95-20021. Customer-Owned Service Lines  

  • [Federal Register Volume 60, Number 156 (Monday, August 14, 1995)]
    [Rules and Regulations]
    [Pages 41821-41828]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 95-20021]
    
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    DEPARTMENT OF TRANSPORTATION
    
    Research and Special Programs Administration
    
    49 CFR Part 192
    
    [Docket PS-135; Amdt. 192-3]
    RIN 2137-AC32
    
    
    Customer-Owned Service Lines
    
    AGENCY: Research and Special Programs Administration (RSPA), DOT.
    
    ACTION: Final rule.
    
    -----------------------------------------------------------------------
    
    SUMMARY: This action requires operators of gas service lines who do not 
    maintain buried customer piping up to building walls or certain other 
    locations to notify their customers of the need to maintain that 
    piping. Congress directed DOT to take this action in view of service 
    line accidents. By advising customers of the need to maintain their 
    buried gas piping, the notices may reduce the risk of further 
    accidents.
    
    EFFECTIVE DATE: September 13, 1995.
    
    FOR FURTHER INFORMATION CONTACT: L. M. Furrow, (202) 366-2392, 
    regarding the content of this document, or the Dockets Unit (202) 366-
    4453 for copies of this final rule or other material in the docket.
    
    SUPPLEMENTARY INFORMATION:
    
    I. Background
    
    A. Customer Piping
    
        RSPA's gas pipeline safety standards (49 CFR Part 192) apply to the 
    distribution of gas up to the end of a pipeline operator's service 
    line. A service line, as defined in Sec. 192.3, is a distribution line 
    that begins at a common source of supply, usually a main, transmission 
    line, or gathering line. The end of a service line is a customer meter 
    or a connection to a customer's piping, whichever is farther 
    downstream. If there is no meter, the connection to a customer's piping 
    marks the end of a service line. A customer is any person who contracts 
    with an operator to receive gas for consumption. Customer's piping (or 
    customer piping) refers to piping not owned by an operator through 
    which a customer receives gas.
        When operators install customer meters, they usually install them 
    outdoors next to the building that houses the customer's principal gas 
    utilization equipment. If that equipment is not inside a building, the 
    meter may be installed next to the equipment. Either of these 
    installations may leave only a short segment of exterior customer 
    piping between the end of the operator's service line and the building 
    or equipment. Sometimes, however, operators install customer meters 
    farther away from buildings or equipment, perhaps at a private property 
    line or fence. The result is a much longer length of exterior customer 
    piping.
        Regardless of length, customer piping downstream from an operator's 
    service line is not subject to the maintenance standards of Part 192. 
    However, according to the National Transportation Safety Board, twenty-
    two states now require operators to monitor portions of customer 
    piping. Also, many operators voluntarily maintain customer piping up to 
    building walls. Still, for much customer piping, maintenance is the 
    responsibility of customers or piping owners, not operators of service 
    lines. In this regard, RSPA is preparing a report on the safety of 
    customer piping located downstream from service lines to see if there 
    is a need for further legislative or regulatory action. The report is 
    required by section 115(b) of the Pipeline Safety Act of 1992 (Pub. L. 
    102-508; 106 Stat. 3296).
    B. Statutory Mandate
    
        During a 7-month period beginning September 16, 1988, a series of 
    five service line accidents killed four people and injured 16 others in 
    Kansas and Missouri. The accidents happened on service lines supplying 
    gas to homes and were due to corrosion and other causes. As a result, 
    Congress became concerned about the safety of gas piping leading up to 
    buildings. Congress felt that customers of distribution pipeline 
    operators may not understand the need for basic maintenance of customer 
    piping.
        Therefore, as provided by 49 U.S.C. Sec. 60113(a) (formerly section 
    18(b) of the 
    
    [[Page 41822]]
    Natural Gas Pipeline Safety Act of 1968), Congress directed DOT to--
    
        Prescribe regulations requiring an operator of a natural gas 
    distribution pipeline that does not maintain customer-owned natural 
    gas service lines up to the building walls to advise its customers 
    of--
        (1) the requirements for maintaining those lines;
        (2) any resources known to the operator that could assist 
    customers in carrying out the maintenance;
        (3) information the operator has on operating and maintaining 
    its lines that could assist customers; and
        (4) the potential hazards of not maintaining the lines.
    
    C. Rulemaking Proposal
    
        In response to this Congressional mandate, RSPA published a notice 
    of proposed rulemaking (NPRM)(59 FR 5168; February 3, 1994) on customer 
    notification. The NPRM proposed to define the piping covered by the 
    mandate (``covered piping''). The NPRM also proposed to establish the 
    details of advice that operators who do not maintain covered piping up 
    to building walls would have to give their customers.
        In a supplemental notice of proposed rulemaking (SNPRM)(59 FR 
    13300; March 21, 1994), RSPA expanded the proposed rules to cover 
    certain exterior customer piping that is above ground. The SNPRM also 
    clarified that the proposed rules were not limited to operators who are 
    local distribution companies. Other operators (primarily transmission 
    companies) that supply gas to customers through service lines were 
    covered as well. RSPA also announced in the SNPRM that the proposed 
    rules did not apply to customer piping that branches from a customer's 
    primary gas supply line to supply gas to secondary equipment, such as 
    pool heaters and yard lanterns.
    
