2023-18531. Energy Conservation Program: Test Procedure for Walk-In Coolers and Walk-In Freezers; Correction  

  • Start Preamble Start Printed Page 73215

    AGENCY:

    Office of Energy Efficiency and Renewable Energy, Department of Energy.

    ACTION:

    Final rule; correcting amendments.

    SUMMARY:

    On May 4, 2023, the U.S. Department of Energy (“DOE”) published a final rule adopting test procedures for walk-in coolers and walk-in freezers. This document corrects errors and omissions in that final rule. Neither the errors and omissions nor the corrections affect the substance of the rulemaking or any conclusions reached in support of the final rule.

    DATES:

    Effective October 25, 2023.

    Start Further Info

    FOR FURTHER INFORMATION CONTACT:

    Mr. Troy Watson, U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, Building Technologies Office, EE–5B, 1000 Independence Avenue SW, Washington, DC 20585–0121. Telephone: (240) 449–9387. Email: ApplianceStandardsQuestions@ee.doe.gov.

    Mr. Matthew Schneider, U.S. Department of Energy, Office of the General Counsel, GC–33, 1000 Independence Avenue SW, Washington, DC 20585–0121. Telephone: (240) 597–6265. Email: matthew.schneider@hq.doe.gov.

    End Further Info End Preamble Start Supplemental Information

    SUPPLEMENTARY INFORMATION:

    I. Background

    On May 4, 2023, DOE published a final rule (“May 2023 Final Rule”) amending the test procedures for walk-in coolers and freezers (“walk-ins”) at title 10 of the Code of Federal Regulations (“CFR”) part 431, subpart R, appendices A, B, C, and C1 (hereafter referred to as “appendix A”, “appendix B”, “appendix C”, and “appendix C1”, respectively). 88 FR 28780. Since publication of the May 2023 Final Rule, DOE has identified errors and omissions in the regulatory text established by that final rule. DOE is issuing this rule to correct certain errors and omissions in the May 2023 Final Rule, specifically in 10 CFR 429.70 and appendices A, B, C, and C1, and to assist regulated entities with compliance efforts. The corrections are described in the following paragraphs.

    In 10 CFR 429.70(f)(5)(vi), Table 7 of the regulatory text in the May 2023 Final Rule was erroneously labeled as “Table 7 to Paragraph (f)(5)(iv),” whereas it should have been labeled as “Table 7 to Paragraph (f)(5)(vi)”. 88 FR 28780, 28837. This document corrects the typographical error.

    Section 5.2.1 of appendix A as finalized by the May 2023 Final Rule erroneously instructs the reader to determine standardized thermal transmittance per section 5.1.1 of appendix A. 88 FR 28780, 28840. However, there is no section 5.1.1 of appendix A; this should instead reference section 5.1 of appendix A. This document corrects this typographical error.

    In the May 2023 Final Rule preamble text, DOE states that it is maintaining the current requirement that testing be completed within 24 hours of cutting a test specimen from the envelope components. 88 FR 28780, 28800. However, this requirement was erroneously omitted from the regulatory text in appendix B. Section 5.3 of appendix B should instruct the reader that “Testing must be completed within 24 hours of samples being cut for testing per section 5.2.5 of this appendix”. This document corrects this inadvertent omission.

    Section 5.2.5.7 of appendix B as finalized by May 2023 Final Rule erroneously instructs the reader “To determine the parallelism of the specimen for side 2, repeat section” while omitting which section to repeat. 88 FR 28780, 28845. Section 5.2.5.7 should state “To determine the parallelism of the specimen for side 2, repeat section 5.2.5.6 of this appendix”. This document corrects this inadvertent omission.

    In the May 2023 Final Rule regulatory text, the seventh column of table 17 in appendix C and table 5 in appendix C1 erroneously specify that the compressor capacity or operating mode of the “Off-Cycle Power” test shall be “Compressor On” and that the compressor capacity or operating mode of “Refrigeration Capacity, Ambient Condition A” test shall be “Compressor Off”. 88 FR 28780, 28846, 28851–28852. These labels in the seventh column should be switched such that the “Off-Cycle Power” test is labeled as “Compressor Off” and the “Refrigeration Capacity, Ambient Condition A” test is labeled as “Compressor On”. This document corrects these typographical errors.

