96-7528. Trade Regulation Rule: Labeling and Advertising of Home Insulation  

  • [Federal Register Volume 61, Number 61 (Thursday, March 28, 1996)]
    [Rules and Regulations]
    [Pages 13659-13666]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 96-7528]
    
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    FEDERAL TRADE COMMISSION
    
    16 CFR Part 460
    
    
    Trade Regulation Rule: Labeling and Advertising of Home 
    Insulation
    
    AGENCY: Federal Trade Commission.
    
    ACTION: Final rule.
    
    -----------------------------------------------------------------------
    
    SUMMARY: The Federal Trade Commission (the ``Commission'' or ``FTC'') 
    announces it is retaining its Trade Regulation Rule Concerning the 
    Labeling and Advertising of Home Insulation (``R-value Rule'' or 
    ``Rule'') and adopting non-substantive amendments to the Rule. The 
    Commission amends section 460.5(a) of the R-value Rule to allow use of 
    the R-value test procedure in American Society of Testing and Materials 
    (``ASTM'') standard test method C 1114-95. The Commission also amends 
    sections 460.5(a), 460.5(a)(2), 460.5(b), and 460.5(d)(1) to specify 
    revised versions of additional ASTM standards that are required for 
    determining the R-value of home insulation. Further, the Commission 
    amends the Rule to add a summary of the exemptions from specific 
    requirements of the Rule that the Commission previously granted for 
    certain classes of persons covered by the Rule. Last, the Commission 
    adopts a non-substantive amendment to revise section 460.10 to cross-
    reference the Commission's enforcement policy statement for foreign 
    language advertising in 16 CFR 14.9 and to delete the current Appendix 
    to the Rule, which merely repeats the text of 16 CFR 14.9.
    
    EFFECTIVE DATE: The amendments are effective on April 29, 1996. The 
    incorporation by reference of certain publications listed in the 
    regulations is approved by the Director of the Federal Register as of 
    April 29, 1996.
    
    FOR FURTHER INFORMATION CONTACT: Kent C. Howerton, Attorney, Federal 
    Trade Commission, Washington, DC 20580, (202) 326-3013 (voice), (202) 
    326-3259 (fax).
    
    SUPPLEMENTARY INFORMATION:
    
    I. Introduction
    
        On April 6, 1995, as part of its oversight responsibilities and its 
    program to review all current Commission rules and guides periodically, 
    the Commission solicited public comments about the economic impact of 
    and current need for the R-value Rule, 60 FR 17492 (1995).1 At the 
    same time, the Commission solicited comments on a petition 
    (``Petition'') requesting the Commission to approve an additional 
    (fifth) ASTM R-value test procedure as an optional, but not required, 
    test procedure for determining the R-value of home insulation under the 
    Rule.
    
        \1\ The Commission reviewed the Rule in 1985 under the 
    Regulatory Flexibility Act, 5 U.S.C. 610, to determine the economic 
    impact of the Rule on small entities. Based on that review, the 
    Commission determined that: There was a continuing need for the 
    Rule; there was no basis to conclude that the Rule had a significant 
    impact on a substantial number of small entities; there was no basis 
    to conclude that the Rule should be amended to minimize its economic 
    impact on small entities; the Rule did not generally overlap, 
    duplicate, or conflict with other regulations; and technological, 
    economic, and other changes had not affected the Rule in any way 
    that would warrant amending the Rule. 50 FR 13246 (1985).
    ---------------------------------------------------------------------------
    
        The Commission received 42 comments in response to the April 6, 
    1995 notice.2 The commenters included the following parties: 
    Manufacturers of cellular plastics, cellulose, mineral fiber, and 
    reflective insulation products; manufacturers of structural insulated 
    panels; trade associations comprised of manufacturers of insulation 
    products and structural insulated panels, professional installers, and 
    roofing contractors; independent technical consultants to industry; a 
    government contractor; and individual consumers. Specific issues 
    addressed by the commenters are described below in Parts III through 
    VI.
    