    D. Advisory Committee Review
    
        RSPA presented the NPRM and SNPRM for deliberation by the Technical 
    Pipeline Safety Standards Committee (TPSSC) at a meeting in Washington, 
    D.C. on May 11, 1994. TPSSC is RSPA's statutory advisory committee for 
    gas pipeline safety. The committee comprises 15 members, representing 
    industry, government, and the public, who are technically qualified to 
    evaluate gas pipeline safety. TPSSC's report of its deliberation is 
    available in the docket of this proceeding.
        TPSSC voted unanimously to find the proposed rules technically 
    feasible, reasonable, and practicable, provided RSPA made the following 
    changes: (1) delete information on age, location, and material of 
    customer piping from proposed Sec. 192.16(a)(4); (2) when customer 
    piping does not enter a building, end covered piping at the point of 
    custody transfer; (3) apply the proposed rule only to buried 
    residential and small-commercial lines; and (4) delete ``transmission 
    or'' from proposed Sec. 192.16(a) to limit the rule to distribution 
    operators. The next section discusses how we handled TPSSC's 
    recommended changes in developing the final rule.
    
    II. Discussion of Comments and TPSSC Recommendations
    
    A. Commenters
    
        We received written comments from 57 persons in response to the 
    NPRM and SNPRM. The comments came from: 47 pipeline operators; 5 state 
    pipeline safety agencies (Maryland, Kansas, Iowa, Michigan, and 
    Missouri); 4 trade associations (American Gas Association (AGA), 
    Interstate Natural Gas Association of America (INGAA), Western 
    Mobilehome Parkowners Association (WMPA), and Texas Gas Association 
    (TGA)); and 1 federal agency (National Transportation Safety Board 
    (NTSB)).
        Most commenters directed their remarks to specific issues. This 
    section of the preamble discusses our resolution of significant issues 
    in light of comments and TPSSC recommendations.
    
    B. The Term ``Customer-Owned Service Line''
    
        The mandate applied to customer piping Congress called ``customer-
    owned service lines.'' So the NPRM and SNPRM used this term to 
    designate the customer piping covered by the proposed rules.
        Despite its statutory origin, many commenters felt the term 
    ``customer-owned service line'' would be confusing in a Part 192 
    regulation. They said many service lines under Part 192 include piping 
    owned by customers. Consequently, they argued the term was too similar 
    to ``service line'' to distinguish customer piping not regulated by 
    Part 192 from service lines regulated by Part 192. The commenters 
    suggested as alternatives the names ``supply pipe,'' ``yard line,'' 
    ``fuel line,'' and ``customer-owned piping.''
        We agree that ``customer-owned service line'' would be a misnomer 
    in Part 192. The term could easily be confused with ``service line,'' 
    because some customers own the portion of a service line on private 
    property between a distribution main and customer meter. Also, other 
    customers (particularly tenants) may not own any of the piping through 
    which they receive gas from an operator. For these reasons, we did not 
    use the term ``customer-owned service line'' in the final rule.
        At the same time, we did not name covered piping as commenters 
    suggested. Since Part 192 currently refers to piping beyond the end of 
    a service line as ``customer's piping'' (see Sec. 192.3, service line), 
    referring to that piping by another name would be confusing. Instead, 
    to designate piping covered by the final rule, we used ``customer's 
    piping'' with other descriptive wording (Sec. 192.16(a)).
    
    C. End of Covered Piping
    
        To delineate the customer piping covered by the proposed rules, the 
    NPRM and SNPRM defined the term ``customer-owned service line.'' The 
    definition proposed was: ``a pipeline that transports natural gas or 
    petroleum gas from a service line to (1) an exterior wall of a 
    building, or (2) end-use equipment'' (proposed amendment to 
    Sec. 192.3).
        Most commenters thought the proposed end of covered piping was 
    unclear. One concern was the end of covered piping when customer piping 
    leads to more than one building. Another concern was the end when 
    customer piping leads both to a building and to outdoor equipment, such 
    as a lantern. Still another concern was the end when customer piping 
    does not enter a building, which happens at some plants. In regard to 
    plants, AGA argued the end should be at a location equivalent to a 
    building wall, such as the plant fence or point of custody transfer. 
    Similarly, TPSSC recommended ending covered piping at a custody 
    transfer point when there is no building.
        As stated above, we intended the proposed rules to apply to 
    customers' primary gas supply lines. Branch lines that serve pool 
    heaters, yard lanterns, or other types of secondary equipment were not 
    intended to be covered. The final rule (Sec. 192.16(a)) clarifies this 
    point by covering customer piping up to gas utilization equipment only 
    when the customer's piping does not enter a building. Also, to avoid 
    the confusion of where covered piping ends when customer piping enters 
    more than one building, the final rule refers to the first building. We 
    used the term ``gas utilization equipment'' instead of ``end-use 
    equipment'' for consistency with present terminology in Part 192 (e.g., 
    Sec. 192.197(a)(5)).
        When customer piping does not enter a building, we agree that a 
    perimeter fence (or wall) surrounding the gas utilization equipment 
    serves the 
    
    [[Page 41823]]
    purpose of a building wall under the mandate. Thus, when there is no 
    building, under the final rule, covered piping ends at the gas 
    utilization equipment or at the intersection of the first fence (or 
    wall) that encloses the equipment (if such a fence (or wall) exists). 
    The fence (or wall) may surround the plant, part of the plant, or just 
    the equipment.
        We did not adopt custody transfer to demarcate the end of covered 
    piping when customer piping does not enter a building. Because custody 
    transfer arguably occurs when gas enters piping not owned by the 
    operator, none of the customer piping downstream from a service line 
    would come under the notification rule.
    D. Aboveground Customer Piping and Short Sections of Piping Between 
    Meters and Buildings
    
