94-19721. Proposed Generic Communication; ``Voltage-Based Repair Criteria For The Repair Of Westinghouse Steam Generator Tubes Affected By Outside Diameter Stress Corrosion Cracking''  

  • [Federal Register Volume 59, Number 155 (Friday, August 12, 1994)]
    [Unknown Section]
    [Page 0]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 94-19721]
    
    
    [[Page Unknown]]
    
    [Federal Register: August 12, 1994]
    
    
    -----------------------------------------------------------------------
    
    
    NUCLEAR REGULATORY COMMISSION
     
    
    Proposed Generic Communication; ``Voltage-Based Repair Criteria 
    For The Repair Of Westinghouse Steam Generator Tubes Affected By 
    Outside Diameter Stress Corrosion Cracking''
    
    AGENCY: U.S. Nuclear Regulatory Commission.
    
    ACTION: Notice of opportunity for public comment.
    
    -----------------------------------------------------------------------
    
    SUMMARY: The Nuclear Regulatory Commission (NRC) is proposing to issue 
    a generic letter. A generic letter is an NRC document that: (1) 
    Requests licensees to submit analyses or descriptions of proposed 
    corrective actions, or both, regarding matters of safety, safeguards, 
    or environmental significance, or (2) requests licensees to submit 
    information to the NRC on other technical or administrative matters, or 
    (3) transmits information to licensees regarding approved changes to 
    rules or regulations, the issuance of reports or evaluations of 
    interest to the industry, or changes to NRC administrative procedures. 
    When issued, this generic letter will provide guidance for licensees 
    who may wish to request a license amendment to the plant technical 
    specifications to implement an alternate steam generator tube repair 
    limit applicable specifically to outside diameter stress corrosion 
    cracking at the tube-to-tube support plate intersections in 
    Westinghouse designed steam generators having drilled-hole tube support 
    plates. This generic letter is intended to provide relief while 
    maintaining an acceptable level of safety for licensees having steam 
    generators experiencing this particular degradation mechanism while the 
    NRC pursues a longer term resolution to the issue of steam generator 
    degradation through the development of a steam generator rule. The NRC 
    is seeking comment from interested parties regarding both the technical 
    and regulatory aspects of the proposed generic letter presented under 
    the Supplementary Information heading. Additionally, the NRC is seeking 
    public comments on the following question which pertains to the 
    technical positions described in the proposed generic letter. The 
    voltage-based repair methodology and calculational approach 
    incorporates numerous conservatism throughout the calculation in part 
    to bound uncertainties that currently exist in the methodology. The NRC 
    is soliciting public comment on the propagation of uncertainties 
    through the leakage rate and radiological dose calculations under 
    postulated accident conditions and the appropriateness of the 
    conservatism that have been included in the analyses to account for 
    these uncertainties. Two examples of uncertainties in the voltage-based 
    repair methodology and calculational approach are: (1) Several 
    functional forms (in addition to the log-logistic curve used in the 
    proposed generic letter) can be fit to the available probability of 
    leakage data equally well from the standpoint of a statistical goodness 
    of fit, and (2) there is a paucity of definitive data describing iodine 
    releases into the reactor coolant system following a large 
    depressurization transient such as the postulated main steam line 
    break.
        During development of the proposed generic letter, three individual 
    NRC staff members expressed technical concerns (including one member 
    filing a differing professional opinion) with the NRC positions 
    described in the generic letter, in response to an internal memorandum 
    requesting such comments. The differing professional opinion is 
    currently being processed in accordance with the established NRC 
    procedures. The NRC policies on differing professional opinions (DPOs) 
    or differing professional views (DPVs) were established to ensure 
    employees have the ability to freely express their DPOs or DPVs and to 
    underscore management's intention to address these concerns in a timely 
    and responsible manner. The NRC has decided to make these technical 
    concerns and the differing professional opinion publicly available as 
    part of the information available in the Public Document Rooms, and to 
    provide the public an opportunity to comment on these concerns as they 
    may relate to the draft generic letter. The NRC held internal technical 
    interactions with the three individuals regarding their technical 
    concerns and gave the concerns careful consideration (the concerns did 
    not necessarily result in revisions to the proposed generic letter nor 
    were they necessarily resolved to the individuals' satisfaction) during 
    development and review of the proposed generic letter. The technical 
    concerns and differing professional opinion are briefly summarized as 
    follows: (1) The first concern is that use of the eddy current voltage 
    repair criteria could result in leakage rates following a postulated 
    main steam line break that could ultimately exceed the make-up capacity 
    of the refueling water storage tank for the emergency core cooling 
    system supply and result in core damage. The concern stems from the 
    belief that there is no direct relation between leakage and measured 
    eddy current voltage. (2) The second concern is that there is no 
    physical basis for choosing a given probability of leakage (POL) 
    function versus other POL functions, when all functions fit the 
    available data from a statistical standpoint. (3) The third concern 
    stems from the application of a voltage-based repair criterion when 
    there is not a unique correlation between voltage amplitude and 
    physical parameters (i.e., length or depth) of a defect that can be 
    directly related to tube structural integrity or leakage. The DPO is 
    similar to technical concern: (1) With additional concerns raised 
    regarding the paucity of iodine spiking data for the calculation of 
    offsite doses for a postulated main steam line break with induced steam 
    generator tube leakage and the effectiveness of reducing reactor 
    coolant system iodine activity for reducing calculated offsite doses. 
    The summaries above are not intended to oversimplify the expressed 
    technical concerns or differing professional opinion. To fully 
    understand the concerns, it is recommended that each concern be read in 
    its entirety. The proposed generic letter and supporting documentation 
    were discussed in the 260th meeting of the Committee to Review Generic 
    Requirements (CRGR). At this meeting, the three individual NRC staff 
    members presented their technical concerns to the CRGR. The relevant 
    information used to support CRGR review of the proposed generic letter 
    will be available in the Public Document Rooms. In addition, the 
    proposed generic letter and supporting documentation were discussed in 
    a meeting of the Materials and Metallurgy Subcommittee of the NRC 
    Advisory Committee on Reactor Safeguards (ACRS) on August 3, 1994, as 
    well as a full ACRS meeting held on August 4, 1994.
        The NRC will consider comments received from interested parties in 
    the final evaluation of the proposed generic letter. The NRC final 
    evaluation will include a review of the technical position and, when 
    appropriate, an analysis of the value/impact on licensees. Should this 
    generic letter be issued in final form by the NRC, it will become 
    available for public inspection in the Public Document Rooms.
    
    DATES: Comment period expires September 12, 1994. Comments submitted 
    after this date will be considered if it is practical to do so, but 
    assurance of consideration cannot be given except for comments received 
    on or before this date.
    
    ADDRESSES: Submit written comments to Chief, Rules Review and 
    Directives Branch, U.S. Nuclear Regulatory Commission, Washington, D.C. 
    20555. Written comments may also be delivered to Room T6-D59, 11545 
    Rockville Pike, Rockville, Maryland, 20852 from 7:30 a.m. to 4:15 p.m., 
    Federal workdays. Copies of written comments received may be examined 
    at the NRC Public Document Room, 2120 L Street, N.W. (Lower Level), 
    Washington, D.C.
    
    FOR FURTHER INFORMATION CONTACT: Timothy A. Reed, (301) 504-1465.
    
    SUPPLEMENTARY INFORMATION
    
    NRC Generic Letter 94-XX: Voltage-Based Repair Criteria For The Repair 
    of Westinghouse Steam Generator Tubes Affected by Outside Diameter 
    Stress Corrosion Cracking
    
    Addressees
    
        All holders of operating licenses or construction permits for 
    nuclear power reactors having steam generators designed by Westinghouse 
    Electric Corporation (W).
    
