94-23730. Consideration of Issuance of Amendment to Facility Operating License, Proposed No Significant Hazards Consideration Determination, and Opportunity for a Hearing; Commonwealth Edison Co.  

  • [Federal Register Volume 59, Number 184 (Friday, September 23, 1994)]
    [Unknown Section]
    [Page 0]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 94-23730]
    
    
    [[Page Unknown]]
    
    [Federal Register: September 23, 1994]
    
    
    -----------------------------------------------------------------------
    
    NUCLEAR REGULATORY COMMISSION
    [Docket Nos. STN 50-454 and STN 50-455]
    
     
    
    Consideration of Issuance of Amendment to Facility Operating 
    License, Proposed No Significant Hazards Consideration Determination, 
    and Opportunity for a Hearing; Commonwealth Edison Co.
    
        The U.S. Nuclear Regulatory Commission (the Commission) is 
    considering issuance of an amendment to Facility Operating License Nos. 
    NPF-37 and NPF-66, issued to Commonwealth Edison Company (the 
    licensee), for operation of Byron Station, Units 1 and 2, located in 
    Ogle County, Illinois.
        The proposed amendment would revise the technical specifications 
    (TS) to incorporate a 1.0 volt steam generator tube interim plugging 
    criteria (IPC) for Unit 1 beginning with Cycle 7, which has begun. This 
    supplements the information that was published in the Federal Register 
    on August 31, 1994 (59 FR 45019).
        Before issuance of the proposed license amendment, the Commission 
    will have made findings required by the Atomic Energy Act of 1954, as 
    amended (the Act) and the Commission's regulations.
        The Commission has made a proposed determination that the amendment 
    request involves no significant hazards consideration. Under the 
    Commission's regulations in 10 CFR 50.92, this means that operation of 
    the facility in accordance with the proposed amendment would not (1) 
    involve a significant increase in the probability or consequences of an 
    accident previously evaluated; or (2) create the possibility of a new 
    or different kind of accident from any accident previously evaluated; 
    or (3) involve a significant reduction in a margin of safety. As 
    required by 10 CFR 50.91(a), the licensee has provided its analysis of 
    the issue of no significant hazards consideration, which is presented 
    below:
    