        Many commenters, including AGA and Missouri, recommended that the 
    final rule apply only to buried piping. Generally, the commenters felt 
    that aboveground piping presents less risk than buried piping. The 
    commenters said operators or customers would see any deteriorated 
    piping or they would smell any leaks. Further, the commenters 
    envisioned that any leaks would go directly to the atmosphere and not 
    migrate into a building. TPSSC also recommended that we limit the final 
    rule to buried piping.
        The chief reason, however, that most commenters wanted to restrict 
    the final rule to buried piping was to reduce the number of customers 
    that would have to be notified. This point was emphasized by AGA at the 
    TPSSC meeting, convincing TPSSC to overturn an earlier vote against 
    excluding aboveground piping. Millions of additional customers would 
    have to be notified if aboveground piping were covered, since most 
    service lines, including lines that end at meters next to buildings, 
    connect to short sections of aboveground piping. For example, one 
    operator said it would have to send 1.3 million notices if the rule 
    covered aboveground piping, compared with 68,000 notices if only buried 
    piping were covered. This operator argued that since the accidents that 
    produced the mandate all involved buried piping, Congress did not 
    intend the mandate to cover aboveground piping. In addition, according 
    to WMPA, if the rule covered aboveground short sections of piping, it 
    would affect most of the 2,950 mobilehome parks in California with 
    master meter systems. WMPA said mobilehomes in these parks are usually 
    connected to gas meters by short flexible pipe that is the 
    responsibility of the mobilehome owner. WMPA recommended that the final 
    rule not apply to aboveground piping less than 6 feet long.
        We too were concerned about the impact of the proposed rules on 
    short sections of piping between customer meters and buildings. So, in 
    the NPRM and SNPRM, we asked for public comment on whether these short 
    sections of piping are properly installed and periodically maintained. 
    One operator commented that trained operator or heating contractor 
    personnel install the short sections. Another operator said 
    installation is done according to the National Fuel Gas Code, interior 
    gas piping standards produced by the American National Standards 
    Institute and the National Fire Protection Association. Several 
    operators said that short sections seldom or never leak. A few 
    operators reported they periodically inspect short sections for leaks 
    and advise customers of any problems. However, one operator said it 
    does not check commercial or industrial piping. Two other operators 
    said they check for leaks when they turn gas on or when they receive 
    leak reports. WMPA commented that leak surveys normally include the 
    customer's connector pipe, and that mobilehome owners are advised of 
    any needed repairs.
        These comments and the TPSSC recommendation convinced us that 
    aboveground customer piping should not be regarded as covered piping. 
    First of all, we recognize that if aboveground piping were covered, 
    almost every gas customer in the U.S. would have to be notified. And 
    there is no evidence that a notification program of this magnitude 
    would result in a comparable increase in public safety. Nor do we think 
    Congress contemplated a huge, nationwide notification program. Although 
    the mandate arguably applies to any customer piping up to building 
    walls, the fact that the accidents that led to the mandate happened on 
    buried service lines means it is reasonable to conclude that Congress 
    intended the mandate to cover only buried customer piping. This 
    conclusion is congruous with the risks involved, because as the 
    comments indicate, aboveground customer piping poses much less risk 
    than buried customer piping. Therefore, the final rule applies only to 
    buried piping (Sec. 192.16(a)). As a result, short sections of customer 
    piping between customer meters and building walls that are entirely 
    aboveground are not covered by the final rule.
    
    E. Farm Taps and Industrial Taps
    
        The proposed rules applied to customers served by ``farm taps'' or 
    ``industrial taps.'' Farm tap is industry jargon for a pipeline that 
    branches from a transmission or gathering line to deliver gas to a 
    farmer or other landowner. Similarly, an industrial tap is a pipeline 
    that branches from a transmission or gathering line to deliver gas to 
    an industrial plant. So companies primarily engaged in the transmission 
    or gathering of gas operate most farm taps and industrial taps.
        About a third of commenters argued against this proposal, saying 
    that Congress intended the mandate to apply only to local distribution 
    companies. In support, they pointed out that residential accidents 
    prompted the mandate. They also said that customers served by farm and 
    industrial taps are more likely than residential customers to be 
    familiar with the need to maintain gas piping. In this regard, a gas 
    production company said its lease agreements with farm tap customers 
    make them aware of their responsibility for maintenance. TPSSC also 
    recommended that we limit the final rule to distribution operators and 
    to residential and small commercial customers.
        We do not believe these arguments and TPSSC recommendations justify 
    excluding farm tap and industrial tap customers from the final rule. To 
    begin with, while we recognize that Congress was primarily concerned 
    about residential customers, the mandate is not so limited. Congress 
    applied the mandate to ``operators of natural gas distribution 
    pipelines.'' But these operators are not just local distribution 
    companies as the commenters suggested. Some operators primarily engaged 
    in the gathering or transmission of gas also operate distribution 
    pipelines. They do so when they deliver gas directly to customers 
    through farm taps and industrial taps. In fact, because portions of 
    these delivery lines qualify as service lines, gathering and 
    transmission operators report them as distribution pipelines under 49 
    CFR 191.13. Moreover, farm and industrial tap customers are not immune 
    from harm by potential hazards that could occur on their piping. And 
    surely not all farm and industrial tap customers know enough about gas 
    piping safety to make even a single maintenance notice unnecessary.
        Therefore, application of the final rule does not depend on the 
    nature of an operator's primary business. To clarify this point, we 
    reworded the final rule (Sec. 192.16(a)) so that it applies to 
    operators of service lines, instead of transmission or distribution 
    operators as proposed. Although this change made it unnecessary to 
    define ``farm tap'' or 
    
    [[Page 41824]]
    ``industrial tap,'' operators of these taps are not excepted from the 
    final rule.
        We recognize that local distribution companies operate some metered 
    farm taps on transmission lines. In these cases, the local distribution 
    company is responsible for compliance with the final rule.
    
