96-24808. Energy Conservation Program for Consumer Products: Granting of the Application for Interim Waiver and Publishing of the Petition for Waiver of Rheem Manufacturing Company from the DOE Furnace Test Procedure. (Case No. F-087)  

  • [Federal Register Volume 61, Number 189 (Friday, September 27, 1996)]
    [Notices]
    [Pages 50813-50815]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 96-24808]
    
    
    -----------------------------------------------------------------------
    
    
    DEPARTMENT OF ENERGY
    
    Energy Conservation Program for Consumer Products: Granting of 
    the Application for Interim Waiver and Publishing of the Petition for 
    Waiver of Rheem Manufacturing Company from the DOE Furnace Test 
    Procedure. (Case No. F-087)
    
    AGENCY: Office of Energy Efficiency and Renewable Energy, Department of 
    Energy.
    
    ACTION: Notice.
    
    -----------------------------------------------------------------------
    
    SUMMARY: Today's notice grants an Interim Waiver to Rheem Manufacturing 
    Company (Rheem) from the existing Department of Energy (DOE or 
    Department) test procedure regarding blower time delay for the 
    company's GLH downflow and GPH upflow/horizontal series furnaces.
        Today's notice also publishes a ``Petition for Waiver'' from Rheem. 
    Rheem's Petition for Waiver requests DOE to grant relief from the DOE 
    furnace test procedure relating to the blower time delay specification. 
    Rheem seeks to test using a blower delay time of 12 seconds for its GLH 
    downflow and GPH upflow/horizontal series furnaces instead of the 
    specified 1.5-minute delay between burner on-time and blower on-time. 
    The Department is soliciting comments, data, and information respecting 
    the Petition for Waiver.
    
    DATES: DOE will accept comments, data, and information not later than 
    October 28, 1996.
    
    ADDRESSES: Written comments and statements shall be sent to: Department 
    of Energy, Office of Codes and Standards, Case No. F-087, Mail Stop EE-
    43, Room 1J-018, Forestall Building, 1000 Independence Avenue, SW., 
    Washington, D.C. 20585, (202) 586-7140.
    
    FOR FURTHER INFORMATION CONTACT:
    
    Cyrus H. Nasseri, U.S. Department of Energy, Office of Energy 
    Efficiency and Renewable Energy, Mail Station EE-431, Forestall 
    Building, 1000 Independence Avenue, SW., Washington, D.C. 20585-0121, 
    (202) 586-9138.
    Eugene Margolis, Esq., U.S. Department of Energy, Office of General 
    Counsel, Mail Station GC-72, Forestall Building, 1000 Independence 
    Avenue, SW., Washington, D.C. 20585-0103, (202) 586-9507.
    
    SUPPLEMENTARY INFORMATION: The Energy Conservation Program for Consumer 
    Products (other than automobiles) was established pursuant to the 
    Energy Policy and Conservation Act, as amended (EPCA), which requires 
    DOE to prescribe standardized test
    
    [[Page 50814]]
    