    Purpose
    
        The U.S. Nuclear Regulatory Commission (NRC) is issuing this 
    guidance for licensees who may wish to request a license amendment to 
    the plant technical specifications to implement an alternate steam 
    generator tube repair limit applicable specifically to outside diameter 
    stress corrosion cracking (ODSCC) at the tube-to-tube support plant 
    intersections in Westinghouse designed steam generators having drilled-
    hole tube support plates (TSP). The NRC has previously allowed a few 
    licensees to implement alternate steam generator repair criteria for 
    this particular degradation mechanism on an operating cycle specific 
    basis. This generic letter does not restrict the approval of such 
    repair criteria to a cycle specific basis.
        Current plant technical specifications require that flawed tubes be 
    removed from service by plugging or repaired by sleeving, if the depths 
    of the flaws exceed the repair limit, typically 40 percent through-
    wall. This generic letter provides guidance on the implementation of an 
    alternate repair criterion to be applied to ODSCC at TSP locations. 
    This criterion does not set limits on the depth of the cracks to ensure 
    tube integrity margins; instead, it relies on correlating the eddy 
    current voltage amplitude from a bobbin coil probe with the more 
    specific measurement of burst pressure and leak rate.
        This generic letter is intended to provide relief while maintaining 
    an acceptable level of safety for licensees having steam generators 
    experiencing this particular degradation mechanism while the staff 
    pursues a longer term resolution to the issue of steam generator 
    degradation through the development of a steam generator rule. Although 
    this generic letter allows licensees to pursue various options 
    regarding the implementation of the voltage-based criteria (e.g., tube 
    support place deflection analyses, probability of detection versus 
    voltage dependence), licensees should recognize that pursuing such 
    options could have significant scheduler implications since the NRC 
    staff would be required to review and approve the associated 
    information and analyses. Regarding the correlations and supporting 
    data utilized to implement the generic letter guidance, the staff will 
    review this information on an as-required basis to enable updated 
    correlations and new data to be used for implementation of the generic 
    letter guidance. The NRC staff will make publicly available an updated 
    list of approved correlations and models on a periodic basis.
    
    Background
    
        The thin-walled tubing of the steam generator constitutes more than 
    half of the reactor coolant pressure boundary (RCPB). Maintenance of 
    the structural and leakage integrity of the RCPB is a requirement under 
    Title 10 of the Code of Federal Regulations Part 50 (10 CFR 50), 
    Appendix A. Specific requirements governing the maintenance of steam 
    generator tube integrity are contained in the plant technical 
    specifications and Section XI of the American Society of Mechanical 
    Engineers (ASME) Boiler and Pressure Vessel Code (ASME Code). These 
    include requirements for periodic inservice inspection of the tubing, 
    flaw acceptance criteria (i.e., repair limits for plugging or 
    sleeving), and primary-to-secondary leakage limits. These requirements 
    coupled with the broad scope of plant operational and maintenance 
    programs, have formed the basis for assuring adequate steam generator 
    tube integrity.
        Flaw acceptance criteria, termed plugging/repair limits, are 
    specified in the plant technical specifications. The purpose of the 
    technical specification repair limits is to ensure that tubes accepted 
    for continued service will retain adequate structural and leakage 
    integrity during normal operating, transient, and postulated accident 
    conditions, consistent with General Design Criteria (GDC) 14, 15, 30, 
    31, and 32 of 10 CFR part 50, appendix A. Structural integrity refers 
    to maintaining adequate margins against gross failure, rupture, and 
    collapse of the steam generator tubing. Leakage integrity refers to 
    limiting primary-to-secondary leakage to within acceptable limits.
        The traditional strategy for accomplishing the objectives of the 
    General Design Criteria related to steam generator tube integrity has 
    been to establish a minimum wall thickness requirement in accordance 
    with the structural criteria of Regulatory Guide 1.121, ``Bases for 
    Plugging Degraded PWR Steam Generator Tubes.'' Development of minimum 
    wall thickness requirements to satisfy Regulatory Guide 1.121 was 
    governed by analyses for uniform thinning of the tube wall in the axial 
    and circumferential directions. The assumption of uniform thinning 
    conservatively bonds the degrading effects of all flaw types occurring 
    in the field, and is the basis of the standard 40 percent depth-based 
    plugging limit incorporated into the technical specifications. However, 
    the 40 percent repair limit is conservative for highly localized flaws 
    such as pits and short cracks. In particular, the 40 percent depth-
    based repair limit is conservative for outside diameter stress 
    corrosion cracking (ODSCC) that occurs at the tube support plates.
        The new voltage-based repair limit does not incorporate a minimum 
    wall thickness requirement. The voltage-based repair limit allows the 
    possibility that tubes with up to 100 percent through-wall cracks, 
    which may develop between successive steam generator inspections, can 
    remain in service, subject to certain restrictions. These restrictions 
    ensure structural integrity and leakage limits consistent with the 
    applicable GDC of 10 CFR part 50 appendix A and the limits of 10 CFR 
    Part 100. Although the voltage-based repair limit ensures adequate 
    structural integrity and leakage limits, the NRC staff recognizes that 
    overall margins have been reduced when compared to the margins 
    associated with the existing 40% depth-based repair limit.\1\ Because 
    of the increased likelihood of through-wall cracks developing in 
    service, the staff has included provisions for augmented steam 
    generator inspections and more restrictive operational tube leakage 
    limits in the generic letter guidance.
    ---------------------------------------------------------------------------
    
        \1\During development of the proposed generic letter, three 
    individual NRC staff members expressed technical concerns (including 
    one member filing a differing professional opinion) with the NRC 
    positions described in the generic letter. The technical concerns 
    and differing professional opinion are publicly available in the 
    Public Document Rooms. The NRC will consider public comments from 
    interested parties on the technical concerns as they relate to the 
    positions proposed in the draft generic letter.
    ---------------------------------------------------------------------------
    
        In taking the interim action described in this letter, the NRC 
    staff wishes to emphasize that, while use of the specific voltage-based 
    repair methods described herein is approved as an acceptable short-term 
    measure for dealing with ODSCC tube degradation, this action should not 
    be construed to discourage the use by licensees of better or further 
    refined data acquisition techniques, eddy current technology, and eddy 
    current data analysis as they become available; and the staff strongly 
    encourages the industry to continue its efforts to improve the 
    nondestructive examination of steam generator tubes. The staff 
    continues to believe that inspection methods and repair criteria based 
    on physical dimensions (e.g., length and depth) of defects are the most 
    desirable when they can be achieved.
    
    Discussion
    
    1. Overview of the Voltage Repair Limit Approach
        In order to use the voltage repair criteria, licensees should 
    complete the following actions:
    
    --Perform an enhanced inspection of tubes, particularly at the tube 
    support plate (TSP) intersections,
    --Utilize nondestructive examination (NDE) data acquisition and 
    analysis procedures that are consistent with the methodology used to 
    develop the voltage-based repair limits,
    --Repair or plug tubes that exceed the voltage limits,
    --Determine the beginning of cycle voltage distribution,
    --Project the end-of-cycle (EOC) distribution,
    --For the projected EOC voltage distribution, calculate leakage and 
    conditional burst probability (and repair additional tubes if 
    necessary).
    