    F. Meaning of ``Maintain''
    
        The mandate applies to operators who do not ``maintain'' customer 
    piping up to building walls. What Congress meant by ``maintain'' is 
    important, because operators who maintain customer piping up to 
    building walls need not advise customers of the need for maintenance. 
    Because ``maintain'' is inexact, the NPRM and SNPRM proposed to clarify 
    the mandate by giving ``maintain'' a particular meaning: ``maintain * * 
    * to Part 192 standards'' (proposed Sec. 192.16(a)).
        Commenters thought the standards in Part 192 were not an 
    appropriate gauge of whether an operator maintains covered piping as 
    Congress had in mind. One operator put it this way: while it may be 
    reasonable to conduct a leakage survey every 3 years (under 
    Sec. 192.723) up to the nearest building wall and, if a leak is 
    detected, shut off the flow of gas, it would not be reasonable to 
    maintain a customer's piping to meet all Part 192 maintenance 
    standards. Another operator thought the proposal was unreasonable 
    because it would require operators to send notices to customers even if 
    operators maintain covered piping according to State requirements, but 
    not to Part 192.
        RSPA agrees that operators would have difficulty meeting Part 192 
    maintenance standards on covered piping. Operators may lack permission 
    from property owners to take maintenance action or lack the necessary 
    information upon which to base maintenance action. For example, under 
    Sec. 192.725, each disconnected service line must be pressure tested as 
    a new line. Yet operators probably would need access to the customer's 
    building and other permission from the customer or property owner to do 
    this test on a customer's piping. Another example is Sec. 192.455(a), 
    which provides that each buried pipeline installed after July 31, 1971, 
    must be protected against external corrosion. This regulation presumes 
    operators know the installation date of their pipelines, a fact they 
    may not know for a customer's piping.
        Upon further consideration, we are defining ``maintain'' to mean 
    whatever maintenance is reasonable for operators to do on covered 
    piping, considering the Congressional intent. Although the legislative 
    history casts little light on what Congress meant by ``maintain,'' it 
    does show that Congress was concerned about corrosion-related accidents 
    on service lines.
        Preventing and correcting hazardous leaks are the major safety 
    reasons to maintain gas pipelines. The comments show that many 
    operators already check customer piping between customer meters and 
    building walls for leaks. Some operators may check for leaks while 
    doing routine leakage surveys on their own pipelines under 
    Sec. 192.723. If a leak is found, depending on the nature of the leak, 
    they either shut off the flow of gas or warn the customer to repair the 
    leak.
        Besides leakage checks, another reasonable maintenance activity is 
    to monitor customer piping for corrosion, a major cause of leaks on 
    metallic pipelines. More specifically, operators must periodically 
    monitor their buried metallic service lines for external corrosion 
    under Sec. 192.465. With permission from the land owner or tenant, 
    operators could also monitor covered piping according to this standard. 
    However, rather than take the specified remedial action, which might be 
    difficult to do on covered piping, they could shut off the flow of gas 
    or warn the customer to repair any harmful corrosion found.
        Considering the reasons for maintenance, Congress's concern about 
    corrosion, present industry practices, and commenters' advice, we 
    believe ``maintain'' means periodic checking for leaks and corrosion, 
    with appropriate follow-up action. Thus, the final rule 
    (Sec. 192.16(a)) provides that operators who do not maintain covered 
    piping according to Sec. 192.465 (if applicable) and Sec. 192.723, with 
    appropriate remedial action, must send the customer a maintenance 
    notice.
        In accordance with Executive Order 12898 on Environmental Justice, 
    we have considered the potential effect of this final rule on minority 
    and low income customers. Because the rule applies only to gas 
    operators who do not inspect certain customer piping, the rule will not 
    impose direct costs on gas customers. However, some customers may incur 
    indirect costs of the rule. Customers who own exterior gas piping and 
    decide to heed the gas company's maintenance advice could face large 
    repair bills, depending on the condition and amount of their piping. 
    Indirect costs can also arise when operators who inspect customer-owned 
    piping discover that it is leaking or otherwise unsafe and require 
    customers to repair the piping if gas service is to continue.
        We cannot predict which customers would be likely to incur these 
    indirect costs. However, the proportion of minority and low income 
    customers that might incur them should be small, because most minority 
    and low income gas customers are tenants. As tenants, they can 
    reasonably be expected to refer the matter of piping maintenance or 
    unsafe piping to their landlords, who are responsible for corrective 
    action.
        When minority and low income customers must bear the indirect costs 
    themselves, voluntary organizations and local welfare agencies can 
    reasonably be expected to provide assistance, especially in response to 
    gas shut off situations if the health of customers is affected. In 
    addition, we expect that states adopting this final rule will monitor 
    its effect on minority and low income gas customers and find additional 
    ways to lessen the indirect cost burden. For example, states may 
    require operators to stand the cost of maintenance or establish a fund 
    to pay for maintenance that minority and low-income customers cannot 
    afford.
        Despite the potentially low impact of this final rule on minority 
    and low income customers as a whole and efforts to defray indirect 
    costs, the cost of piping maintenance will unavoidably be a hardship 
    for some minority and low income customers. Still, in view of the high 
    safety risk of deteriorating residential gas piping and Congress's 
    mandate that operators warn customers about this potential problem, we 
    see no federal regulatory alternative that would lessen the potential 
    cost burden. We will, however, examine this issue further in the report 
    to Congress on the safety of customer-owned service lines that is 
    required by section 115(b) of the Pipeline Safety Act of 1992 (Public 
    Law 102-508, 106 Stat. 3296).
    G. Customer Responsibility
    
        The NPRM and SNPRM proposed that operators who do not maintain 
    covered piping must notify the customer that ``the customer owns and is 
    responsible for the maintenance of the customer-owned service line'' 
    (proposed Sec. 192.16(a)(1)). The purpose of this proposal was to alert 
    customers that the operator does not maintain the customer's piping.
        AGA and several operators pointed out that customers who occupy 
    rental properties, especially commercial buildings, may not own the 
    piping through which they receive gas. Other commenters observed that 
    operators may not know who owns the customer's piping. One solution a 
    commenter suggested was that the notice advise 
    
    [[Page 41825]]
    rental customers to refer the maintenance advice to the landlord.
        Another consideration, not raised by commenters, is that many 
    states now require operators to do some maintenance on customer piping. 
    In these states, it would be incorrect for operators to notify 
    customers that the customers or their landlords are responsible for 
    maintenance of customer piping.
        Thus, it appears the proposal could be confusing or incorrect in 
    some circumstances if included in maintenance notices. To avoid this 
    confusion, the final rule (Sec. 192.16(b)(1)) merely requires operators 
    to notify customers that the operator does not maintain the customer's 
    piping.
        Some operators may do a level of maintenance on customer piping 
    (either voluntarily or under State law) that does not reach the minimum 
    level prescribed by the final rule. If these operators wish to avoid 
    advising customers that they do not maintain customer piping, they 
    would have to increase their maintenance to the minimum level.
    
