Tables 1A, 1B, and 1C. Test results shall be tabulated in a 
    like manner.
    
    [[Page 32097]]
    
    
    
                                                                                         Table 1A.--Physical Properties of Single Component Refrigerants                                                                                    
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
                                                                      Reference                                                                                                                                                             
                                                Reporting units      (subclause)      R11         R12         R13         R22         R23         R32        R113        R114        R123        R124        R125        R134a       R143a  
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
    Characteristics*:                                                                                                                                                                                                                       
        Boiling Point*...................   deg.F @ 1.00 atm.......  ...........        74.9       -21.6      -114.6       -41.4      -115.7       -61.1       117.6        38.8        82.6        12.2       -55.3       -15.1       -52.6
                                            deg.C @ 1.00 atm.......  ...........        23.8       -29.8       -81.4       -40.8       -82.1       -51.7        47.6         3.8        27.9       -11.0       -48.5       -26.2       -47.0
        Boiling Point Range*.............  K.......................  ...........         0.3         0.3         0.5         0.3         0.5         0.3         0.3         0.3         0.3         0.3         0.3         0.3         0.3
        Typical Isomer Content...........  by weight...............  ...........  ..........  ..........  ..........  ..........  ..........  ..........        0-1%       0-30%        0-8%        0-5%         N/A  0-5000 ppm   0-100 ppm
                                                                                                                                                               R113a      R-114a       R123a      R-124a                   R-134       R-143
    Vapor Phase Contaminants:                                                                                                                                                                                                               
        Air and other non-condensables...  % by volume @ 25  deg.C.          5.9       N/A**         1.5         1.5         1.5         1.5         1.5       N/A**         1.5       N/A**         1.5         1.5         1.5         1.5
    Liquid Phase Contaminants:                                                                                                                                                                                                              
        Water............................  ppm by weight...........          5.4          20          10          10          10          10          10          20          10          20          10          10          10          10
        All other impurities including     % by weight.............          5.1        0.50        0.50        0.50        0.50        0.50        0.50        0.50        0.50        0.50        0.50        0.50        0.50        0.50
         refrigerants.                                                                                                                                                                                                                      
        High boiling residue.............  % by volume.............          5.7        0.01        0.01        0.05        0.01        0.01        0.01        0.03        0.01        0.01        0.01        0.01        0.01        0.01
        Particulates/solids..............  Visually clean to pass..          5.8        pass        pass        pass        pass        pass        pass        pass        pass        pass        pass        pass        pass        pass
        Acidity..........................  ppm by weight...........          5.6         1.0         1.0         1.0         1.0         1.0         1.0         1.0         1.0         1.0         1.0         1.0         1.0         1.0
        Chlorides***.....................  No visible turbidity....          5.5        pass        pass        pass        pass        pass        pass        pass        pass        pass        pass        pass        pass        pass
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
    * Boiling points and boiling point ranges, although not required, are provided for informational purposes.                                                                                                                              
    ** Since R11, R13, and R123 have normal boiling points at or above room temperature, non-condensable determinations are not required for these refrigerants.                                                                            
    *** Recognized chloride level for pass/fail is 3 ppm.                                                                                                                                                                                   
    