    2. Generic Letter Applicability
        The criteria in this generic letter are only applicable to ODSCC 
    located at the tube-to-tube support plate intersections in Westinghouse 
    designed steam generators. These criteria are not applicable to other 
    forms of steam generator tube degradation, nor are they applicable to 
    ODSCC that occurs at other locations within a steam generator. The 
    voltage-based repair criteria can be applied only under the following 
    constraints:
        (1) The repair criteria of this generic letter apply only to 
    Westinghouse designed steam generators with 1.9 cm [\3/4\ inch] and 2.2 
    cm [\7/8\ inch] diameter tubes and drilled hole tube support plates,
        (2) The repair criteria of this generic letter apply only to 
    predominantly axially oriented ODSCC confined within the tube-to-tube 
    support plate intersection (refer to Section 1.a of Enclosure 1 for 
    further guidance) and,
        (3) Certain intersections are excluded from the application of the 
    voltage-based repair criteria as discussed in Section 1.b of Enclosure 
    1.
    3. Voltage Repair Limit
        The voltage repair limits are:
        (1) for 2.2 cm [\7/8\ inch] diameter tubes:
         Indications below 2.0 volts as measured by bobbin coil may 
    remain in service;
         Indications between 2.0 and 5.6 volts as measured by 
    bobbin coil can remain in service if motorized rotating pancake coil 
    (MRPC) inspections do not confirm the indications; and
         Indications between 2.0 and 5.6 volts as measured by 
    bobbin coil that are confirmed by MRPC and indications exceeding 5.6 
    volts as measured by bobbin coil must be repaired.
        (2) For 1.9 cm [\3/4\-inch] diameter tubes.
         Indications below 1.0 volt as measured by bobbin coil may 
    remain in service;
         Indications between 1.0 and 2.7 volts as measured by 
    bobbin coil can remain in service if MRPC inspections do not confirm 
    the indications; and
         Indications between 1.0 and 2.7 volts as measured by robin 
    coil that are confirmed by MRPC and indications exceeding 2.7 volts as 
    measured by bobbin coil must be repaired.
        The voltage-based repair limits of this generic letter were 
    determined considering the entire range of design basis events that 
    could challenge tube integrity. The voltage repair limits ensure 
    structural integrity and leakage limits for all postulated design basis 
    events. The structural criteria are intended to ensure that tubes 
    subjected to the voltage repair limits will be able to withstand a 
    pressure of 1.4 times a maximum possible main steam line break (MSLB) 
    differential pressure postulated to occur at the end of the operating 
    cycle consistent with the criteria of Regulatory Guide 1.121. The 
    leakage criteria ensure that for tubes subject to the voltage repair 
    limits, induced leakage under worst-case MSLB conditions calculated 
    using licensing basis assumptions, will not result in offsite dose 
    releases that exceed the applicable limits of 10 CFR Part 100.
    
    Requested Actions
    
        Implementation of the guidance in this generic letter is voluntary. 
    If a licensee chooses to implement these criteria, the following should 
    be included in the proposed program:
        (1) Implementation of the inspection guidance discussed in Section 
    3 of Enclosure 1. The inspection guidance ensures that the techniques 
    used to inspect steam generators are consistent with the techniques 
    used to develop voltage-based repair limit methodology.
        (2) Calculation of leakage per the guidance of Section 2.b of 
    Enclosure 1. This calculation, in conjunction with the use of licensing 
    basis assumptions for calculating offsite releases, enables licensees 
    to demonstrate that the applicable limits of 10 CFR Part 100 continue 
    to be met.
        (3) Calculation of conditional burst probability per the guidance 
    of Section 2.a of Enclosure 1. This is a calculation to assess the 
    voltage distribution left in service against a threshold value.
        (4) Implementation of the operational leakage limits identified in 
    Section 5 of Enclosure 1. The operational leak limit is a defense-in-
    depth measure that provides a means for identifying leaks during 
    operation to enable repair before such leaks result in tube failure.
        (5) Review of leakage monitoring measures including the procedures 
    for timely detection, trending, and response to rapidly increasing 
    leaks. The objective is to ensure that should a significant leak be 
    experienced in service, it will be detected and the plant shut down in 
    a timely manner to reduce the likelihood of a potential rupture.
        (6) Acquisition of tube pull data per the guidance of Section 4 of 
    Enclosure 1. It is necessary to acquire pulled tube data to confirm the 
    degradation mechanism.
        (7) Reporting of results per the guidance of Section 6 of Enclosure 
    1.
        (8) Submittal of a technical specification (TS) amendment request 
    that commits to the above and provides TS pages per the guidance of 
    Enclosure 2 including the associated consideration of no significant 
    hazards consideration (10 CFR 50.92) and supporting safety analysis.
        Licensees that plan to adopt this TS amendment are encouraged to 
    follow the guidance given in Enclosures 1 and 2. The staff requests 
    that licensees following the guidance of this generic letter submit 
    their TX amendment request at least 90 days prior to the beginning of 
    the refueling outage during which the alternate repair criteria are to 
    be implemented.
    
    Backfit Discussion
    
        Licensee action to propose TS changes under the guidance of this 
    generic letter is voluntary; therefore, such action is not a backfit 
    under the provisions of 10 CFR 50.109.
    
    Paperwork Reduction Act Statement
    
    [To Be Provided in the Final Generic Letter]
        Enclosures:
        1. Guidance for a Proposed License Amendment to Implement an 
    Alternate Steam Generator Tube Repair Limit for Outside Diameter Stress 
    Corrosion Cracking at the Tube Support Plate Intersections
        2. Model Technical Specifications
        3. List of Recently Issued NRC Generic Letters
    
    Guidance for a Proposed License Amendment To Implement an Alternate 
    Steam Generator Tube Repair Limit for Outside Diameter Stress Corrosion 
    Cracking at the Tube Support Plate Intersections
    