    procedures to measure the energy consumption of certain consumer 
    products, including furnaces. The intent of the test procedures is to 
    provide a comparable measure of energy consumption that will assist 
    consumers in making purchasing decisions. These test procedures appear 
    at Title 10 CFR Part 430, Subpart B.
        The Department amended the test procedure rules to provide for a 
    waiver process by adding Section 430.27 to Title 10 CFR Part 430. 45 FR 
    64108, September 26, 1980. Subsequently, DOE amended the waiver process 
    to allow the Assistant Secretary for Energy Efficiency and Renewable 
    Energy (Assistant Secretary) to grant an Interim Waiver from test 
    procedure requirements to manufacturers that have petitioned DOE for a 
    waiver of such prescribed test procedures. Title 10 CFR Part 430, 
    Section 430.27(a)(2).
        The waiver process allows the Assistant Secretary to waive 
    temporarily test procedures for a particular basic model when a 
    petitioner shows that the basic model contains one or more design 
    characteristics which prevent testing according to the prescribed test 
    procedures, or when the prescribed test procedures may evaluate the 
    basic model in a manner so unrepresentative of its true energy 
    consumption as to provide materially inaccurate comparative data. 
    Waivers generally remain in effect until final test procedure 
    amendments become effective, resolving the problem that is the subject 
    of the waiver.
        An Interim Waiver will be granted if it is determined that the 
    applicant will experience economic hardship if the Application for 
    Interim Waiver is denied, if it appears likely that the Petition for 
    Waiver will be granted, and/or the Assistant Secretary determines that 
    it would be desirable for public policy reasons to grant immediate 
    relief pending a determination on the Petition for Waiver. Title 10 CFR 
    Part 430, Section 430.27 (g). An Interim Waiver remains in effect for a 
    period of 180 days or until DOE issues its determination on the 
    Petition for Waiver, whichever is sooner, and may be extended for an 
    additional 180 days, if necessary.
        On August 28, 1996, Rheem filed an Application for Interim Waiver 
    and a Petition for Waiver regarding blower time delay. Rheem's 
    Application seeks an Interim Waiver from the DOE test provisions that 
    require a 1.5-minute time delay between the ignition of the burner and 
    starting of the circulating air blower. Instead, Rheem requests the 
    allowance to test using a 12-second blower time delay when testing its 
    GLH downflow and GPH upflow/horizontal series furnaces. Rheem states 
    that the 12-second delay is indicative of how these furnaces actually 
    operate. Such a delay results in an average 2.0 percent increase in 
    AFUE. Since current DOE test procedures do not address this variable 
    blower time delay, Rheem asks that the Interim Waiver be granted.
        The Department has published a Notice of Proposed Rulemaking on 
    August 23, 1993, (58 FR 44583) to amend the furnace test procedure, 
    which addresses the above issue.
        Previous Petitions for Waiver for this type of time blower delay 
    control have been granted by DOE to Coleman Company, 50 FR 2710, 
    January 18, 1985; Magic Chef Company, 50 FR 41553, October 11, 1985; 
    Rheem Manufacturing Company, 53 FR 48574, December 1, 1988, 56 FR 2920, 
    January 25, 1991, 57 FR 10166, March 24, 1992, 57 FR 34560, August 5, 
    1992; 59 FR 30577, June 14, 1994, and 59 FR 55470, November 7, 1994; 
    Trane Company, 54 FR 19226, May 4, 1989, 56 FR 6021, February 14, 
    1991,57 FR 10167, March 24, 1992, 57 FR 22222, May 27, 1992, 58 FR 
    68138, December 23, 1993, and 60 FR 62835, December 7, 1995; Lennox 
    Industries, 55 FR 50224, December 5, 1990, 57 FR 49700, November 3, 
    1992, 58 FR 68136, December 23, 1993, and 58 FR 68137, December 23, 