    In the May 2023 Final Rule regulatory text, the table for Test Operating Conditions for Medium-Temperature CO2 Unit Coolers in appendix C is erroneously labeled as Table 17. 88 FR 28780, 28846. In appendix C, Table 15 and Table 16 provide modifications to Table 15 and Table 16 included in the referenced industry standard, AHRI 1250–2009 “Standard for Performance Rating of Walk-in Coolers and Freezers.” Because these tables do not represent table numbering within appendix C, subsequent tables only included in appendix C ( i.e., Tables 17 through 19 and the final Table 1, discussed in the following paragraphs) should not continue with the AHRI 1250–2009 table numbering approach and should provide distinct table labels. To address this error and to avoid confusion with the table numbering referencing AHRI 1250–2009, Table 17 as well as the references thereto should instead be labeled as Table C.1. This document corrects this typographical error.

    Similarly, in the May 2023 Final Rule regulatory text, the table for Test Operating Conditions for Low-Temperature CO2 Unit Coolers in appendix C is erroneously labeled as Table 18. Id. This table as well as the references thereto should instead be labeled as Table C.2. This document corrects this typographical error.

    In the May 2023 Final Rule regulatory text, the table for Test Operating Conditions for High-Temperature Unit Coolers in appendix C is erroneously labeled as Table 19. Id. This table as well as the references thereto should Start Printed Page 73216 instead be labeled as Table C.3. This document corrects this typographical error.

    In the May 2023 Final Rule regulatory text, the table for Test Condition Tolerances and Hierarchy for Refrigerant Charging and Setting of Refrigerant Conditions is erroneously labeled as Table 1. 88 FR 28780, 28847–28848. This table should instead be labeled as Table C.4. This document corrects this typographical error.

    In the May 2023 Final Rule regulatory text, in the first column from the left of table 3 to appendix C1, rows three, five, and seven erroneously included a table note numbered five at the end of each “Test description”. 88 FR 28780, 28851. There is no table note that corresponds to note five in this table, however. This document corrects this error.

    In the May 2023 Final Rule regulatory text, in the sixth column from the left of table 9 to appendix C1, row nine has “Compressor operating mode” erroneously specified as “Maximum Capacity, k=2”. 88 FR 28780, 28853. This label should instead read “High Capacity, k=2”. This document corrects this error.

    In the May 2023 Final Rule regulatory text, in the sixth column from the left of table 13 to appendix C1, rows three, seven, and eleven have “Compressor operating mode” erroneously specified as “Minimum Capacity, k=i”. 88 FR 28780, 28854. These labels should instead read “Intermediate Capacity, k=i”. This document corrects this error.

    In the May 2023 Final Rule regulatory text, in the sixth column of table 14 to appendix C1, row 2 has “Compressor operating mode” erroneously specified as “Minimum Capacity, k=i”. Id. This label should instead read “Intermediate Capacity, k=i”. This document corrects this error.

    II. Need for Correction

    As published, the regulatory text in May 2023 Final Rule may lead to confusion in the execution of the DOE test procedure for walk-ins due to incorrect table labeling, omitted section references, and extraneous footnotes. Because this final rule would simply correct errors and omissions in the text without making substantive changes to test procedures adopted in the May 2023 Final Rule, the changes addressed in this document are technical in nature.

    III. Procedural Issues and Regulatory Review

    DOE has concluded that the determinations made pursuant to the various procedural requirements applicable to the May 2023 Final Rule remain unchanged for these final rule technical corrections. These determinations are set forth in the May 2023 Final Rule. 88 FR 28780, 28827–28834.