    H. Requirements for Maintenance
    
        Under the mandate, operators who do not maintain covered piping 
    must advise their customers of the requirements for maintenance of that 
    piping. To carry out this feature of the mandate, the NPRM and SNPRM 
    proposed that operators notify customers ``of the essential elements 
    for proper maintenance * * * such as those listed in subpart M of [Part 
    192] or those listed in applicable local building codes'' (proposed 
    Sec. 192.16(a)(2)).
        Many commenters, including Iowa, Michigan, AGA, and TGA, 
    recommended that the final rule not refer to Part 192 or local codes as 
    examples of the essential elements of maintenance. The objection 
    expressed most often was that Subpart M of Part 192 is not appropriate 
    for customer piping downstream from meters; it was written for 
    operators, not customers. Commenters also said the proposed rule was 
    indefinite about which sections in Subpart M to apply to customer 
    piping. Several commenters said that Subpart M and the local codes may 
    conflict with each other, forcing operators to choose which standard is 
    appropriate for customers to follow. One commenter stated it would be 
    unreasonable to require operators to learn the essential elements of 
    local building codes applicable to maintenance of customer piping and 
    then send that information to each customer. For example, one large 
    distribution company said it would be especially burdensome to examine 
    the details of local codes in the 535 cities, towns, and communities it 
    serves, and to continually keep abreast of them.
        Alternatively, INGAA and an operator suggested that the final rule 
    specify the maintenance advice operators are to give customers, instead 
    of leaving it to the operator's discretion. INGAA said this approach 
    would minimize the potential liability for giving inappropriate advice. 
    The operator said it would reduce the confusion of different operators 
    giving different advice to similar customers. Two operators thought we 
    should limit the maintenance advice to periodic leakage surveys. Also, 
    two other operators advised us to mention corrosion control as an 
    example of essential maintenance.
        We believe Congress used the word ``requirements'' in the sense of 
    actions that are necessary for maintenance, rather than required by law 
    for maintenance. So we proposed that operators use local codes, Subpart 
    M of Part 192, or other sources as a guide to identify essential 
    elements of maintenance. Although many commenters interpreted the 
    proposal to the contrary, we did not intend for operators to keep 
    abreast of local code requirements applicable to maintenance of 
    customer piping. Nor did we intend for notifications to bring customers 
    up to date about their obligations under local law.
        We recognize, though, that the proposed rules gave operators wide 
    latitude to decide what maintenance advice to provide customers. We 
    also recognize that confusion could result if operators gave different 
    advice in similar situations. So we adopted the suggestion to specify 
    essential maintenance advice. We based the specified maintenance advice 
    on the recommendations of commenters and the decision discussed above 
    on the meaning of ``maintain.'' Since the specified maintenance advice 
    is commonly found in pipeline safety programs, we doubt it conflicts 
    with local codes.
        Consequently, the final rule (Sec. 192.16(b)(3)(i)-(iii)) does not 
    require notice of any provisions of Subpart M of Part 192 or of any 
    local code requirements. It simply requires operators to notify 
    customers that their buried gas piping should be periodically inspected 
    for leaks; periodically inspected for corrosion, if the piping is 
    metallic; and repaired if any unsafe condition is found. By referring 
    to buried piping, the notice will encourage customers to apply the 
    advice to any buried piping they may have besides their primary supply 
    line.
    
    I. Maintenance Assistance
    
        The mandate requires that operators advise customers of any 
    resources known to the operator that could assist customers in carrying 
    out maintenance. In response, we proposed that operators notify 
    customers ``of available resources that could aid the customer in 
    obtaining maintenance assistance, such as the gas pipeline operator, 
    the state licensing board for plumbers and state plumbers' 
    associations, Federal and state gas pipeline safety organizations, the 
    local building code agencies, and appropriate leak detection, gas 
    utility, and corrosion protection contractors'' (proposed 
    Sec. 192.16(a)(3)).
        Many commenters said it would be too burdensome to maintain current 
    lists of agencies, associations, and contractors over wide areas. They 
    said customers could easily find maintenance assistance by consulting 
    the local better business bureau or chamber of commerce. A few 
    commenters were concerned the proposed rule would cause suits to be 
    filed against the operator for unfair competition if notices omitted 
    appropriate contractors, or for negligence if recommended contractors 
    caused injuries or did unsatisfactory work. One commenter thought the 
    proposed rule was unfair because it would force operators to refer 
    customers to businesses that compete with the operators to provide 
    maintenance services on gas piping.
        In view of these comments, we decided to require operators to give 
    only general advice about maintenance assistance. Operators need not 
    maintain lists of specific contractors that might do maintenance work 
    on customer piping. Although government agencies probably could advise 
    customers about State or local laws, this advice probably would not be 
    helpful in carrying out maintenance. Instead of advising inquirers 
    about the details of maintenance, agencies and associations probably 
    would refer them to contractors. Since customers can learn the names of 
    contractors through the yellow pages or local chambers of commerce, the 
    final rule does not require notice of specific contractors, agencies, 
    or associations. The rule (Sec. 192.16(b)(5)) simply requires notice 
    that the operator (if applicable), plumbers, and heating contractors 
    may be contacted for assistance in maintaining and locating the 
    customer's piping. Under this rule, if an operator does not offer such 
    assistance, it would not have to mention itself as a possible source of 
    assistance. At the same time, an operator may not mention only itself 
    