    1993; Inter-City Products Corporation, 55 FR 51487, December 14, 1990, 
    56 FR 63945, December 6, 1991 and 61 FR 27057, May 30, 1996; DMO 
    Industries, 56 FR 4622, February 5, 1991, and 59 FR 30579, June 14, 
    1994; Heil-Quaker Corporation, 56 FR 6019, February 14, 1991; Carrier 
    Corporation, 56 FR 6018, February 14, 1991, 57 FR 38830, August 27, 
    1992, 58 FR 68131, December 23, 1993, 58 FR 68133, December 23, 1993, 
    59 FR 14394, March 28, 1994, and 60 FR 62832, December 7, 1995; Amana 
    Refrigeration Inc., 56 FR 27958, June 18, 1991, 56 FR 63940, December 
    6, 1991, 57 FR 23392, June 3, 1992, and 58 FR 68130, December 23, 1993; 
    Snyder General Corporation, 56 FR 54960, September 9, 1991; Goodman 
    Manufacturing Corporation, 56 FR 51713, October 15, 1991, 57 FR 27970, 
    June 23, 1992, 59 FR 12586, March 17, 1994 and 61 FR 17289, April 19, 
    1996; The Ducane Company Inc., 56 FR 63943, December 6, 1991, 57 FR 
    10163, March 24, 1992, and 58 FR 68134, December 23, 1993; Armstrong 
    Air Conditioning, Inc., 57 FR 899, January 9, 1992, 57 FR 10160, March 
    24, 1992, 57 FR 10161, March 24, 1992, 57 FR 39193, August 28, 1992, 57 
    FR 54230, November 17, 1992, and 59 FR 30575, June 14, 1994; Thermo 
    Products, Inc., 57 FR 903, January 9, 1992, and 61 FR 17887, April 23, 
    1996; Consolidated Industries Corporation, 57 FR 22220, May 27, 1992, 
    and 61 FR 4262, February 5, 1996; Evcon Industries, Inc., 57 FR 47847, 
    October 20, 1992, and 59 FR 46968, September 13, 1994; Bard 
    Manufacturing Company, 57 FR 53733, November 12, 1992, and 59 FR 30578, 
    June 14, 1994; and York International Corporation, 59 FR 46969, 
    September 13, 1994, 60 FR 100, January 3, 1995, 60 FR 62834, December 
    7, 1995, and 60 FR 62837, December 7, 1995.
        Thus, it appears likely that this Petition for Waiver for blower 
    time delay will be granted. In those instances where the likely success 
    of the Petition for Waiver has been demonstrated based upon DOE having 
    granted a waiver for a similar product design, it is in the public 
    interest to have similar products tested and rated for energy 
    consumption on a comparable basis.
        Therefore, based on the above, DOE is granting Rheem an Interim 
    Waiver for its GLH downflow and GPH upflow/horizontal series furnaces. 
    Rheem shall be permitted to test its GLH downflow and GPM upflow/
    horizontal series furnaces on the basis of the test procedures 
    specified in Title 10 CFR Part 430, Subpart B, Appendix N, with the 
    modification set forth below:
        (i) Section 3.0 in Appendix N is deleted and replaced with the 
    following paragraph:
        3.0  Test Procedure. Testing and measurements shall be as specified 
    in Section 9 in ANSI/ASHRAE 103-82 with the exception of Sections 
    9.2.2, 9.3.1, and 9.3.2, and the inclusion of the following additional 
    procedures:
        (ii) Add a new paragraph 3.10 in Appendix N as follows:
        3.10  Gas- and Oil-Fueled Central Furnaces. After equilibrium 
    conditions are achieved following the cool-down test and the required 
    measurements performed, turn on the furnace and measure the flue gas 
    temperature, using the thermocouple grid described above, at 0.5 and 
    2.5 minutes after the main burner(s) comes on. After the burner start- 
    up, delay the blower start-up by 1.5 minutes (t-) unless: (1) the 
    furnace employs a single motor to drive the power burner and the indoor 
    air circulation blower, in which case the burner and blower shall be 
    started together; or (2) the furnace is designed to operate using an 
    unvarying delay time that is other than 1.5 minutes, in which case the 
    fan control shall be permitted to start the blower; or (3) the delay 
    time results in the activation of a temperature safety device which 
    shuts off the burner, in which case the fan control shall be permitted 
    to start the blower. In the latter case, if the fan control is 
    adjustable, set it to start the
    