    Pursuant to the Administrative Procedure Act, 5 U.S.C. 553(b), DOE finds that there is good cause to not issue a separate notice to solicit public comment on those technical corrections contained in this document. Issuing a separate notice to solicit public comment would be impracticable, unnecessary, and contrary to the public interest. As explained previously, the corrections in this document do not affect the substance of or any of the conclusions reached in support of the May 2023 Final Rule. Additionally, given the May 2023 Final Rule is a product of an extensive administrative record with numerous opportunities for public comment, DOE finds additional comment on the technical corrections is unnecessary. Therefore, providing prior notice and an opportunity for public comment on correcting objective errors and omissions that do not change the substance of the test procedure serves no useful purpose.

    Further, this rule correcting errors and omissions makes non-substantive changes to the test procedure in the May 2023 Final Rule. As such, this rule is not subject to the 30-day delay in effective date requirement of 5 U.S.C. 553(d) otherwise applicable to rules that make substantive changes.

    Start List of Subjects

    List of Subjects

    10 CFR Part 429

    • Administrative practice and procedure
    • Confidential business information
    • Energy conservation
    • Household appliances
    • Imports
    • Intergovernmental relations
    • Reporting and recordkeeping requirements
    • Small businesses

    10 CFR Part 431

    • Administrative practice and procedure
    • Confidential business information
    • Energy conservation test procedures
    • Incorporation by reference, and Reporting and recordkeeping requirements
    End List of Subjects

    Signing Authority

    This document of the Department of Energy was signed on August 23, 2023, by Francisco Alejandro Moreno, Acting Assistant Secretary for Energy Efficiency and Renewable Energy, U.S. Department of Energy, pursuant to delegated authority from the Secretary of Energy. That document with the original signature and date is maintained by DOE. For administrative purposes only, and in compliance with requirements of the Office of the Federal Register, the undersigned DOE Federal Register Liaison Officer has been authorized to sign and submit the document in electronic format for publication, as an official document of the Department of Energy. This administrative process in no way alters the legal effect of this document upon publication in the Federal Register .

    Start Signature

    Signed in Washington, DC, on August 23, 2023.

    Treena V. Garrett,

    Federal Register Liaison Officer, U.S. Department of Energy.

    End Signature

    For the reasons stated in the preamble, DOE corrects part 429 and 431 of chapter II of title 10 of the Code of Federal Regulations by making the following correcting amendments:

    Start Part

    PART 429—CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT

    End Part Start Amendment Part

    1. The authority citation for part 429 continues to read as follows:

    End Amendment Part Start Authority

    Authority: 42 U.S.C. 6291–6317; 28 U.S.C. 2461 note.

    End Authority Start Amendment Part

    2. Amend § 429.70 by revising the heading for the table in paragraph (f)(5)(vi) to read as follows:

    End Amendment Part
    Alternative methods for determining energy efficiency and energy use.
    * * * * *

    (f) * * *

    (5) * * *

    (vi) * * *

    Table 7 to Paragraph (f)(5)(vi)

    * * * * *
    Start Part

    PART 431—ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL EQUIPMENT

    End Part Start Amendment Part

    3. The authority citation for part 431 continues to read as follows:

    End Amendment Part Start Authority

    Authority: 42 U.S.C. 6291–6317; 28 U.S.C. 2461 note.

    End Authority Start Amendment Part

    4. Appendix A to subpart R of part 431 is amended by revising section 5.2.1 to read as follows:

    End Amendment Part

    Appendix A to Subpart R of Part 431—Uniform Test Method for the Measurement of Energy Consumption of the Components of Envelopes of Walk-In Coolers and Walk-In Freezers

    * * * * *
    Start Printed Page 73217

    5. * * *

    5.2 * * *

    5.2.1 For display doors and display panels, thermal transmittance, Udd or Udp, respectively, shall be the standardized thermal transmittance, UST, determined per section 5.1 of this appendix.