        1. The proposed change does not involve a significant increase 
    in the probability or consequences of an accident previously 
    evaluated.
        Consistent with Regulatory Guide (RG) 1.121, ``Basis for 
    Plugging Degraded PWR Steam Generator Tubes,'' Revision 0, August 
    1976, the traditional depth-based criteria for SG tube repair 
    implicitly ensures that tubes accepted for continued service will 
    retain adequate structural and leakage integrity during normal 
    operating, transient, and postulated accident conditions. It is 
    recognized that defects in tubes permitted to remain in service, 
    especially cracks, occasionally grow entirely through-wall and 
    develop small leaks. Limits on allowable primary-to-secondary 
    leakage established in Technical Specifications ensure timely plant 
    shutdown before the structural and leakage integrity of the affected 
    tube is challenged.
        The proposed license amendment request to implement voltage 
    amplitude [steam generator] SG tube support plate Interim Plugging 
    Criteria for Byron Unit 1 Cycle 7 meets the requirements of RG 
    1.121. The IPC methodology demonstrates that tube leakage is 
    acceptably low and tube burst is a highly improbable event during 
    either normal operation or the most limiting accident condition, a 
    postulated main steam line break (MSLB) event. Requesting a single 
    cycle applicability is more conservative than the guidance contained 
    in the draft Generic Letter on voltage-based repair criteria issued 
    for comment on August 12, 1994.
        Adequate SG tube leakage integrity during normal operating 
    conditions is assured by limiting allowable primary-to-secondary 
    leakage to 150 gpd per SG or 600 gpd total. Currently, this limit is 
    administratively controlled.
        However, a license amendment request was submitted on June 3, 
    1994, to incorporate this limit into the Byron Technical 
    Specifications. During normal operating conditions, the tube support 
    plate constrains the [outer diameter stress corrosion cracking] 
    ODSCC affected area of the tube to provide additional strength that 
    precludes burst. Any leakage of a tube exhibiting ODSCC at the [tube 
    support plate] TSP is fully bounded by the existing SG tube rupture 
    analysis included in the Byron [Updated Final Safety Analysis 
    Report] UFSAR. Therefore, probability of failure of a tube left in 
    service or consequences of tube failure during normal operating 
    conditions is not significantly increased by the application of IPC.
        During transients, the TSP is conservatively assumed to displace 
    due to the thermal-hydraulic loads associated with the transient. 
    This may partially expose a crack which is within the boundary of 
    the TSP during normal operations to free span conditions. Burst is 
    therefore conservatively evaluated assuming the crack is fully 
    exposed to free span conditions. The structural eddy current bobbin 
    coil voltage limit for free-span burst is 4.54 volts. This limit 
    takes into consideration a 1.43 safety factor applied to the steam 
    line break differential pressure that is consistent with RG 1.121 
    requirements. With additional considerations for growth rate 
    assumptions and an upper 95% confidence estimate on voltage 
    variability, the maximum voltage indication that could remain in 
    service is reduced to 2.7 volts. For added conservatism, the 
    allowable indication voltage is further reduced in the proposed 
    amendment to a 1.0 volt confirmed ODSCC indication limit. All 
    indications greater than 1.0 volt will be subject to an RPC 
    examination. Tubes with RPC confirmed ODSCC indications will be 
    plugged or sleeved. Any ODSCC indications between 1.0 volt and 2.7 
    volts which are not confirmed as ODSCC will be allowed to remain in 
    service since these indications are not as likely to affect tube 
    structural integrity or leakage integrity over the next operating 
    cycle as the indications that are detectable by both bobbin and RPC 
    inspections.
        The eddy current inspection process has been enhanced to address 
    RG 1.83, ``Inservice Inspection of PWR Steam Generator Tubes,'' 
    Revision 1, July 1975. consideration as well as the EPRI SG 
    Inspection Guidelines. Enhancements in accordance with NUREG-1477 
    and Appendix A of the Catawba IPC report (WCAP-13698) are in place 
    to increase detection of ODSCC indications and to ensure reliable, 
    consistent acquisition and analysis of data. Based on the 
    conservative selection of the voltage criteria and the increased 
    ability to identify ODSCC, the probability of tube failure during an 
    accident is also not significantly increased due to application of 
    requested IPC.
        For consistency with current offsite dose limits, the site 
    allowable leakage limit during a MSLB has been conservatively 
    calculated to be 12.8 gpm. This leakage limit includes maximum 
    allowable operational leakage from the unaffected SGs and the 
    accident leakage from the affected SG. As a requirement for 
    operation following application of IPC, the projected distribution 
    of crack indications over the operating period must be verified to 
    result in primary to secondary accident leakage less than the site 
    allowable leakage limit. Thus, the consequences of a MSLB remain 
    unchanged.
        For an unscheduled mid-cycle inspection as a result of leakage 
    due to mechanisms other than ODSCC at support plates or some other 
    cause, the ODSCC indication limit is represented by the following 
    equation:
    
    
    TN23SE94.003
    
    where:
    
    V=measured voltage
    VBOC=voltage at BOC
    t=time period of operation to unscheduled outage
    CL=cycle length (full operating cycle length where operating cycle 
    is the time between two scheduled steam generator inspections)
    VSL=4.5 volts
    