    1. Introduction
    
        This guidance provides the NRC staff position on the implementation 
    of the voltage-based repair criteria in steam generators designed by 
    Westinghouse for outside diameter stress corrosion cracking (ODSCC) 
    located at the tube-to-tube support plate intersections. This guidance 
    is not applicable to other forms of steam generator tube degradation 
    nor is it applicable to ODSCC that occurs at other locations with the 
    steam generator. The voltage-based repair criteria have been developed 
    for, and are currently applicable only to, Westinghouse-designed steam 
    generators with 2.2 cm [\7/8\-inch] or 1.9 cm [\3/4\-inch] diameter 
    tubes with drilled hole tube support plates (TSPs). Application of the 
    alternate repair criteria to other vendor designed steam generators 
    would require both the development and NRC staff review and approval of 
    a comparable data base and the associated correlations for each vendor 
    steam generator type.
        The NRC staff wants to emphasize that while the NRC has approved 
    the implementation of the voltage-based repair methods described in 
    this generic letter as a short-term measure, this guidance should not 
    be construed to discourage the development and use of better 
    acquisition techniques, eddy current technology, and eddy current data 
    analysis. The staff strongly encourages the industry to continue to 
    improve the NDE of steam generator tubes.
    1.a ODSCC
        The voltage-based repair criteria are applicable only to 
    indications at support plate intersections where the degradation 
    mechanism is dominantly axial ODSCC with no significant cracks 
    extending outside the thickness of the support plate.
        For purposes of this guidance, OSDCC refers to degradation whose 
    dominant morphology consists of axial stress corrosion cracks which 
    occur either singularly or in networks of multiple cracks, sometimes 
    with limited patches of general intergranular attack (IGA). 
    Circumferential cracks may sometimes occur in the IGA affected regions 
    resulting in a grid-like pattern of axial and circumferential cracks, 
    termed cellular corrosion. Cellular corrosion is assumed to be 
    relatively shallow (based on available data from tube specimens removed 
    from the field), transitioning to dominantly axial cracks as the 
    cracking progresses in depth. The circumferential cracks are assumed 
    (based on available data) not to be of sufficient size to produce a 
    discrete, crack-like circumferential indication during field 
    nondestructive examination (NDE) inspections. Thus, the failure mode of 
    ODSCC is axial and the burst pressure is controlled by the geometry of 
    the most limiting axial crack or array of axial cracks.
        It is also assumed for purposes of this guidance that the ODSCC is 
    confined to within the thickness of the tube support plate, based on 
    available data from tube specimens removed from the field. Very shallow 
    microcracks are sometimes observed on these specimens to initiate at 
    locations slightly outside the thickness of the tube support plate; 
    however, these microcracks are small compared to the cracks within the 
    thickness of the support plate and are too small to produce an eddy 
    current response.
        Confirmation that the degradation mechanism is dominantly axial 
    ODSCC should be accomplished by periodically removing tube specimens 
    from the steam generators and by examining and testing these specimens 
    as specified in Section 4 of this guidance. The acceptance criteria 
    should consist of demonstrating that the dominant degradation mechanism 
    affecting the burst and leakage properties of the tube is axially 
    oriented ODSCC. In addition, results of inservice inspections with 
    motorized rotating pancake coil (MRPC) probes should be evaluated in 
    accordance with Section 3.b of this guidance to confirm the absence of 
    detectable crack-like circumferential indications and detectable ODSCC 
    indications extending outside the tube support plate thickness.
    1.b Exclusion of Intersections
        The voltage repair criteria of this guidance do not apply to 
    intersections meeting the criteria discussed below:
    1.b.1 The repair criteria do not apply to support plate intersections 
    where the tubes may potentially collapse or deform following a 
    postulated loss-of-coolant accident plus safe shutdown earthquake event 
    (e.g., intersections located near the wedge supports at the upper tube 
    support plates). Licensees should perform or reference an analysis that 
    identifies which intersections are to be excluded.
    1.b.2 The repair criteria do not apply to tubes support plate 
    intersections having dent signals greater than 5 volts as measured with 
    the bobbin probe.
    1.b.3 The repair criteria do not apply to intersections where there are 
    mixed residuals of sufficient magnitude to cause a 1-volt ODSCC 
    indication (as measured with a bobbin probe) to be missed or misread.
    1.b.4 The repair criteria do not apply to the tube-to-flow distribution 
    baffle plate intersections.
    
    2. Tube Integrity Evaluation
    
        Licensees should perform an evaluation prior to plant restart to 
    confirm that the steam generator tubes will retain adequate structural 
    and leakage integrity until the next scheduled inspection. The first 
    portion of this evaluation, referred to as the conditional burst 
    probability calculation, assesses the voltage distribution left in 
    service against a threshold value of 1 x 10-2 probability of 
    rupture under postulated main steam line break (MSLB) conditions. The 
    conditional burst probability calculation is intended to provide a 
    conservative assessment of tube structural integrity during a 
    postulated MSLB occurring at end-of-cycle2 (EOC). It is used to 
    determine whether the NRC needs to focus additional attention on the 
    particular voltage repair limit application. If the calculated 
    conditional burst probability exceeds 1 x 10-2, the licensee 
    should notify the NRC per the guidance provided in Section 6 of this 
    guidance.
    ---------------------------------------------------------------------------
    
        \2\For the purposes of this guidance, ``cycle'' refers to the 
    operating cycle between two scheduled steam generator inspections. 
    Operating cycle and inspection cycle are used interchangeably.
    ---------------------------------------------------------------------------
    
        The second portion of the tube integrity evaluation is intended to 
    assure that total leak rate from the affected steam generator (SG) 
    during a postulated MSLB occurring at EOC would be less than that which 
    could lead to radiological releases in excess of the licensing basis 
    for the plant. If calculated leakage exceeds the allowable limit 
    determined by the licensing basis dose calculation, licensees can 
    either repair tubes, beginning with the largest voltage indications 
    until the leak limit is met, or reduce reactor coolant system specific 
    iodine activity (refer to example technical specification (TS) pages of 
    Enclosure 2). The analyses discussed above may incorporate or reference 
    previous analyses, or portions thereof, to the extent that they 
    continue to bound the conditions of the steam generator as determined 
    by inspection.
        For plants in which the technical specifications do not require the 
    pressurizer power-operated relief valves (PORVs) to be operable during 
    power operation, these tube integrity analyses should be conducted for 
    an assumed differential pressure across the tube walls equal to the 
    pressurizer safety valve set point plus 3 percent for the valve 
    accumulation less atmospheric pressure in faulted steam generators. For 
    plants in which the technical specifications do require the PORVs to be 
    operable, the assumed differential pressure may be based on the PORV 
    set point in lieu of the safety valve set point with similar 
    adjustments.
    2. a  Conditional Probability of Burst During MSLB
        For this generic letter, the conditional probability of burst 
    refers to the probability that the burst pressures associated with 1 or 
    more indications in the faulted steam generator will be less than the 
    maximum pressure differential associated with a postulated MSLB assumed 
    to accur at EOC. A methodology should be submitted for NRC review and 
    approval for calculating this conditional burst probability. After the 
    NRC approves a method for calculating conditional probability of burst, 
    licensees may reference the approved method. This methodology should 
    involve: (1) Determining the distribution of indications as a function 
    of their voltage response at beginning of cycle (BOC) as discussed in 
    Section 2.b.1, (2) projecting this BOC distribution to an EOC voltage 
    distribution based on consideration of voltage growth due to defect 
    progression between inspections as discussed in Section 2.b.2(2) and 
    voltage measurement uncertainty as discussed in Section 2.b.2(1), and 
    (3) evaluating the conditional probability of burst for the projected 
    EOC voltage distribution using the correlation between burst pressure 
    and voltage discussed in Section 2.a.1. The solution methodology should 
    account for uncertainties in voltage measurement (Section 2.b.2(1)), 
    the distribution of potential voltage growth rates applicable to each 
    indication (Section 2.b.2(2)), and the distribution of potential burst 
    pressures as a function of voltage (Section 2.a.1). Monte Carlo 
    simulations constitute an acceptable approach for accounting for these 
    various sources of uncertainty.
    2.a.1  Burst Pressure Versus Bobbin Voltage
        An empirical model, for \7/8\-inch or \3/4\-inch diameter tubing as 
    applicable, should be used to relate burst pressure to bobbin voltage 
    response for purposes of estimating the conditional probability of 
    burst during a postulated MSLB. This model should explicitly account 
    for burst pressure uncertainty as indicated by scatter of the 
    supporting test data and should also account for the parametric (i.e., 
    slope and intercept) uncertainty of the regression fit of the data. The 
    supporting data for \7/8\-inch diameter and \3/4\-inch diameter tubing 
    should include all applicable data consistent with the industry 
    recommendations in letter dated April 22, 1994, to Jack Strosnider, 
    NRC, from David A. Steininger, EPRI, ``Exclusion of Data from Alternate 
    Repair Criteria (ARC) Databases Associated with \7/8\ inch Tubing 
    Exhibiting ODSCC'' (Reference 1) and letter dated June 9, 1994, to 
    Brian Sheron, NRC, from David J. Modeen, Nuclear Energy Institute 
    (Reference 2) respectively, with certain exceptions. Specifically, data 
    excluded under criteria 2a and 2b in References 1 and 2 should not be 
    excluded pending staff review and approval of these criteria.
    2.b  Total Leak Rate During MSLB
        A methodology should be submitted for NRC review and approval for 
    calculating the total primary-to-secondary leak rate in the faulted 
    steam generator during a postulated MSLB assumed to occur at EOC. After 
    the NRC approves a leakage calculation methodology, licensees may 
    reference the approved method. This methodology involves: (1) 
    Determining the distribution of indications as a function of their 
    voltage response at beginning of cycle (BOC) as discussed in Section 
    2.b.1, (2) projecting this BOC distribution to an EOC voltage 
    distribution based on consideration of voltage growth due to defect 
    progression between inspection as discussed in Section 2.b.2(2) and 
    voltage measurement uncertainty as discussed in Section 2.b.2(1), and 
    (3) evaluating the total leak rate for the projected EOC voltage 
    distribution using a probability of leakage (POL) model as discussed in 
    Section 2.b.3(1) and conditional leak rate model as discussed in 
    Section 2.b.3(2). The solution methodology should account for 
    uncertainties in voltage measurement (Section 2.b.2(1)), the 
    distribution of potential voltage growth rates applicable to each 
    indication (Section 2.b.2(2)), the uncertainties in the probability of 
    leakage as a function of voltage (Section 2.b.3(1)), and the 
    distribution of potential conditional leak rates as a function of 
    voltage (Section 2.b.3(2)). Monte Carlo simulations are an acceptable 
    method for accounting for these sources of uncertainty provided that 
    the calculated total leak rate reflects an upper 95% quantile value. 
    [Note: draft NUREG-1477, Section 3.3, page 3-21, presents an expression 
    for Tl (i.e., working bound for total leak rate) which is based on 
    the premise that leak rate is independent of voltage. This expression 
    does not account for parametric uncertainty in either the POL or 
    conditional leak rate model. Thus, the draft NUREG-1477 equation should 
    not be used unless appropriate modifications are made to the equation 
    to account for these parametric uncertainties.]
    2.b.1  Distribution of Bobbin Indications as a Function of Voltage at 
    BOC
        The frequency distribution by voltage of bobbin indications 
    actually found during inspection should be scaled upward by a factor of 
    1/POD to account for non-detected cracks which can potentially leak or 
    rupture under postulated MSLB conditions during the next operating 
    cycle. POD stands for probability of detection of ODSCC flaws. This 
    adjusted frequency distribution minus detected indications for tubes 
    that have been plugged or repaired should constitute, for purposes of 
    the tube integrity analyses, the assumed frequency distribution of 
    bobbin indications at BOC as a function of voltage. This can also be 
    expressed as:
    Nl=(1/POD)(Nd)--Nr
    