    * * * * *
    Start Amendment Part

    5. Appendix B to subpart R of part 431 is amended by revising sections 5.2.5.7 and 5.3 to read as follows:

    End Amendment Part

    Appendix B to Subpart R of Part 431— Uniform Test Method for the Measurement of R-Value of Insulation for Envelope Components of Walk-In Coolers and Walk-In Freezers

    * * * * *

    5. * * *

    5.2 * * *

    5.2.5 * * *

    5.2.5.7 To determine the parallelism of the specimen for side 2, repeat section 5.2.5.6 of this appendix.

    * * * * *

    5.3  K-factor Test. Determine the thermal conductivity, or K-factor, of the 1-inch-thick specimen in accordance with the specified sections of ASTM C518–17. Testing must be completed within 24 hours of the specimen being cut for testing per section 5.2.5 of this appendix.

    * * * * *
    Start Amendment Part

    6. Appendix C to subpart R of part 431 is amended by:

    End Amendment Part Start Amendment Part

    a. In section 3.1.6:

    End Amendment Part Start Amendment Part

    i. Removing the words “table 17” and adding in its place, the words “table C.1” wherever they appear;

    End Amendment Part Start Amendment Part

    ii. Revising the newly designated table C.1;

    End Amendment Part Start Amendment Part

    iii. Removing the words “table 18” and adding in its place, the words “table C.2” wherever they appear;

    End Amendment Part Start Amendment Part

    b. In section 3.1.7, removing the words “table 19” and adding in its place, the words “table C.3” wherever they appear;

    End Amendment Part Start Amendment Part

    c. In section 3.2.7.1, removing the words “table 1” and adding in its place, the words “table C.4” wherever they appear.

    End Amendment Part

    The revision reads as follows:

    Appendix C to Subpart R of Part 431—Uniform Test Method for the Measurement of Net Capacity and AWEF of Walk-In Cooler and Walk-In Freezer Refrigeration Systems

    * * * * *

    3. * * *

    3.1. * * *

    3.1.6 * * *

    Table C.1—Test Operating Conditions for Medium-Temperature CO 2 Unit Coolers

    Test descriptionUnit cooler air entering dry-bulb, °FUnit cooler air entering relative humidity, %Suction dew point temp, °FLiquid inlet bubble point temperature °FLiquid inlet subcooling, °FCompressor capacityTest objective
    Off-Cycle Power35<50Compressor OffMeasure fan input power during compressor off-cycle.
    Refrigeration Capacity, Ambient Condition A35<5025385Compressor OnDetermine Net Refrigeration Capacity of Unit Cooler.
    Notes:
    1  Superheat shall be set as indicated in the installation instructions. If no superheat specification is given a default superheat value of 6.5 °F shall be used.
    Start Amendment Part

    7. Appendix C1 to subpart R of part 431 is amended by:

    End Amendment Part Start Amendment Part

    a. In section 3.2.1, revising table 3;

    End Amendment Part Start Amendment Part

    b. In section 3.2.2, revising table 5;

    End Amendment Part Start Amendment Part

    c. In section 3.2.3, revising table 9; and

    End Amendment Part Start Amendment Part

    d. In section 3.2.4, revising tables 13 and 14.

    End Amendment Part

    The revisions read as follows:

    Appendix C1 to Subpart R of Part 431—Uniform Test Method for the Measurement of Net Capacity and AWEF2 of Walk-In Cooler and Walk-In Freezer Refrigeration Systems

    * * * * *

    3. * * *

    3.2. * * *

    3.2.1. * * *

    Table 3—Test Operating Conditions for Fixed-Capacity High-Temperature Outdoor Matched-Pair or Single-Packaged Refrigeration Systems