        Assuming linear flaw growth from BOC to EOC and a maximum 
    structural limit of 4.5 volts, the voltage expected for an 
    identified flaw at any time in the cycle can be predicted. The 
    allowed voltage limit for an unscheduled inspection, as identified 
    by the equation given above, reduces the predicted straightline 
    growth voltage to ensure conservatism in the limit. A flaw which has 
    not exceeded the predicted voltage growth at any point in the cycle 
    would not be expected to exceed the structural limit at end of cycle 
    or negatively impact the burst probability calculated based on 
    results from the last scheduled inspection. Therefore, it is 
    acceptable to leave the tube in service.
        Therefore, as implementation of the 1.0 volt IPC for Byron Unit 
    1 Cycle 7 does not adversely affect steam generator tube integrity 
    and results in acceptable dose consequences, the proposed license 
    amendment request does not result in any significant increase in the 
    probability or consequences of an accident previously evaluated 
    within the Byron Updated Final Safety Analysis Report.
        2. The proposed change does not create the possibility of a new 
    or different kind of accident from any accident previously 
    evaluated.
        Implementation of the proposed SG tube IPC for Byron Unit 1 
    Cycle 7 does not introduce any significant changes to the plant 
    design basis. Use of the criteria does not provide a mechanism which 
    could result in an accident outside the tube support plate 
    elevations since industry experience indicates that ODSCC 
    originating within the tube support plate does not extend 
    significantly beyond the thickness of the support plate. This 
    criteria only applies to ODSCC contained within the region of the 
    tube bounded by the tube support plate.
        In addressing the combined effects of Loss of Coolant Accident 
    (LOCA) coincident with a Safe Shutdown Earthquake (SSE) on the SG 
    (as required by General Design Criterion 2), it has been determined 
    that tube collapse of select tubes may occur in the SGs at some 
    plants, including Byron Unit 1. There are two issues associated with 
    SG tube collapse. First, the collapse of SG tubing reduces the RCS 
    flow area through the tubes. The reduction in flow area increases 
    the resistance to flow of steam from the core during a LOCA which, 
    in turn, may potentially increase Peak Clad Temperature (PCT). 
    Second, there is a potential that partial through-wall cracks in 
    tubes could progress to through-wall cracks during tube deformation 
    or collapse.
        A number of tubes have been identified, in the ``wedge'' 
    locations of the SG TSPs, that demonstrate the potential for tube 
    collapse during a LOCA + SSE event. Because of this potential, these 
    tubes have been excluded from application of the voltage-based SG 
    TSP IPC.
        Therefore, neither a single nor multiple tube rupture event 
    would be expected in a steam generator in which IPC has been 
    applied.
        ComEd has implemented a maximum primary to secondary leakage 
    limit of 150 gpd through any one SG at Byron to help preclude the 
    potential for excessive leakage during all plant conditions. The 150 
    gpd limit provides for leakage detection and plant shutdown in the 
    event of an unexpected single crack leak associated with the longest 
    permissible free span crack length. The 150 gpd limit provides 
    adequate leakage detection and plant shutdown criteria in the event 
    an unexpected single crack results in leakage that is associated 
    with the longest permissible free span crack length. Since tube 
    burst is precluded during normal operation due to the proximity of 
    the TSP to the tube and the potential exists for the crevice to 
    become uncovered during MSLB conditions, the leakage from the 
    maximum permissible crack must preclude tube burst at MSLB 
    conditions. Thus, the 150 gpd limit provides a conservative limit to 
    prompt plant shutdown prior to reaching critical crack lengths under 
    MSLB conditions.
        Upon implementation of the 1.0 volt IPC for Byron Unit 1 Cycle 
    7, steam generator tube integrity continues to be maintained through 
    inservice inspection and primary-to-secondary leakage monitoring. 
    Therefore, the possibility of a new or different kind of accident 
    from any previously evaluated is not created.
        3. The proposed change does not involve a significant reduction 
    in a margin of safety.
        The use of the voltage based bobbin coil probe SG TSP IPC for 
    Byron Unit 1 Cycle 7 will maintain steam generator tube integrity 
    commensurate with the criteria of RG 1.121 as discussed above. Upon 
    implementation of the criteria, even under the worst case 
    conditions, the occurrence of ODSCC at the TSP elevations is not 
    expected to lead to a steam generator tube rupture event during 
    normal or faulted plant conditions. The distribution of crack 
    indications at the TSP elevations result in acceptable primary-to-
    secondary leakage during all plant conditions and radiological 
    consequences are not adversely impacted by the application of IPC.
        The installation of SG tube plugs and sleeves reduces the RCS 
    flow margin. As noted previously, implementation of the SG TSP IPC 
    will decrease the number of tubes which must be repaired by plugging 
    or sleeving. Thus, implementation of IPC will retain additional flow 
    margin that would otherwise be reduced due to increased tube 
    plugging. Therefore, no significant reduction in the margin of 
    safety will occur during Cycle 7 as a result of the implementation 
    of this proposed license amendment request.
        Although not relied upon to prove adequacy of the proposed 
    amendment request, the following analyses demonstrate that 
    significant conservatism exists in the methods and justifications 
    described above:
    
    Limited Tube Support Plate Displacement
    
        An analysis was performed to verify the extent of limited TSP 
    displacement during accident conditions (MSLB). Application of 
    minimum TSP displacement assumptions reduce the likelihood of a tube 
    burst to negligible levels.
        Consideration of limited TSP displacement would also reduce 
    potential MSLB leakage when compared to the leakage calculated 
    assuming free span indications.
    
    Probability of Detection
    
        The Electric Power Research Institute (EPRI) Performance 
    Demonstration Program analyzed the performance of approximately 20 
    eddy current data analysts evaluating data from a unit with \3/4\'' 
    inside diameter and 0.049'' wall thickness tubes. The results of 
    this analysis clearly show that the detectability of larger voltage 
    indications is increased which lends creditability for application 
    of a POD of >0.6 for ODSCC indications larger than 1.0 volt.
    