    Nl=assumed frequency distribution of bobbin indications
    Nd=frequency distribution of indications actually detected
    Nr=frequency distribution of repaired indications
    POD=probability of detection of ODSCC flaws
    
        POD should be assumed to have a value of 0.6, or as an alternative, 
    and NRC approved POD function can be used if such a function becomes 
    available.
        Nd includes all flaw indications detected by the bobbin coil, 
    regardless of whether these indications are confirmed by MRPC 
    inspection.
    2.b.2  Projected End-of-Cycle (EOC) Voltage Distribution
        As discussed above, the calculation of both conditional burst 
    probability and leakage (during a postulated MSLB) requires the 
    generation of the projected EOC voltage distribution. To project an EOC 
    voltage distribution from the BOC voltage distribution determined 
    above, requires consideration of: (1) Eddy current voltage measurement 
    uncertainty and (2) the addition of voltage growth to account for 
    defect progression. Monte Carlo techniques are an acceptable means for 
    sampling eddy current measurement uncertainty and the voltage growth 
    distribution to determine the projected EOC voltage distribution. Eddy 
    current measurement uncertainty and voltage growth are discussed below.
    2.b.2(1)  Eddy Current Voltage Measurement Uncertainty
        Uncertainty in eddy current voltage measurements stems primarily 
    from two sources:
        (a) Voltage response variability (i.e., test repeatability error) 
    which stems primarily from probe wear
        (b) Voltage measurement variability among data analysts (i.e., 
    measurement repeatability error)
        Each of these uncertainties should be quantified. An acceptable 
    characterization of these uncertainties is contained in EPRI TR-100407, 
    Revision 1, Draft Report August 1993, ``PWR Steam Generator Tube Repair 
    Limits-Technical Support Document for Outside Diameter Stress Corrosion 
    Cracking at the tube Support Plates'' (Reference 3), Sections 2.4.1, 
    2.4.2, and D.4.2.3, with the exception that no distribution cutoff 
    should be applied to the voltage measurement variability distribution. 
    (However, the assumed 15 percent cutoff for the voltage response 
    variability distribution in Reference 3 is acceptable.)
    2.b.2(2)  Voltage Growth Due to Defect Progression
        Potential voltage growth rates during the next inspection cycle 
    (i.e. operating cycle between two scheduled steam generator 
    inspections) should be based on voltage growth rates observed during 
    the last one or two inspection cycles. For a given inspection, previous 
    inspections results at tube support plate intersections currently 
    exhibiting a bobbin indication should be re-evaluated consistent with 
    the date analysis guidelines in Section 3 below. In cases where data 
    acquisition guidelines employed during previous inspection differ from 
    those discussed in Section 3, adjustments to the evaluation of the 
    previous data should be made to compensate for the difference. Voltage 
    growth rates should only be evaluated for those intersections where 
    bobbin indications can be identified at tow successive inspections.
        The distribution of observed voltage growth rates (based on the 
    change in voltage on an intersection-to-intersection basis) should be 
    determined for each of the last one or two inspection cycles. When only 
    the current or only the current and previous inspections employed data 
    acquisition guidelines similar to those discussed in Section 3, only 
    the growth rate distribution for the previous cycle should be used to 
    estimate the voltage growth rate distribution for the next inspection 
    cycle. If both the two previous inspections employed such similar 
    guidelines, the most limiting of the two previous growth rate 
    distributions should be used to estimate the voltage growth rate 
    distribution for the next inspection cycle. However, the two 
    distributions should be combined if one or both the distributions is 
    based on a minimal number (i.e., <200) of="" indications.="" it="" is="" acceptable="" to="" use="" a="" statistical="" model="" fit="" of="" the="" observed="" growth="" rate="" distribution="" as="" part="" of="" the="" integrity="" analysis.="" it="" is="" also="" acceptable="" that="" the="" voltage="" growth="" distribution="" be="" in="" terms="" of=""> volts rather than percent  volts provided the 
    conservatism of this approach continues to be supported by operating 
    experience. Finally, negative growth rates should be included as zero 
    growth rates in the assumed growth distribution.
    2.b.3  Calculation of Projected MSLB Leakage
        Once the projected EOC voltage distribution is determined, the 
    leakage for the postulated MSLB is calculated utilizing the EOC voltage 
    distribution and the use of two models: (1) The probability of leakage 
    model and (2) the conditional leak rate model. As previously discussed 
    in Section 2.b, Monte Carlo techniques are an acceptable approach for 
    accounting for the uncertainties implicit in these models. These models 
    are discussed below.
    2.b3(1)  Probability of Leakage as a Function of Voltage
        The Probability of leakage (POL) model should utilize the log-
    logistic functional form. This model should explicitly account for 
    parameter uncertainty of the POL functional fit of the data (i.e., 
    ``model fit'' uncertainty). The supporting data sets for 2.2 cm (\7/8\-
    inch) diameter and 1.9 cm (\3/4\-inch) diameter tubing should include 
    all applicable data consistent with the industry recommendations in 
    References 1 and 2, respectively, with certain exceptions. Namely, data 
    excluded under criteria 2a and 2b in References 1 and 2 should not be 
    excluded pending staff review and approval of these criteria.
    2.b.3(2)  Conditional Leakage Rate under MSLB Conditions
        The conditional leak rate model should incorporate a linear 
    regression fit to the log of the leak rate data, for 2.2 cm (\7/8\-
    inch) and 1.9 cm (\3/4\-inch) diameter tubing respectively, as a 
    function of the log of the bobbin voltage and should account for both 
    data scatter and parameter uncertainty of the linear regression fit. 
    Use of this approach is subject to demonstrating that the linear 
    regression fit is valid at the 5% level with a ``p-value'' test. If 
    this condition is not satisfied, the linear regression fit should be 
    assumed to have zero slope (i.e., the linear regression fit should be 
    assumed to be constant with voltage).
        The supporting data sets for 2.2 cm (\7/8\-inch) diameter and 1.9 
    cm (\3/4\-inch) diameter tubing should include all applicable data 
    consistent with the industry recommendations in References 1 and 2, 
    respectively, with certain exceptions. Specifically, data excluded 
    under criteria 2a, 2b, 3a, 3b, and 3c in References 1 and 2 should not 
    be excluded pending staff review and approval of these criteria. In 
    addition, an MSLB leak rate of 2496 liters/hour should be utilized for 
    the data point obtained from V.C. Summer tube R28C41 pending staff 
    review and approval of the revised leakage estimate for this tube 
    described in Reference 2.
    2.b.4  Calculation of Offsite and Control Room Doses
        For the MSLB leak rate calculated above, offsite and control room 
    doses should be calculated utilizing currently accepted licensing basis 
    assumptions. Licensees should note that Enclosure 2 of this generic 
    letter provides example TS pages for reducing reactor coolant system 
    specific iodine activity limits. Reactor coolant system iodine 
    activities may be reduced to .35 microcuries per gram does equivalent 
    I-131. Licensees wishing to reduce iodine activities below this level 
    should provide a justification supporting the request that addresses 
    the release rate data described in Reference 6. Reduction of reactor 
    coolant iodine activity is an acceptable means for accepting higher 
    projected leakage rates and still meeting the applicable limits of 
    Title 10 of the Code of Federal Regulations Part 100 utilizing 
    licensing basis assumptions.
    