    
                                                                                  Table 1B.--Physical Properties of Zeotropic Blends (400 Series Refrigerants)                                                                              
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
                                                           Reference                                                                                                                                                                        
                                     Reporting units      (subclause)           R401A              R401B              R402A             R402B             R404A             R405A             R406A             R407A             R407B     
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
    Characteristics *                                                                                                                                                                                                                       
        Refrigerant Components....  .................  .................  R22/152a/124.....  R22/152a/124.....  R125/290/22.....  125/290/22......  R125/143a/134a..  R22/152a/142b/    R22/600a/142b...  R32/125/134a....  R32/125/134a.   
                                                                                                                                                                       C318.                                                                
        Nominal Comp, weight %....  .................  .................  53/13/34.........  61/11/28.........  60/2/38.........  38/2/60.........  44/52/4.........  45/7/5.5/42.5...  55/4/41.........  20/40/40........  10/70/20.       
        Allowable Comp, weight %..  .................  .................  51-54/11.5-13.5/   59-63/9.5-11.5/27- 58-62/1-3/36-40.  36-40/1-3/58-62.  42-46/51-53/2-6.  43-47/6-8/4.5-    53-57/3-5/40-42.  19-21/38-42/38-   9-11/68-72/18-  
                                                                           33-35.             29.                                                                      6.5/40.5-44.5.                      42.               22.            
        Boiling Point *...........   deg.F @ 1.00 atm  .................  -27.7 to -18.1...  -30.4 to -21.2...  -54.8 to -53.9..  -53.3 to -49.0..  -51.0 to -49.8..  -31.8 to -21.8..  -32.7 to -15.0..  -49.9 to -38.1..  -53.1 to -45.2. 
                                     deg.C @ 1.00 atm  .................  -33.2 to -27.8...  -34.7 to -29.6...  -48.2 to -47.7..  -47.4 to -45.0..  -46.1 to -45.4..  -34.0 to -21.9..  -36.0 to -26.1..  -45.5 to -38.9..  -47.3 to -42.9. 
        Boiling Point Range*......  K................  .................  5.4..............  5.1..............  0.5.............  2.4.............  0.7.............  12.1............  9.9.............  6.6.............  4.4.            
    Vapor Phase Contaminants:                                                                                                                                                                                                               
        Air and other non-          % by volume @ 25   5.9..............  1.5..............  1.5..............  1.5.............  1.5.............  1.5.............  1.5.............  1.5.............  1.5.............  1.5.            
         condensables.               deg.C.                                                                                                                                                                                                 
    Liquid Phase Contaminants:                                                                                                                                                                                                              
        Water.....................  ppm by weight....  5.4..............  10...............  10...............  10..............  10..............  10..............  10..............  10..............  10..............  10.             
        All other impurities        % by weight......  5.1..............  0.50.............  0.50.............  0.50............  0.50............  0.50............  0.50............  0.50............  0.50............  0.50.           
         including refrigerants.                                                                                                                                                                                                            
        High boiling residue......  % by volume......  5.7..............  0.01.............  0.01.............  0.01............  0.01............  0.01............  0.01............  0.01............  0.01............  0.01.           
        Particulates/solids.......  Visually clean to  5.8..............  pass.............  pass.............  pass............  pass............  pass............  pass............  pass............  pass............  pass.           
                                     pass.                                                                                                                                                                                                  
        Acidity...................  ppm by weight....  5.6..............  1.0..............  1.0..............  1.0.............  1.0.............  1.0.............  1.0.............  1.0.............  1.0.............  1.0.            
        Chlorides**...............  No visible         5.5..............  pass.............  pass.............  pass............  pass............  pass............  pass............  pass............  pass............  pass.           
                                     turbidity.                                                                                                                                                                                             
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
    * Boiling points and boiling point ranges, although not required, are provided for informational purposes.                                                                                                                              
    ** Recognized chloride level for pass/fail is 3ppm.                                                                                                                                                                                     
    Shaded columns denote refrigerants for which analytical data is not available.                                                                                                                                                          
    
    
    [[Page 32098]]
    
    
                                                                            Table 1B (Continued).--Physical Properties of Zeotropic Blends (400 Series Refrigerants)                                                                        
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
                                                            Reference                                                                                                                                                                       
                                        Reporting units    (subclause)         R407C                R408A                R409A                R410A                R410B                R411A                R411B               R412A      
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
    Characteristics: *                                                                                                                                                                                                                      
        Refrigerant Components......  ...................  ...........  R32/125/134a.......  R125/143a/22.......  R22/124/142b.......  R32/125............  R32/125............  R1270/22/152a......  R1270/22/152a.....  R22/218/          
                                                                                                                                                                                                                          142.              
        Nominal Comp, weight %......  ...................  ...........  23/25/52...........  7/46/47............  60/25/15...........  50/50..............  45/55..............  1.5/87.5/11.0......  3/94/3............  70/5/25.          
        Allowable Comp, weight %....  ...................  ...........  22-24/23-27/50-54..  5-9/45-47/45-49....  58-62/23-27/14-16..  48.5-50.5/49.4-51.5  44-46/54-56........  0.5-1.5/87.5-89.5/   2-3/94-96/2-3.....  68-72/3-7/24-26.  
                                                                                                                                                                                  10-11.                                                    
        Boiling Point...............   [email protected] atm....  ...........  46.4 to -33.0......  -48.8 to -47.9.....  32.4 to -18.2......  -60.1 to -60.0.....  -60.3 to -60.2.....  ...................  ..................  -40.2 to 25.6.    
                                       [email protected] atm....  ...........  -43.6 to -36.6.....  -44.9 to -44.4.....  -35.8 to -27.9.....  -51.2 to -51.1.....  -51.3 to -51.2.....  ...................  ..................  -40.1 to 32.0.    
        Boiling Point Range*........  K..................  ...........  7.0................  0.5................  7.9................  0.1................  0.1................  ...................  ..................  8.1               
    Vapor Phase Contaminants:                                                                                                                                                                                                               
        Air and other non-            % by volume @25             5.9   1.5................  1.5................  1.5................  1.5................  1.5................  1.5................  1.5...............  1.5               
         condensables.                 deg.C.                                                                                                                                                                                               
    Liquid Phase Contaminants:                                                                                                                                                                                                              
        Water.......................  ppm by weight......         5.4   10.................  10.................  10.................  10.................  10.................  10.................  10................  10                
        All other impurities          % by weight........         5.1   0.50...............  0.50...............  0.50...............  0.50...............  0.50...............  0.50...............  0.50..............  0.50              
         including refrigerants.                                                                                                                                                                                                            
        High boiling residue........  % by volume........         5.7   0.01...............  0.01...............  0.01...............  0.01...............  0.01...............  0.01...............  0.01..............  0.01              
        Particulates/solids.........  Visually clean to           5.8   pass...............  pass...............  pass...............  pass...............  pass...............  pass...............  pass..............  pass              
                                       pass.                                                                                                                                                                                                
        Acidity.....................  ppm by weight......         5.6   1.0................  1.0................  1.0................  1.0................  1.0................  1.0................  1.0...............  1.0               
        Chlorides**.................  No visible                  5.5   pass...............  pass...............  pass...............  pass...............  pass...............  pass...............  pass..............  pass              
                                       turbidity.                                                                                                                                                                                           
    ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
    *Boiling points and boiling point ranges, although not required, are provided for informational purposes.                                                                                                                               
    **Recognized chloride level for pass/fail is 3ppm.                                                                                                                                                                                      
    Shaded columns denote refrigerants for which analytical data is not available.                                                                                                                                                          
    