    [[Page 41826]]
    as a source of assistance on customer piping.
    J. Other Helpful Information
    
    1. General
        The mandate requires that operators provide information the 
    operator has on operating and maintaining its lines that could assist 
    customers. In turn, we proposed that operators notify customers of 
    ``any information that the operator has concerning the operation and 
    maintenance of the customer-owned service line that could aid the 
    customer, such as information on excavation damage prevention, local 
    codes and standards (when applicable), and the age, location, and 
    material of the customer-owned service line'' (proposed 
    Sec. 192.16(a)(4)).
    2. Age, Location, and Material
        TPSSC and about a third of commenters urged us not to require 
    operators to provide information about the age, location, and material 
    of customer piping. Several commenters said that because the 
    information was site specific, operators could not use a notice 
    generally applicable to all customers, as contemplated in the NPRM. 
    Others said operators typically do not have the proposed information 
    about customer piping, and it would be an undue burden to get it. A 
    number of commenters also pointed out that the age of customer piping 
    may not correspond to the date the operator established gas service, 
    because the customer may have replaced or altered the piping since that 
    date.
        We agree that operators may not have the proposed information about 
    customer piping, since they are not required by Part 192 to maintain 
    the piping. Also, obtaining the information would be a significant 
    burden that Congress did not intend operators to assume. The mandate 
    requires operators to give customers helpful information based on the 
    operation and maintenance of the operator's pipelines. The mandate does 
    not require operators to gather information about customer piping. Even 
    when operators do have some information about customer piping, 
    requiring them to add the information to notices might not allow the 
    operators to use a general notice to meet the notification rule. 
    Therefore, this final rule does not require operators to notify 
    customers of the age, location, and material of customer piping.
        As a result, operators may send each customer a notice on the 
    proper maintenance of customer piping in general. Notices need not be 
    tailored to meet specific customer situations. However, operators who 
    have specific information about customer piping and wish to include it 
    in notices are encouraged to do so.
    3. Local Laws
        For reasons discussed above concerning proposed Sec. 192.16(a)(2), 
    several commenters suggested that the final rule not make operators 
    responsible for advising customers about local laws. Since local 
    building codes would be burdensome for operators to track, are the 
    responsibility of local agencies to enforce, and are unlikely to 
    contain instructions on how to carry out piping maintenance, the final 
    rule does not require notice of local laws.
    4. Excavation Damage Prevention
        Two operators asked us to clarify the information they would have 
    to provide about excavation damage. They suggested the notice stress 
    the need to locate piping before excavating and to dig with care.
        We agree that this information would be helpful to customers, 
    because of the large number of gas pipeline accidents attributable to 
    excavation damage. The final rule (Sec. 192.16(b)(4)) reflects these 
    comments. However, operators are not required to notify customers to 
    contact ``one-call'' systems to learn the location of buried customer 
    piping before excavating. One-call systems provide such service only 
    for piping of companies that are members of the system. One-call 
    systems generally have no information regarding customer piping.
        Apart from the maintenance requirements discussed above, 
    information about preventing excavation damage is probably the most 
    significant information operators have about operating and maintaining 
    their own pipelines that would be helpful to customers. In the interest 
    of producing a general notice limited to basic advice, the final rule 
    does not require notice of any other information related to operation 
    and maintenance of the operator's pipelines. However, operators may 
    supplement the required information as they deem appropriate.
    
    K. Potential Hazards
    
        The mandate requires that operators notify customers about the 
    potential hazards of not maintaining customer piping. As proposed in 
    the NPRM and SNPRM, operators would have to advise customers of ``the 
    potential hazards of not maintaining the customer-owned service line, 
    such as corrosion and gas leakage'' (proposed Sec. 192.16(a)(5)).
        Only a few commenters addressed this proposal. Two commenters 
    thought it would be unfair if operators had to warn their customers 
    that gas piping can be hazardous, while their competitors, fuel oil and 
    electric companies, do not have to give a similar warning. One 
    commenter said that sending notices about potential hazards would not 
    be compatible with the goal of market expansion. Another commenter 
    requested that in the final rule, we insert ``reasonably foreseeable'' 
    before ``potential hazard.''
        Although we do not have discretion under the mandate not to require 
    notice of potential hazards, we did not find the arguments against such 
    notice persuasive. The risks involved in using fuel oil and electricity 
    have not demanded the same level of public attention as gas pipeline 
    risks. So, from a public policy standpoint, it is not unfair if only 
    gas pipeline operators must warn their customers of risks. Also, we do 
    not agree that warning customers of potential hazards is incompatible 
    with business expansion. Part 192 already requires operators to post 
    signs over their pipelines warning of potential danger (Sec. 192.707), 
    and to educate the public to recognize gas pipeline emergencies 
    (Sec. 192.615). These programs and the abundant advertisements about 
    using ``one call'' systems to guard against the hazards of excavation 
    damage have, to our knowledge, not adversely affected the growth of 
    business. Indeed, we believe people prefer to do business with socially 
    responsible companies that do not hesitate to publicize information 
    that could help prevent accidents. Finally, to qualify ``potential 
    hazard'' the way one commenter suggested would not enhance the clarity 
    of the final rule.
        The proposal concerning notice of potential hazards is adopted in 
    this final rule as Sec. 192.16(b)(2)--the second item in the list of 
    information to be provided, rather than the last item, as proposed. 
    This rearrangement encourages operators to warn customers of potential 
    hazards at the beginning of notices instead of at the end. A notice may 
    mention just two potential hazards: corrosion and leaks. Most 
    commenters referred to these potential hazards in response to the 
    proposal, and service line accidents generally involve these hazards.
    