    Risk Evaluation of Core Damage
    
        As part of ComEd's evaluation of the operability of Byron Unit 1 
    Cycle 7, a risk evaluation was completed. The objective of this 
    evaluation was to compare core damage frequency under containment 
    bypass conditions, with and without the interim plugging criteria 
    applied at Byron Unit 1.
        The total Byron core damage frequency is estimated to be 3.09E-5 
    per reactor year with a total contribution from containment bypass 
    sequences of 3.72E-8 per reactor year according to the results of 
    the current individual plant evaluation (IPE). Operation with the 
    requested IPC resulted in an insignificant increase in core damage 
    frequency resulting from MSLB with containment bypass conditions.
    
        The NRC staff has reviewed the licensee's analysis and, based on 
    this review, it appears that the three standards of 10 CFR 50.92(c) are 
    satisfied. Therefore, the NRC staff proposes to determine that the 
    amendment request involves no significant hazards consideration.
        The Commission is seeking public comments on this proposed 
    determination. Any comments received within 30 days after the date of 
    publication of this notice will be considered in making any final 
    determination.
        Normally, the Commission will not issue the amendment until the 
    expiration of the 30-day notice period. However, should circumstances 
    change during the notice period such that failure to act in a timely 
    way would result, for example, in derating or shutdown of the facility, 
    the Commission may issue the license amendment before the expiration of 
    the 30-day notice period, provided that its final determination is that 
    the amendment involves no significant hazards consideration. The final 
    determination will consider all public and State comments received. 
    Should the Commission take this action, it will publish in the Federal 
    Register a notice of issuance and provide for opportunity for a hearing 
    after issuance. The Commission expects that the need to take this 
    action will occur very infrequently.
        Written comments may be submitted by mail to the Rules Review and 
    Directives Branch, Division of Freedom of Information and Publications 
    Services, Office of Administration, U.S. Nuclear Regulatory Commission, 
    Washington, DC 20555, and should cite the publication date and page 
    number of this Federal Register notice. Written comments may also be 
    delivered to Room 6D22, Two White Flint North, 11455 Rockville Pike, 
    Rockville, Maryland, from 7:30 a.m. to 4:15 p.m. Federal workdays. 
    Copies of written comments received may be examined at the NRC Public 
    Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC 
    20555.
        The filing of requests for hearing and petitions for leave to 
    intervene is discussed below.
        By October 24, 1994, the licensee may file a request for a hearing 
    with respect to issuance of the amendment to the subject facility 
    operating license and any person whose interest may be affected by this 
    proceeding and who wishes to participate as a party in the proceeding 
    must file a written request for a hearing and a petition for leave to 
    intervene. Requests for a hearing and a petition for leave to intervene 
    shall be filed in accordance with the Commission's ``Rules of Practice 
    for Domestic Licensing Proceedings'' in 10 CFR Part 2. Interested 
    persons should consult a current copy of 10 CFR 2.714 which is 
    available at the Commission's Public Document Room, the Gelman 
    Building, 2120 L Street, NW., Washington, DC 20555 and at the local 
    public document room located at the Byron Public Library, 109 N. 
    Franklin, Byron, Illinois 61010. If a request for a hearing or petition 
    for leave to intervene is filed by the above date, the Commission or an 
    Atomic Safety and Licensing Board, designated by the Commission or by 
    the Chairman of the Atomic Safety and Licensing Board Panel, will rule 
    on the request and/or petition; and the Secretary or the designated 
    Atomic Safety and Licensing Board will issue a notice of hearing or an 
    appropriate order.
        As required by 10 CFR 2.714, a petition for leave to intervene 
    shall set forth with particularity the interest of the petitioner in 
    the proceeding, and how that interest may be affected by the results of 
    the proceeding. The petition should specifically explain the reasons 
    why intervention should be permitted with particular reference to the 
    following factors: (1) the nature of the petitioner's right under the 
    Act to be made party to the proceeding; (2) the nature and extent of 
    the petitioner's property, financial, or other interest in the 
    proceeding; and (3) the possible effect of any order which may be 
    entered in the proceeding on the petitioner's interest. The petition 
    should also identify the specific aspect(s) of the subject matter of 
    the proceeding as to which petitioner wishes to intervene. Any person 
    who has filed a petition for leave to intervene or who has been 
    admitted as a party may amend the petition without requesting leave of 
    the Board up to 15 days prior to the first prehearing conference 