    [[Page 50815]]
    
    blower at the highest temperature. If the fan control is permitted to 
    start the blower, measure time delay (t-) using a stop watch. Record 
    the measured temperatures. During the heat-up test for oil-fueled 
    furnaces, maintain the draft in the flue pipe within 0.01 
    inch of water column of the manufacturer's recommended on-period draft.
        This Interim Waiver is based upon the presumed validity of 
    statements and all allegations submitted by the company. This Interim 
    Waiver may be removed or modified at any time upon a determination that 
    the factual basis underlying the Application is incorrect.
        The Interim Waiver shall remain in effect for a period of 180 days 
    or until DOE acts on the Petition for Waiver, whichever is sooner, and 
    may be extended for an additional 180-day period, if necessary.
        Rheem's Petition for Waiver requests DOE to grant relief from the 
    DOE furnace test procedure relating to the blower time delay 
    specification. Rheem seeks to test using a blower delay time of 12 
    seconds for its GLH downflow and GPH upflow/horizontal series furnaces 
    instead of the specified 1.5-minute delay between burner on-time and 
    blower on-time. Pursuant to paragraph (b) of Title 10 CFR Part 430.27, 
    DOE is hereby publishing the ``Petition for Waiver'' in its entirety. 
    The Petition contains no confidential information. The Department 
    solicits comments, data, and information respecting the Petition.
    
        Issued in Washington, DC, September 19, 1996.
    Christine A. Ervin,
    Assistant Secretary, Energy Efficiency and Renewable Energy.
    
    Rheem Manufacturing Company
    
    August 28, 1996.
    Mr. Cyrus Nasseri,
    Assistant Secretary, Conservation and Renewable Energy, United 
    States Department of Energy, 1000 Independence Avenue, SW, 
    Washington, D.C. 20585.
    
        Dear Mr. Nasseri: This is a petition for waiver and application 
    for interim waiver submitted pursuant to title 10 CFR Part 430.27 
    Waiver is requested from the furnace test procedure as prescribed in 
    appendix N to Subpart B of Part 430. The test procedure requires a 
    1.5 minute delay between burner and blower start-up. Rheem is 
    requesting authorization to use a 12 second delay instead of 1.5 
    minutes for our series (-)GLH downflow, and (-)GPH upflow/horizontal 
    residential gas-fired furnaces utilizing General Electric type ICM2+ 
    main blower motors.
        Rheem will be manufacturing these appliances with an electronic 
    device that controls the blower operation on a timing sequence as 
    opposed to temperature.
        Improved energy efficiency is achieved by reducing on cycle 
    losses. Under the Appendix N procedures, the stack temperature is 
    allowed to climb at a faster rate than it would with a 12 second 
    blower on time, allowing energy to be lost out of the vent system. 
    This waste of energy would not occur in actual operation. If this 
    petition is granted, the true blower on time delay would be used in 
    the calculations.
        The current test procedures do not give Rheem credit for the 
    energy savings which averages approximately 2% Annual Fuel 
    Utilization Efficiency (AFUE). This improvement is an average 
    reduction of 20% of the normal on cycle energy losses. Rheem is of 
    the opinion that a 20% reduction is a worthwhile energy savings.
        Rheem has been granted previous waivers regarding blower on time 
    to be used in the efficiency calculations for our (-)GEB and (-)GKA 
    series condensing furnaces and/or (-)GDE, (-)GLE, (-)GDG, (-)GLG, 
    (-)GPH, (-)GLH, (-)GVH, and (-)GVG series furnaces. Several other 
    manufacturers of gas furnaces have also been granted a waiver to 
    permit calculations based on timed blower operation. Also, ASHRAE 
    Standard 103-1993, paragraph 9.5.1.2.2 specifically addresses the 
    use of a timed blower operation.
        Confidential and comparative test data is available to you upon 
    your request, confirming the above energy savings.
        Manufacturers that domestically market similar products are 
    being sent a copy of this petition for waiver and petition for 
    interim waiver.
    
          Sincerely,
    Daniel J. Canclini,
    Vice-President, Product Development and Research Engineering.
    
    bcc: B.A. Cook, K.W. Kleman, R.W. Willis
    
    [FR Doc. 96-24808 Filed 9-26-96; 8:45 am]
    BILLING CODE 6450-01-P
    
    
    

Document Information

Published:
09/27/1996
Department:
Energy Department
Entry Type:
Notice
Action:
Notice.
Document Number:
96-24808
Dates:
DOE will accept comments, data, and information not later than October 28, 1996.
Pages:
50813-50815 (3 pages)
PDF File:
96-24808.pdf