    3. Inspection Criteria
    
        The inspection scope, data acquisition, and data analysis should be 
    performed in a manner consistent with the methodology utilized to 
    develop the voltage limits (e.g., the methodology described in 
    Reference 4, Appendix A, and Reference 5, Appendix A) with the 
    exceptions and clarifications noted below.
    3.a  Bobbin Coil Inspection Scope and Sampling
        3.a.1  The bobbin coil inspection should include 100 percent of the 
    hot-leg TSP intersections and cold-leg intersections down to the lowest 
    cold-leg TSP with known ODSCC. The determination of TSPs having ODSCC 
    should be based on the performance of at least a 20 percent random 
    sampling of tubes inspected over their full length.
    3.b  Motorized Rotating Pancake Coil (MRPC) Inspection
        MRPC\3\ inspections should be conducted as given below for purposes 
    of obtaining additional characterization of ODSCC flaws found with the 
    bobbin probe and to inspect intersections with significant bobbin 
    interference signals (due to copper, dents, large mix residuals) which 
    may impair the detectability of ODSCC with the bobbin probe or which 
    may unduly influence the bobbin voltage measurement. With respect to 
    ODSCC flaw characterization, a key purpose of the MRPC inspections is 
    to ensure the absence of detectable crack-like circumferential 
    indications and detectable indications extending outside the thickness 
    of the tube support plate. The voltage-based repair criteria are not 
    applicable to intersections exhibiting such indications, and special 
    reporting requirements pertaining to the finding of such indications 
    are described in Section 6.
    ---------------------------------------------------------------------------
    
        \3\For the purposes of this guidance, MRPC also includes the use 
    of comparable or improved nondestructive examination techniques.
    ---------------------------------------------------------------------------
    
        3.b.1  MRPC inspection should be performed for all indications 
    exceeding 1.5 volts as measured by bobbin coil for 2.2 cm [\7/8\-inch] 
    diameter tubes or 1.0 volt as measured by bobbin coil for 1.9 cm [\7/
    8\-inch] diameter tubes.
        3.b.2  The voltage-based criteria of this guidance are not 
    applicable to intersections with copper deposits, dent signals greater 
    than 5 volts, and large mixed residuals.
        3.b.3  All intersections with bobbin coil signals indicative of 
    copper deposits should be inspected with MRPC. Any indications found at 
    such intersections with MRPC should cause the tube to be repaired.
        3.b.4  All intersections with dent signals greater than 5 volts 
    should be inspected with MRPC. Any indications found at such 
    intersections with MRPC should cause the tube to be repaired.
        3.b.5  All intersections with large mixed residuals should be 
    inspected with MRPC. For purposes of this guidance, large mixed 
    residuals are those that could cause a 1-volt bobbin signal to be 
    missed or misread. Any indications found at such intersections with 
    MRPC should cause the tube to be repaired.
        3.b.6  A minimum sample of 100 intersections should be inspected 
    with MRPC to meet the criteria of this part.
    3.c  Data Acquisition and Analysis
        3.c.1  The bobbin coil calibration standard should be calibrated 
    against the reference standard used in the laboratory as part of the 
    development of the voltage-based approach by direct testing or through 
    use of a transfer standard.
        3.c.2  Bobbin coil probes should be calibrated based on four 100 
    percent through-wall holes.
        3.c.3  Once the probe has been calibrated on the 100 percent 
    through-wall hole, the voltage response of new bobbin coil probes for 
    the 20 percent to 80 percent American Society of Mechanical Engineers 
    (ASME) through-wall holes should not differ from the nominal voltage by 
    more than +/-10 percent.
        3.c.4  Probe wear should be controlled by either an inline 
    measurement device or through the use of a periodic wear measurement. 
    When utilizing the periodic wear measurement approach, if a probe is 
    found to be out-of-specification, all tubes inspected since the last 
    successful calibration should be reinspected with the new calibrated 
    probe.
        3.c.5  Data analysts should be trained and qualified in the use of 
    the analyst's guidelines and procedures. Data analyst performance 
    should be consistent with the assumptions for analyst measurement 
    variability (Section 2.b.2(1)) utilized in the tube integrity 
    evaluation (Section 2).
        3.c.6  Quantitative noise criteria (resulting from electrical 
    noise, tube noise, calibration standard noise) should be included in 
    the data analysis procedures. Data failing to meet these criteria 
    should be rejected, and the tube reinspected.
        3.c.7  Data analysts should review the mixed residuals on the 
    standard itself and take action as necessary to minimize these 
    residuals.
        3.c.8  Smaller diameter probes can be used to inspect tubes where 
    it is impractical to utilize a full-sized probe provided that the 
    probes and procedures have been demonstrated on a statistically 
    significant basis to give an equivalent voltage response and detection 
    capability when compared to the full size probe. This demonstration can 
    be done on a plant-specific or generic basis.
    