    Test descriptionUnit cooler air entering dry-bulb, °FUnit cooler air entering relative humidity, % 1Condenser air entering dry-bulb, °FCondenser air entering wet-bulb, °FCompressor statusTest objective
    Refrigeration Capacity A5555953  75,4  68Compressor OnDetermine Net Refrigeration Capacity of Unit Cooler, input power, and EER at Test Condition.
    Off-Cycle Power, Capacity A5555953  75,4  68Compressor OffMeasure total input wattage during compressor off-cycle, ( E cu,off + E F comp,off ) 2 .
    Refrigeration Capacity B5555593  54,4  46Compressor OnDetermine Net Refrigeration Capacity of Unit Cooler and system input power at moderate condition.
    Off-Cycle Power, Capacity B5555593  54,4  46Compressor OffMeasure total input wattage during compressor off-cycle, (E cu,off + E F comp,off ) 2 .
    Refrigeration Capacity C5555353  34,4  29Compressor OnDetermine Net Refrigeration Capacity of Unit Cooler and system input power at cold condition.
    Off-Cycle Power, Capacity C5555353  34,4  29Compressor OffMeasure total input wattage during compressor off-cycle, (E cu,off + E F comp,off ) 2 .
    Notes:
    1  The test condition tolerance (maximum permissible variation of the average value of the measurement from the specified test condition) for relative humidity is 3%.
    2  Measure off-cycle power as described in sections C3 and C4.2 of AHRI 1250–2020.
    3  Required only for evaporative condensing units ( e.g., incorporates a slinger ring).
    4  Maximum allowable value for Single-Packaged Systems that do not use evaporative Dedicated Condensing Units, where all or part of the equipment is located in the outdoor room.
    Start Printed Page 73218
    * * * * *

    3.2.2 * * *

    Table 5—Test Operating Conditions 1 for Medium-Temperature CO 2 Unit Coolers

    Test titleUnit cooler air entering dry-bulb, °FUnit cooler air entering relative humidity, %Suction dew point temp,3 °FLiquid inlet bubble point temperature, °FLiquid inlet subcooling, °FCompressor operating modeTest objective
    Off-Cycle Power35<50Compressor OffMeasure unit cooler input wattage during compressor off-cycle, E Fcomp,off  2 .
    Refrigeration Capacity, Ambient Condition A35<5025385Compressor OnDetermine Net Refrigeration Capacity of Unit Cooler, q mix,rack
    Notes:
    1  Superheat shall be set as indicated in the installation instructions. If no superheat specification is given a default superheat value of 6.5 °F shall be used.
    2  Measure off-cycle power as described in sections C3 and C4.2 of AHRI 1250–2020.
    3  Suction Dew Point shall be measured at the Unit Cooler Exit conditions.
    * * * * *

    3.2.3 * * *

    Table 9—Test Operating Conditions for Two-Capacity Low-Temperature Outdoor Dedicated Condensing Units

    Test titleSuction dew point, °FReturn gas, °FCondenser air entering dry-bulb, °FCondenser air entering wet-bulb, °F 1Compressor operating mode
    Capacity, Condition A, Low Capacity−2259575Low Capacity, k=1.
    Capacity, Condition A, High Capacity−2259575High Capacity, k=2.
    Off-Cycle, Condition A9575Compressor Off.
    Capacity, Condition B, Low Capacity−2255954Low Capacity, k=1.
    Capacity, Condition B, High Capacity−2255954High Capacity, k=2.
    Off-Cycle, Condition B5954Compressor Off.
    Capacity, Condition C, Low Capacity−2253534Low Capacity, k=1.
    Capacity, Condition C, High Capacity−2253534High Capacity, k=2.
    Off-Cycle, Condition C3534Compressor Off.
    Notes:
    1  Required only for evaporative condensing units ( e.g., incorporates a slinger ring).
    * * * * *

    3.2.4 * * *

    Table 13—Test Operating Conditions for Variable- or Multiple-Capacity Low-Temperature Outdoor Dedicated Condensing Units