    scheduled in the proceeding, but such an amended petition must satisfy 
    the specificity requirements described above.
        Not later than 15 days prior to the first prehearing conference 
    scheduled in the proceeding, a petitioner shall file a supplement to 
    the petition to intervene which must include a list of the contentions 
    which are sought to be litigated in the matter. Each contention must 
    consist of a specific statement of the issue of law or fact to be 
    raised or controverted. In addition, the petitioner shall provide a 
    brief explanation of the bases of the contention and a concise 
    statement of the alleged facts or expert opinion which support the 
    contention and on which the petitioner intends to rely in proving the 
    contention at the hearing. The petitioner must also provide references 
    to those specific sources and documents of which the petitioner is 
    aware and on which the petitioner intends to rely to establish those 
    facts or expert opinion. Petitioner must provide sufficient information 
    to show that a genuine dispute exists with the applicant on a material 
    issue of law or fact. Contentions shall be limited to matters within 
    the scope of the amendment under consideration. The contention must be 
    one which, if proven, would entitle the petitioner to relief. A 
    petitioner who fails to file such a supplement which satisfies these 
    requirements with respect to at least one contention will not be 
    permitted to participate as a party.
        Those permitted to intervene become parties to the proceeding, 
    subject to any limitations in the order granting leave to intervene, 
    and have the opportunity to participate fully in the conduct of the 
    hearing, including the opportunity to present evidence and cross-
    examine witnesses.
        If a hearing is requested, the Commission will make a final 
    determination on the issue of no significant hazards consideration. The 
    final determination will serve to decide when the hearing is held.
        If the final determination is that the amendment request involves 
    no significant hazards consideration, the Commission may issue the 
    amendment and make it immediately effective, notwithstanding the 
    request for a hearing. Any hearing held would take place after issuance 
    of the amendment.
        If the final determination is that the amendment request involves a 
    significant hazards consideration, any hearing held would take place 
    before the issuance of any amendment.
        A request for a hearing or a petition for leave to intervene must 
    be filed with the Secretary of the Commission, U.S. Nuclear Regulatory 
    Commission, Washington, DC 20555, Attention: Docketing and Services 
    Branch, or may be delivered to the Commission's Public Document Room, 
    the Gelman Building, 2120 L Street, NW., Washington, DC 20555, by the 
    above date. Where petitions are filed during the last 10 days of the 
    notice period, it is requested that the petitioner promptly so inform 
    the Commission by a toll-free telephone call to Western Union at 1-
    (800) 248-5100 (in Missouri 1-(800) 342-6700). The Western Union 
    operator should be given Datagram Identification Number N1023 and the 
    following message addressed to Mr. Robert A. Capra: petitioner's name 
    and telephone number, date petition was mailed, plant name, and 
    publication date and page number of this Federal Register notice. A 
    copy of the petition should also be sent to the Office of the General 
    Counsel, U.S. Nuclear Regulatory Commission, Washington, DC 20555, and 
    to Michael I. Miller, Esquire; Sidney and Austin, One First National 
    Plaza, Chicago, Illinois 60690, attorney for the licensee.
        Nontimely filings of petitions for leave to intervene, amended 
    petitions, supplemental petitions and/or requests for hearing will not 
    be entertained absent a determination by the Commission, the presiding 
    officer or the presiding Atomic Safety and Licensing Board that the 
    petition and/or request should be granted based upon a balancing of the 
    factors specified in 10 CFR 2.714(a)(1) (i)-(v) and 2.714(d).
        For further details with respect to this action, see the 
    applications for amendment dated September 7, 1994, and September 17, 
    1994, (two letters) which are available for public inspection at the 
    Commission's Public Document Room, the Gelman Building, 2120 L Street, 
    NW., Washington, DC 20555 and at the local public document room located 
    at the Byron Public Library, 109 N. Franklin, P.O. Box 434, Byron, 
    Illinois 61010.
    
        Dated at Rockville, Maryland, this 21st day of September 1994.
    
        For the Nuclear Regulatory Commission.
    Robert A. Capra,
    Director Project Directorate III-2, Division of Reactor Projects--III/
    IV, Office of Nuclear Reactor Regulation.
    [FR Doc. 94-23730 Filed 9-22-94; 8:45 am]
    BILLING CODE 7590-01-M
    
    
    

Document Information

Published:
09/23/1994
Department:
Nuclear Regulatory Commission
Entry Type:
Uncategorized Document
Document Number:
94-23730
Pages:
0-0 (1 pages)
Docket Numbers:
Federal Register: September 23, 1994, Docket Nos. STN 50-454 and STN 50-455