98-16538. Rochester Gas and Electric Corporation (R.E. Ginna Nuclear Power Plant); Revocation of Exemption  

  • [Federal Register Volume 63, Number 119 (Monday, June 22, 1998)]
    [Notices]
    [Page 33966]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 98-16538]
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    NUCLEAR REGULATORY COMMISSION
    
    [Docket No. 50-244]
    
    
    Rochester Gas and Electric Corporation (R.E. Ginna Nuclear Power 
    Plant); Revocation of Exemption
    
    I
    
        The Rochester Gas and Electric Corporation (the licensee) is the 
    holder of Facility Operating License No. DPR-18, which authorizes 
    operation of the R. E. Ginna Nuclear Power Plant. The license provides 
    that the licensee is subject to all rules, regulations, and orders of 
    the U.S. Nuclear Regulatory Commission (NRC or the Commission) now or 
    hereafter in effect.
        The facility consists of a pressurized-water reactor at the 
    licensee's site located in Wayne County, New York.
    
    II
    
        On March 21, 1985, the NRC issued 11 exemptions from the 
    requirements of Section III.G of Appendix R to 10 CFR Part 50. The 
    first exemption, relevant here, related to the Refueling Water Storage 
    Tank (RWST). The licensee was granted an exemption from the technical 
    requirements of Section III.G.2 in connection with the absence of a 
    required continuous fire-rated barrier between redundant shutdown 
    systems in the Auxiliary Building Fire Areas ABBM and ABI. The RWST 
    extends through the concrete floor/ceiling at elevation 271 feet, which 
    provides the common boundary between Fire Area ABBM and ABI. An 8-foot 
    concrete block wall partially circles the circumference of the RWST on 
    the upper side of the barrier. At the time the exemption was granted, 
    there was a 6-inch gap around the circumference of the RWST.
    
    III
    
        By letter dated January 13, 1998, the licensee informed the NRC 
    that the exemption is no longer required. The licensee indicated that 
    the subject barrier has now been sealed by insertion of a 12 inch 
    minimum depth of kaowool into the 6-inch gap around the circumference 
    of the tank and closure of the gap by a \3/4\-inch thick steel plate.
        On the basis of the licensee's submittal, the Commission hereby 
    revokes the exemption granted on March 21, 1985, from the technical 
    requirements of Section III.G of Appendix R to 10 CFR Part 50 with 
    respect to the absence of a continuous fire-rated barrier at the common 
    boundary between Fire Areas ABBM and ABI. The NRC staff did not review 
    the modification that the licensee implemented to eliminate the need 
    for the original exemption. The NRC staff may review the modification 
    and its supporting technical bases during a future on-site inspection.
        Pursuant to 10 CFR 51.32, the Commission has determined that the 
    revocation of the exemption will have no significant impact on the 
    quality of the human environment (63 FR 31534).
        This revocation of exemption is effective upon issuance.
    
        Dated at Rockville, Maryland, this 15th day of June 1998.
    
        For the Nuclear Regulatory Commission.
    S. Singh Bajwa,
    Director, Project Directorate I-1, Division of Reactor Projects--I/II, 
    Office of Nuclear Reactor Regulation.
    [FR Doc. 98-16538 Filed 6-19-98; 8:45 am]