    Test titleSuction dew point, °FReturn gas, °FCondenser air entering dry-bulb, °FCondenser air entering wet-bulb, °F 1Compressor operating mode
    Capacity, Condition A, Minimum Capacity−2259575Minimum Capacity, k=1.
    Capacity, Condition A, Intermediate Capacity−2259575Intermediate Capacity, k=i.
    Capacity, Condition A, Maximum Capacity−2259575Maximum Capacity, k=2.
    Off-Cycle, Condition A9575Compressor Off.
    Capacity, Condition B, Minimum Capacity−2255954Minimum Capacity, k=1.
    Capacity, Condition B, Intermediate Capacity−2255954Intermediate Capacity, k=i.
    Capacity, Condition B, Maximum Capacity−2255954Maximum Capacity, k=2.
    Off-Cycle, Condition B5954Compressor Off.
    Capacity, Condition C, Minimum Capacity−2253534Minimum Capacity, k=1.
    Capacity, Condition C, Intermediate Capacity−2253534Intermediate Capacity, k=i.
    Capacity, Condition C, Maximum Capacity−2253534Maximum Capacity, k=2.
    Start Printed Page 73219
    Off-Cycle, Condition C3534Compressor Off.
    Notes:
    1  Required only for evaporative condensing units ( e.g., incorporates a slinger ring).

    Table 14—Test Operating Conditions for Variable- or Multiple-Capacity Low-Temperature Indoor Dedicated Condensing Units

    Test titleSuction dew point, °FReturn gas, °FCondenser air entering dry-bulb, °FCondenser air entering wet-bulb, °F 1Compressor operating mode
    Capacity, Condition A, Minimum Capacity−2259075Minimum Capacity, k=1.
    Capacity, Condition A, Intermediate Capacity−2259075Intermediate Capacity, k=i.
    Capacity, Condition A, Maximum Capacity−2259075Maximum Capacity, k=2.
    Off-Cycle, Condition A9075Compressor Off.
    Notes:
    1  Required only for evaporative condensing units ( e.g., incorporates a slinger ring).
    * * * * *
    End Supplemental Information

    [FR Doc. 2023–18531 Filed 10–24–23; 8:45 am]

    BILLING CODE 6450–01–P

Document Information

Effective Date:
10/25/2023
Published:
10/25/2023
Department:
Energy Department
Entry Type:
Rule
Action:
Final rule; correcting amendments.
Document Number:
2023-18531
Dates:
Effective October 25, 2023.
Pages:
73215-73219 (5 pages)
Docket Numbers:
EERE-2017-BT-TP-0010
RINs:
1904-AD78: Test Procedures for Walk-In Coolers and Walk-In Freezers
RIN Links:
https://www.federalregister.gov/regulations/1904-AD78/test-procedures-for-walk-in-coolers-and-walk-in-freezers
Topics:
Administrative practice and procedure, Confidential business information, Energy conservation, Household appliances, Imports, Incorporation by reference, Intergovernmental relations, Reporting and recordkeeping requirements, Small businesses
PDF File:
2023-18531.pdf
Supporting Documents:
» 2022-01-25 Krack MS Series Unit Coolers Technical Bulletin: MSUC_013_012522
» 2022-05-09 Transcript Of Proceedings In The Matter Of: Walk-In Coolers And Freezers Test Procedure Notice Of Proposed Rulemaking, Docket No.: EERE-2017-BT-TP-0010
» 2022-05-09 Meeting Attendee list (registration-20220509143631)
» 2022-05-09 Meeting Presentation: Walk-in Coolers and Freezers Test Procedure Notice of Proposed Rulemaking, Public Meeting – May 9, 2022
» WhitePaper: Development of Test Conditions for Two-Capacity, Multiple-Capacity, and Variable-Capacity Condensing Units
» 2020-06-09 Copeland Digital Outdoor Refrigeration Unit, X-Line Series Presentation
» 2018 Optyma™ Plus INVERTER Application Guidelines
» 2020-04 Copeland™ F-Line Air-cooled and water-cooled condensing units Product Information Brochure (2020ECT-1_F-Line (4/20))
» Copeland ™ Digital Outdoor Refrigeration Unit X-line Series Brochure
» Next-Gen WC-Series™ 1/2 to 6 HP Indoor Water Cooled Condensing Units Publication (Publication No. RU-RWC-1120A)
CFR: (1)
10 CFR 429.70