    L. Frequency and Time of Notification
    
    1. General
        The mandate does not specify how often operators must give their 
    customers maintenance advice or when 
    
    [[Page 41827]]
    they must give them the advice. To clarify these points, we proposed 
    that operators notify existing customers within 6 months after 
    publication of the final rule, and new customers within that time or 
    within 30 days after the service line is placed in service, whichever 
    is later (proposed Sec. 192.16(b)).
    2. Number of Notices
        Several commenters thought the final rule should clearly state 
    whether operators must notify a customer more than once. Other 
    commenters, including NTSB, felt a single notice to each customer would 
    not be sufficient. They recommended that operators send notices 
    annually (to refresh customer memory), every 2 years, every 5 years, or 
    occasionally.
        A single notice sent to each present and future customer would 
    satisfy the mandate. None of the advocates for more frequent 
    notification showed that additional notices would significantly improve 
    safety. Furthermore, the cost of periodic notices would be high, and 
    the effect of customer notification on accident prevention is 
    uncertain. There is also an absence of accumulated accident data on 
    customer piping from which to project the benefits of sending multiple 
    notices to the same customers. Consequently, the final rule expressly 
    states that operators must notify each customer only once.
    3. New Customers
        Three commenters said the proposed rule was unclear whether ``new 
    customers'' meant new customers on new service lines or new customers 
    on existing service lines. A few operators said it would be a 
    tremendous burden to notify every new customer on an existing service 
    line because of the large changeover in customers. One operator said it 
    has over 100,000 of such new customers annually. These operators would 
    prefer to notify only the first customer on a new service line or to 
    send notices to all customers periodically.
        For the mandate to have a continuing effect on customer safety, 
    each present and future customer must receive a maintenance notice if 
    the operator does not maintain covered piping. There would be no 
    continuing effect if operators were to notify just existing customers 
    and the first customers on new service lines. As these customers leave, 
    their successors might lack necessary maintenance information, and the 
    safety of customer piping might decline. So the final rule applies to 
    all new customers. Operators can mitigate the burden of notifying large 
    numbers of customers by inserting general notices in billing envelopes.
        To avoid confusion, the final rule does not distinguish new 
    customers from existing customers. Instead, the rule (Sec. 192.16(c)) 
    requires operators to notify each customer by a certain date, as 
    discussed next.
    4. Time of Notification
        AGA and several operators recommended a compliance time of 1 year 
    to notify existing customers, instead of 6 months as proposed. They 
    argued that operators would need more time to learn which customers to 
    notify, to draft and send notices, and to instruct personnel to handle 
    inquiries. These commenters also said more time would ease the burden 
    on staff by allowing operators to spread notifications over a longer 
    period.
        For new customers, one operator advised that sending notices within 
    30 days after the customer's service begins would not fit the company's 
    billing cycle. AGA and INGAA suggested an appropriate time to notify 
    new customers would be the time of first billing, rather than when a 
    service line is placed in service.
        We proposed a 6-month compliance period to notify existing 
    customers based primarily on our estimate of the time needed to prepare 
    and send out notices. However, in view of the additional information 
    commenters provided, 1 year now seems more appropriate. Further, 
    because service lines are often left in service during customer 
    changeover, the suggestion to notify new customers upon first billing 
    seems reasonable. However, some operators may not choose billing as the 
    method of notification. And, as one commenter remarked, many farm tap 
    customers who receive gas under a right-of-way agreement are not 
    billed. Considering the variations among billing cycles and the 
    alternative means of distributing notices, we believe 90 days after 
    first receipt of gas at a particular location would be a reasonable 
    deadline by which to notify new customers. Therefore, the final rule 
    requires operators to notify each customer not later than 1 year from 
    today or 90 days after the customer first receives gas at a particular 
    location, whichever is later (Sec. 192.16(c)).
    
    M. Records
    
        The mandate does not require that operators keep records of the 
    advice they give customers. However, as a way to check compliance, we 
    proposed that ``each operator must keep a record of the written 
    notifications'' (proposed Sec. 192.16(c)).
        AGA and several operators said the type of record and the retention 
    time were unclear under the proposed rule. Maryland suggested that to 
    see if operators have notified customers, inspectors would have to 
    inspect a record of the date a notice was sent, the name of the 
    customer, and a copy of the notice. In contrast, several operators 
    thought keeping a list of notified customers and the dates they were 
    notified would be too burdensome. Three operators suggested the final 
    rule just require maintenance of a copy of the notice being sent to 
    customers.
        To check compliance, RSPA and State inspectors will need to view a 
    copy of the notice operators send customers and evidence that notices 
    have been sent to customers. This evidence may relate to the overall 
    notification process, and need not be customer-specific. For example, a 
    record showing the approximate dates notices are mailed or a written 
    procedure for the notification process would be evidence notices have 
    been sent. More in depth checks on compliance could be conducted where 
    warranted without requiring more detailed records. Therefore, we 
    clarified the final rule to provide that operators must maintain a copy 
    of the notice currently in use and evidence that the notices have been 
    sent to customers as required (Sec. 192.16(d)). Evidence of 
    notifications more than 3 years old may be discarded.
    