    4. Tube Removal and Examination/Testing
    
        Implementation of voltage-based plugging criteria should include a 
    program of tube removals for testing and examination as described 
    below. The purpose of this program is to confirm axial ODSCC as the 
    dominant degradation mechanism as discussed in Section 1.a and to 
    provide additional data to enhance the burst pressure, probability of 
    leakage, and conditional leak rate correlations described in Sections 
    2.a.1, 2.b.3(1), and 2.b.3(2), respectively.
    4.a  Number and Frequency of Tube Pulls
        Pulled tube specimens for at least six tube support plate 
    intersections should be obtained for each plant either during the plant 
    steam generator inspection outage that implements the voltage repair 
    limits or during the inspection outage preceding initial application of 
    voltage-based repair criteria. Additional pulled tube specimens should 
    be obtained periodically after the initial application of voltage-based 
    plugging criteria on a frequency of six tube intersections every two 
    steam generator inspections outages. In some cases, it may be necessary 
    for the staff to request plant specific tube pulls due to special 
    circumstances involved with a particular plant specific application of 
    the voltage-based repair limits.
        Alternatively, the request to acquire pulled tube specimens may be 
    met by participating in an industry sponsored tube pull program 
    endorsed by the NRC that meets the objectives of this guidance. Such a 
    program would have to satisfy the following objectives: (1) To confirm 
    the degradation mechanism for plants utilizing the generic letter for 
    the first time, (2) to continue monitoring the ODSCC mechanism over 
    time, and (3) to enhance the burst pressure, probability of leakage, 
    and conditional leak rate correlations. [Note; the industry has 
    proposed such a program in letter dated May 10, 1994, to Brian Sheron, 
    NRC, from David J. Modeen, Nuclear Energy Institute (Reference 5), 
    which is currently under NRC staff review.]
    4.b  Selection Criteria
        Selection of tube pulls should consider the following criteria:
        4.b.1  There should be an emphasis on removing tube intersections 
    with large voltage indications.
        4.b.2  Where possible the removed tube intersections should cover a 
    range of voltages, including intersections with no detectable 
    degradation.
        4.b.3  As a minimum, selected intersections should be such as to 
    ensure that the total data set includes at least a representative 
    number of intersections with MRPC signatures indicative of a single 
    dominant crack as compared to intersections with MRPC signatures 
    indicative of two or more dominant cracks about the circumference.
    4.c  Examination and Testing
        Removed tube intersections should be subjected to leak and burst 
    tests under simulated MSLB conditions to confirm that the failure mode 
    and leakage rates are consistent with that assumed in development of 
    the voltage-based criteria. In addition, these data may be used to 
    enhance the supporting data sets for the burst pressure and leakage 
    correlations subject to NRC review and approval as stated in 4.d, 
    below. Subsequent to burst testing, the intersections should be 
    destructively examined to confirm that the degradation morphology is 
    consistent with the assumed morphology for ODSCC.
    4.d  General Criteria for Burst and Leakage Models and Supporting Test 
    Data
        This guidance allows only the use of NRC approved burst and leakage 
    models and correlations; this includes NRC approval of the data that 
    supports the models and correlations.
    
    5. Operational Leakage Limits
    
        5.a  The operational leakage limit should be reduced to 150 gallons 
    per day (gpd) through each steam generator.
        5.b  Licensees should review their leakage monitoring measures to 
    ensure that should a significant leak be experienced in service, it 
    will be detected and the plant shut down in a timely manner to reduce 
    the likelihood of a potential rupture. Specifically, the effectiveness 
    of these procedures for ensuring the timely detection, trending, and 
    response to rapidly increasing leaks should be assessed. This should 
    include consideration of the appropriateness of alarm set points on the 
    primary-to-secondary leakage detection instrumentation and the various 
    criteria for operator actions in response to detected leakage.
        5.c  Steam generator tubes with known leaks should be repaired 
    prior to returning the steam generators to service following a steam 
    generator inspection outage.
    
    6. Reporting Requirements
    
    6.a  Threshold Criteria for Requiring Prior Staff Approval To Continue 
    With Voltage-Based Criteria
        This guidance allows licensees to implement the voltage-based 
    repair criteria on a continuing basis after the NRC staff has approved 
    the initial TS amendment. However, there are several situations for 
    which the NRC staff must receive prior notification before a licensee 
    can continue with the implemtation of the voltage-based repair 
    criteria:
        6.a.1  If the actual measured voltage distribution would have 
    resulted in an estimated leakage during the previous operating cycle 
    greater than the leakage limit (determined from the licensing basis 
    calculation), then the licensee should notify the NRC of this 
    occurrence and provide an assessment of its significance prior to 
    returning the steam generators to service.
        6.a.2  If (1) indications are identified that extend beyond the 
    confines of the TSP or (2) indications are identified that appear to be 
    circumferential in nature, then the NRC staff should be notified prior 
    to returning the steam generators to service.
        6.a.3  If the calculated conditional probability of burst based on 
    the projected EOC voltage distribution exceeds 1X10-2, licensees 
    should notify NRC and provide an assessment of the significance of this 
    occurrence prior to returning the steam generators to service. This 
    assessment should address the safety significance of the calculated 
    conditional probability.
    6.b  Information To Be Provided Following Each Restart
        The following information should be submitted to the NRC staff 
    within 90 days of each restart following a steam generator inspection:
        (a) The results of metallurgical examinations performed for tube 
    intersections removed from the steam generator.
        (b) The following distributions should be provided in both tabular 
    and graphical form. This information is to enable the staff to assess 
    the effectiveness of the methodology, determine whether the degradation 
    is changing significantly, determine whether the data supports higher 
    voltage repair limits, and to perform confirmatory calculations:
        (i) EOC voltage distribution--all indications found during the 
    inspection regardless of MRPC confirmation
        (ii) Cycle voltage growth rate distribution (i.e., from BOC to EOC)
        (iii) Voltage distribution for EOC repaired indications--
    distribution of indications presented in (i) above that were repaired 
    (i.e., plugged or sleeved)
        (iv) Voltage distribution for indications left in service at the 
    beginning of the next operating cycle regardless of MRPC confirmation--
    obtained from (i) and (iii) above
        (v) Voltage distribution for indications left in service at the 
    beginning of the next operating cycle that were confirmed by MRPC to be 
    crack-like or not MRPC inspected
        (vi) Non-destructive examination uncertainty distribution used in 
    predicting the EOC (for the next cycle of operation) voltage 
    distribution
        (c) The results of the tube integrity evaluation described in 
    Section 2. Note that these calculations must be completed prior to 
    restart to ensure that an adequate number of tubes have been repaired 
    to meet the leakage limit and ensure continued tube integrity.
    
    7. References
    
        1. Letter dated April 22, 1994, to Jack Strosnider, NRC, from David 
    A. Steininger, EPRI, ``Exclusion of Data from Alternate Repair Criteria 
    (ARC) Databases Associated with \7/8\ inch Tubing Exhibiting ODSCC''.
        2. Letter dated June 9, 1994, to Brian Sheron, NRC, from David J. 
    Modeen, Nuclear Energy Institute.
        3. EPRI TR-100407, Revision 1, Draft Report August 1993, ``PWR 
    Steam Generator Tube Repair Limits-Technical Support Document for 
    Outside Diameter Stress Corrosion Cracking at the Tube Support 
    Plates''.
        4. WCAP-12985, Revision 1. ``Kewaunee Steam Generator Tube Plugging 
    Criteria for ODSCC at Tube Support Plates,'' Westinghouse Electric 
    Corporation, January 1993, Westinghouse Proprietary Class 2.
        5. WCAP-13522, ``V.C. Summer Steam Generator Tube Plugging Criteria 
    for Indications at Tube Support Plates,'' Westinghouse Electric 
    Corporation, Westinghouse Proprietary Class 2.
        6. J.P. Adams and C.L. Atwood, ``The Iodine Spike Release Rate 
    During a Steam Generator Tube Rupture,'' Vol. 94, pg. 361, (1991).
    