    
                                                              Table 1C.--Physical Properties of Azeotropic Blends (500 Series Refrigerants)                                                         
    ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
                                                            Reference                                                                                                                               
                                        Reporting units    (subclause)          R500                 R502                 R503                 R507                 R508                 R509       
    ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
    Characteristics:*                                                                                                                                                                               
        Refrigerant Components......  ...................  ...........  R12/152a...........  R22/115............  R23/13.............  R125/143a..........  R23/116............  R22/218.           
        Nominal Comp. weight %......  ...................  ...........  73.8/26.2..........  48.8/51.2..........  40.1/59.9..........  50/50..............  39/61..............  44/56.             
        Allowable Comp. weight %....  ...................  ...........  72.8-74.8/25.2-27.2  44.8-52.8/47.2-55.2  39-41/59.61........  49-51/49-51........  37-41/59-63........  42-46/56-60.       
        Boiling Point*..............   [email protected] atm....  ...........  -28.1..............  -49.7..............  -127.7.............  -52.1..............  -123.5.............  -53.9.             
                                       [email protected] atm....  ...........  -33.4..............  -45.4..............  -88.7..............  -46.7..............  -86.4..............  -47.7.             
        Boiling Point Range*........  K..................  ...........  0.5................  0.5................  0.5................  0.5................  0.5................  0.5.               
    Vapor Phase Contaminants:                                                                                                                                                                       
        Air and other non-            % by volume @25             5.9   1.5................  1.5................  1.5................  1.5................  1.5................  1.5.               
         condensables.                 deg. C.                                                                                                                                                      
    Liquid Phase Contaminants:                                                                                                                                                                      
        Water.......................  ppm by weight......         5.4   10.................  10.................  10.................  10.................  10.................  10.                
        All other impurities          % by weight........         5.1   0.50...............  0.50...............  0.50...............  0.50...............  0.50...............  0.50.              
         including refrigerants.                                                                                                                                                                    
        High boiling residue........  % by volume........         5.7   0.05...............  0.01...............  0.01...............  0.01...............  0.01...............  0.01.              
        Particulates/solids.........  Visually clean to           5.8   Pass...............  Pass...............  Pass...............  Pass...............  Pass...............  Pass               
                                       pass.                                                                                                                                                        
        Acidity.....................  ppm by weight......         5.6   1.0................  1.0................  1.0................  1.0................  1.0................  1.0                
        Chlorides**.................  No visible                  5.5   Pass...............  Pass...............  Pass...............  Pass...............  Pass...............  Pass.              
                                       turbidity.                                                                                                                                                   
    ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
    *Boiling points and boiling point ranges, although not required, are provided for informational purposes.                                                                                       
    **Recognized chloride level for pass/fail in 3ppm.                                                                                                                                              
    
    
    [[Page 32099]]
    
    Appendix A. References--Normative
    
        Listed here are all standards, handbooks, and other publications 
    essential to the formation and implementation of the standard. All 
    references in this appendix are considered as part of this standard.
        ASHRAE Terminology of Heating, Ventilating, Air Conditioning and 
    Refrigeration, American Society of Heating Refrigeration and Air-
    Conditioning Engineers, 1992, 1791 Tullie Circle N.E., Atlanta, GA 
    30329-2305; U.S.A.
        ASHRAE Standard 34-1992, Number Designation and Safety 
    Classification of Refrigerants, American Society of Heating 
    Refrigeration and Air-Conditioning Engineers, 1992, 1791 Tullie Circle 
    N.E., Atlanta, GA 30329-2305; U.S.A.
        Appendix C to ARI Standard 700-95: Analytical Procedures to ARI 
    Standard 700-95, Specifications for Fluorocarbon and Other 
    Refrigerants, Air-Conditioning and Refrigeration Institute, 1995, 4301 
    North Fairfax Drive, Suite 425, Arlington, VA 22203; U.S.A.
        Federal Specification for Fluorocarbon Refrigerants, BB-F-1421-B, 
    dated March 5, 1992, Office of the Federal Register, National Archives 
    and Records Administration, 1992, 800 North Capitol Street, N.W., 
    Washington, D.C. 20402; U.S.A.
    
    [FR Doc. 98-15003 Filed 6-10-98; 8:45 am]
    BILLING CODE 6560-50-P