    N. Master Meter Operators
    
        One commenter recommended that we specifically exempt operators of 
    master meter systems from the final rule. Operators of master meter 
    systems purchase gas from pipeline companies through master meters, and 
    then resell and distribute the gas to customers. The customers are 
    usually residents of mobilehome parks or housing projects, the 
    operator's primary enterprise.
        In developing the NPRM, we assumed the proposed rules would not 
    affect many master meter operators because they generally own all gas 
    distribution piping up to each customer's dwelling. However, as stated 
    above, WMPA advised that the proposed rules would affect mobilehome 
    parks in California because of customer-owned short sections of 
    connector piping. Although that piping was aboveground and would not 
    come under the final rule, it is reasonable to assume that buried 
    connector piping may occur in some master meter systems. So the 
    proposed rule may have affected small entities to a larger extent than 
    we first pictured.
        To mitigate this impact, the final rule (Sec. 192.16(c)) allows 
    master meter operators to continuously post a general 
    
    [[Page 41828]]
    notice as an alternative to sending notices to customers individually. 
    This type of notification is appropriate for master meter systems 
    because there is commonly a prominent place visited by residents, such 
    as a management office, that is suitable for such posting.
        Although the final rule probably does not affect many master meter 
    operators, we did not adopt the suggestion to specifically exempt these 
    operators. As operators of distribution pipelines, they come under the 
    mandate when they do not maintain buried customer piping up to building 
    walls. Also, there is no evidence to suggest that customers of master 
    meter operators have less need for safety information than customers of 
    other operators.
    
    III. Regulatory Analyses and Notices
    
    A. Executive Order 12866 and DOT Policies and Procedures
    
        The Office of Management and Budget (OMB) does not consider this 
    final rule to be a significant regulatory action under section 3(f) of 
    Executive Order 12866. Therefore, OMB did not review the final rule. 
    Also, DOT does not consider the final rule to be significant under its 
    regulatory policies and procedures (44 FR 11034, February 26, 1979). A 
    final regulatory evaluation is available for review in the docket.
    B. Executive Order 12612
    
        We analyzed the final rule under the principles and criteria in 
    Executive Order 12612 (``Federalism''). The final rule does not have 
    sufficient federalism impacts to warrant preparation of a federalism 
    assessment.
    
    C. Regulatory Flexibility Act
    
        I certify, under Section 605 of the Regulatory Flexibility Act, 
    that this final rule will not have a significant economic impact on a 
    substantial number of small entities. For purposes of that act, small 
    entities supply gas to fewer than 10,000 customers, and most small 
    entities are operators of master meter systems. As discussed above, 
    most master meter operators do not come under the final rule because 
    they own all gas piping up to building walls. Master meter operators 
    that do come under the rule may comply merely by posting a notice in a 
    prominent location. So compliance cost will be nominal for the bulk of 
    small entities. The remaining small entities, mostly operators of 
    distribution systems in small towns, will be subject to the same rule 
    as other operators. But, as explained above, operators can either avoid 
    notification costs by maintaining covered piping, or mitigate costs by 
    including general notices in billing envelopes.
    
    D. Paperwork Reduction Act
    
        OMB has approved the information collection requirements of this 
    final rule under 44 U.S.C. Chapter 35.
    
    List of Subjects in 49 CFR Part 192
    
        Natural gas, Pipeline safety, Reporting and recordkeeping 
    requirements.
    
        RSPA amends 49 CFR part 192 as follows:
    
    PART 192--[AMENDED]
    
        1. The authority citation for part 192 is revised to read as 
    follows:
    
        Authority: 49 U.S.C. 5103, 60102, 60104, 60108, 60109, 60110, 
    60113, and 60118; 49 CFR 1.53.
    
        2. Section 192.16 is added to read as follows:
    
    
    Sec. 192.16  Customer notification.
    
        (a) This section applies to each operator of a service line who 
    does not maintain the customer's buried piping up to entry of the first 
    building downstream, or, if the customer's buried piping does not enter 
    a building, up to the principal gas utilization equipment or the first 
    fence (or wall) that surrounds that equipment. For the purpose of this 
    section, ``maintain'' means monitor for corrosion according to 
    Sec. 192.465 if the customer's buried piping is metallic, survey for 
    leaks according to Sec. 192.723, and if an unsafe condition is found, 
    either shut off the flow of gas or advise the customer of the need to 
    repair the unsafe condition.
        (b) Each operator shall notify each customer once in writing of the 
    following information:
        (1) The operator does not maintain the customer's buried piping.
        (2) If the customer's buried piping is not maintained, it may be 
    subject to the potential hazards of corrosion and leakage.
        (3) Buried gas piping should be--
        (i) Periodically inspected for leaks;
        (ii) Periodically inspected for corrosion if the piping is 
    metallic; and
        (iii) Repaired if any unsafe condition is discovered.
        (4) When excavating near buried gas piping, the piping should be 
    located in advance, and the excavation done by hand.
        (5) The operator (if applicable), plumbers, and heating contractors 
    can assist in locating, inspecting, and repairing the customer's buried 
    piping.
        (c) Each operator shall notify each customer not later than August 
    14, 1996, or 90 days after the customer first receives gas at a 
    particular location, whichever is later. However, operators of master 
    meter systems may continuously post a general notice in a prominent 
    location frequented by customers.
        (d) Each operator must make the following records available for 
    inspection by the Administrator or a State agency participating under 
    49 U.S.C. 60105 or 60106:
        (1) A copy of the notice currently in use; and
        (2) Evidence that notices have been sent to customers within the 
    previous 3 years.
    
        Issued in Washington, D.C. on August 9, 1995.
    Ana Sol Gutierrez,
    Deputy Administrator.
    [FR Doc. 95-20021 Filed 8-11-95; 8:45 am]
    BILLING CODE 4910-60-P
    
    

Document Information

Effective Date:
9/13/1995
Published:
08/14/1995
Department:
Research and Special Programs Administration
Entry Type:
Rule
Action:
Final rule.
Document Number:
95-20021
Dates:
September 13, 1995.
Pages:
41821-41828 (8 pages)
Docket Numbers:
Docket PS-135, Amdt. 192-3
RINs:
2137-AC32
PDF File:
95-20021.pdf
CFR: (10)
49 CFR 192.3)
49 CFR 192.723)
49 CFR 192.197(a)(5))
49 CFR 192.16(a)(2))
49 CFR 192.16(a)(3))
More ...