    Model Technical Specifications
    
        The model technical specifications are based on the ``Standard 
    Technical Specifications (STS) for Westinghouse Pressurized Water 
    Reactors,'' NUREG-0452, Revision 4a. The indicated changes are 
    identified in italics. Note that the model technical specification 
    changes described below also include an example change to reduce 
    reactor coolant system specific activity. The model technical 
    specifications identified below should be adopted consistent with the 
    licensing basis. It should be noted that in the improved STS, some of 
    these surveillance requirements have been relocated to the 
    Administrative Controls section.
    3/4.4.5  Reactor Coolant System
    4/4.5.2  Steam Generator Tube Selection and Inspection
    
    [add the following paragraphs]
    
        b.4. Tubes left in service as a result of application of the tube 
    support plate plugging criteria shall be inspected by bobbin coil probe 
    during all future refueling outages.
    
        d. Implementation of the steam generator tube/tube support plate 
    plugging criteria requires a 100 percent bobbin coil inspection for 
    hot-leg tube support plate intersections and cold-leg intersections 
    down to the lowest cold-leg tube support plate with known outside 
    diameter stress corrosion cracking (ODSCC) indications. The 
    determination of tube support plate intersections having ODSCC 
    indications shall be based on the performance of at least a 20 percent 
    random sampling of tubes inspected over their full length.
    4.4.5.4  Acceptance Criteria
        a. As used in this specification:
        6. Plugging Limit\4\ means the imperfection depth at or beyond 
    which the tube shall be removed from service and is equal to 40 percent 
    of the nominal wall thickness. This definition does not apply to tube 
    support plate intersections for which the voltage-based plugging 
    criteria are being applied. Refer to 4.4.5.4.a.10 for the plugging 
    limit applicable to these intersections.
    ---------------------------------------------------------------------------
    
        \4\For plants that have approved sleeving, ``plugging'' can be 
    replaced with ``repair'' to allow tubes to be either plugged or 
    sleeved when indications exceed applicable repair limits.
    ---------------------------------------------------------------------------
    
        10. Tube Support Plate Plugging Limit is used for the disposition 
    of a steam generator tube for continued service that is experiencing 
    outside diameter stress corrosion cracking confined within the 
    thickness of the tube support plates. At tube support plate 
    intersections, the repair limit is based on maintaining steam generator 
    tube serviceability as described below:
        a. Degradation attributed to outside diameter stress corrosion 
    cracking within the bounds of the tube support plate with bobbin 
    voltage less than or equal to [Note 1] will be allowed to remain in 
    service.
        b. Degradation attributed to outside diameter stress corrosion 
    cracking within the bounds of the tube support plate with a bobbin 
    voltage greater than [Note 1] will be repaired or plugged except as 
    noted in 4.4.5.4.a.10.c below.
        c. Indications of potential degradation attributed to outside 
    diameter stress corrosion cracking within the bounds of the tube 
    support plate with a bobbin voltage greater than [Note 1] but less than 
    or equal to [Note 2] may remain in service if a rotating pancake coil 
    inspection does not detect degradation. Indications of outside diameter 
    stress corrosion cracking degradation with a bobbin voltage greater 
    than [Note 2] volts will be plugged or repaired.
        d. [If applicable] Certain intersections as identified in 
    [reference report] will be excluded from application of the voltage-
    based repair criteria as it is determined that these intersections may 
    collapse or deform following a postulated LOCA + SSE event.
        e. If a result of leakage due to a mechanism other than ODSCC at 
    the tube support plate intersection, or some other cause, an 
    unscheduled mid-cycle inspection is performed, the following repair 
    criteria apply instead of 4.4.5.4.10.c. If bobbin voltage is within 
    expected limits, the indication can remain in service. The expected 
    bobbin voltage limits are determined from the following equation:
    
    TN12AU94.000
    
    where:
    
    V=measured voltage
    VBOC=voltage at BOC
    t=time period of operation to unscheduled outage
    CL=cycle length (full operating cycle length where operating cycle is 
    the time between two scheduled steam generator inspections)
    VSL=4.5 volts for \3/4\-inch tubes and 9.6 volts for \7/8\-inch 
    tubes
    
         Note 1.--1.0 volt for \3/4\-inch diameter tubes or 2.0 volts 
    for \7/8\-inch diameter tubes.
        Note 2.--2.7 volts for \3/4\-inch diameter tubes or 5.6 volts 
    for \7/8\-inch diameter tubes.
    4.4.5.5  Reports
        d. For implementation of the voltage-based repair criteria to tube 
    support plate intersections, notify the staff prior to returning the 
    steam generators to service should any of the following conditions 
    arise:
        1. If estimated leakage based on the actual measured end-of-cycle 
    voltage distribution would have exceeded the leak limit (for the 
    postulated main steam line break utilizing licensing basis assumptions) 
    during the previous operation cycle.
        2. If circumferential crack-like indications are detected at the 
    tube support plate intersections.
        3. If indications are identified that extend beyond the confines of 
    the tube support plate.
        4. If the calculated conditional burst probability exceeds 
    1 x 10-2, notify the NRC and provide an assessment of the safety 
    significance of the occurrence.
    Reactor Coolant system
    3/4.4.6  Reactor Coolant System Leakage
        3.4.6.2  Reactor Coolant System leakage shall be limited to:
        a. No Pressure boundary Leakage,
        b. 1 GPM UNIDENTIFIED LEAKAGE,
        c. Primary-to-secondary leakage through all steam generators shall 
    be limited to 150 gallons per day through any one steam generator,
        d. 10 GPM IDENTIFIED LEAKAGE from the Reactor Coolant System, and
        3. ____ GPM CONTROLLED LEAKAGE at a Reactor Coolant System pressure 
    of 2235 +/- 20 psig.
        f. 1 GPM leakage at a Reactor Coolant System pressure of 2235 +/- 
    20 psig from any Reactor Coolant System Pressure Isolation Valve 
    specified in Table 3.4-1.
        For licensees who want to reduce RCS specific iodine activity, the 
    following TS pages apply:
    Reactor Coolant System
    3/4.4.8  Specific Activity
        3.4.8  The specific activity of the primary coolant shall be 
    limited to:
        a. Less than or equal to [reduced value] microcurie per gram DOSE 
    EQUIVALENT I-131, and
        b. Less than or equal to 100/E microcuries per gram.
        APPLICABILITY: MODES 1, 2, 3, 4, and 5.
        ACTION:
        MODES 1, 2, AND 3*:
        a. With the specific activity of the primary coolant greater than 
    [reduced value] microcurie per gram DOSE EQUIVALENT I-131 for more than 
    48 hours . . .
    * * * * *
        MODES 1, 2, 3, 4, and 5:
        a. With the specific activity of the primary coolant greater than 
    [reduced value] microcurie per gram DOSE EQUIVALENT I-131 or greater
         [Revised Figure 3.4-1 to lower the line by a factor corresponding 
    to the reduction in specific activity. The lowered line should parallel 
    the original]
    Reactor Coolant System
    BASES
    3/4.4.5  STEAM GENERATORS
        [To be provided in the final generic letter]
    
        Dated at Rockville, Maryland, this 8th day of August 1994.
    
        For the Nuclear Regulatory Commission.
    Elizabeth L. Doolittle,
    Acting Chief, Generic Communications Branch, Division of Operating 
    Reactor Support, Office of Nuclear Reactor Regulation.
    [FR Doc. 94-19721 Filed 8-11-94; 8:45 am]
    BILLING CODE 7590-01-M
    
    
    

Document Information

Published:
08/12/1994
Department:
Nuclear Regulatory Commission
Entry Type:
Uncategorized Document
Action:
Notice of opportunity for public comment.
Document Number:
94-19721
Dates:
Comment period expires September 12, 1994. Comments submitted after this date will be considered if it is practical to do so, but assurance of consideration cannot be given except for comments received on or before this date.
Pages:
0-0 (1 pages)
Docket Numbers:
Federal Register: August 12, 1994