        \2\ Plymouth Foam Products (``Plymouth''), comment number #01; 
    Advanced Foil Systems (``AFS''), #02; W.H. Porter, Inc. 
    (``Porter''), #03; Benchmark Foam, Inc. (``Benchmark''), #04; Big 
    Sky Insulations, Inc. (``Big Sky''), #05; Rock Wool Manufacturing 
    Co. (``Rock Wool Mfg./1''), #06; Rose E. Kettering (``Kettering''), 
    #07; Matt Anderson (``Anderson''), #08; Marilyn Raeth (``Raeth''), 
    #09; James A. McGarry (``McGarry''), #10; Structural Insulated Panel 
    Association (``SIPA''), #11; Tierra Consulting Group (``Tierra''), 
    #12; EPS Molders Association (``EPSMA''), #13; Western Insulfoam, 
    Division of Premier Industries, Inc. (``Western''), #14; Fi-Foil 
    Co., Inc. (``Fi-Foil/Nowman''), #15; Regal Industries, Inc. 
    (``Regal''), #16; Insulation Contractors Association of America 
    (``ICAA/1''), #17; England & Associates (``England''), #18; 
    Cellulose Insulation Manufacturers Association (``CIMA''), #19; 
    GreenStone Industries (``Greenstone/Tranmer''), #20; Styropor 
    Business, BASF Corporation (``BASF''), #21; Hamilton Mfg., Inc. 
    (``Hamilton''), #22; Energy Control, Inc. (``ECI''), #23; North 
    American Insulation Manufacturers Association (``NAIMA''), #24; The 
    Celotex Corporation (``Celotex''), #25; Tennessee Technological 
    University, (``TN Tech''), #26; Superior Aluminum Insulation Inc. 
    (``Superior''), #27; Oak Ridge National Laboratory (``ORNL/
    Yarbrough''), #28; Oak Ridge National Laboratory (``ORNL/Wilkes''), 
    #29; Polyisocyanurate Insulation Manufacturers Association 
    (``PIMA''), #30; Midwest Roofing Contractors Association (``MRCA''), 
    #31; GreenStone Industries (``GreenStone/Smith''), #32; Insulspan, 
    Inc. (``Insulspan''), #33; Clayville Insulation (``Clayville''), 
    #34; Tascon, Inc. (``Tascon''), #35; FischerSips Inc. 
    (``FischerSips''), #36; Dow Chemical Canada Inc. (``Dow/Canada''), 
    #37; AFM Corporation (``AFM''), #38; Rock Wool Manufacturing Co. 
    (``Rock Wool Mfg./2''), #39; Insulation Contractors Association of 
    America (``ICAA/2''), #40; Corbond Corp. (``Corbond''), #41; Fi-Foil 
    Co., Inc. (``Fi-Foil/Lippy''), #42. The April 6, 1995 notice is 
    filed as document number B172394. The comments submitted in response 
    to the that notice are filed as document numbers B17239400001, 
    B17239400002, etc. In today's notice, the comments are cited as #01, 
    #02, etc. The Commission's staff added an additional letter from the 
    Petitioner, R. S. Graves, R & D Services, Inc. This letter, cited as 
    Graves, #43, was not filed as a comment in response to the April 6, 
    1995 notice, but instead, as a response to a request for 
    clarification from the Commission's staff. See Part V and note 64, 
    infra.
    ---------------------------------------------------------------------------
    
    II. Requirements of the R-Value Rule
    
        The Commission promulgated the R-value Rule under section 18 of the 
    FTC Act, 15 U.S.C. 57a, on August 27, 1979.3 The Rule became 
    effective on September 29, 1980, 45 FR 54702 (1980).
    
        \3\ Final trade regulation rule (``Statement of Basis and 
    Purpose'' or ``SBP''), 44 FR 50218 (1979).
    ---------------------------------------------------------------------------
    
        The R-value Rule covers home insulation products. The Rule defines 
    ``insulation'' as any product mainly used to slow down heat flow, for 
    example through a house's exterior walls, attic, floors over crawl 
    spaces, or basement. It defines ``home insulation'' as insulation used 
    in old or new houses, condominiums, cooperatives, apartments, modular 
    homes, and mobile homes. The Rule does not cover insulation products 
    sold for use in commercial or industrial buildings, such as offices or 
    factories. It does not apply to other products with insulating 
    characteristics, such as storm windows or doors.
        The Rule applies to home insulation manufacturers, professional 
    installers, retailers, and new home sellers (including sellers of 
    manufactured or mobile homes). It also applies to testing laboratories 
    that conduct R-value tests for home insulation manufacturers or other 
    sellers who use the test results as the basis for making R-value claims 
    about home insulation products.
        The Rule requires that those who manufacture or sell thermal 
    insulation products for use in residential structures disclose specific 
    information about the thermal performance of the insulation at
    
    [[Page 13660]]
    the point of sale (on product labels, manufacturers' fact sheets, and 
    receipts or contracts to purchasers from professional installers and 
    new home sellers), and in advertising and other promotional materials 
    that contain certain claims. Thermal performance is described by the 
    product's R-value, which varies among insulation types and forms and 
    among specific products of the same type and form.4 ``R-value'' is 
    the recognized numerical measure of the ability of an insulation 
    product to restrict the flow of heat and, therefore, to reduce energy 
    costs. The higher the R-value, the better the product's insulating 
    ability. The major reason consumers purchase thermal insulation is to 
    reduce energy expenditures to heat and cool their homes. The Rule 
    requires sellers to have adequate substantiation for these R-value 
    disclosures and for any energy savings claims they make.
    
        \4\ ``Type'' refers to the material from which the insulation is 
    made, e.g., fiberglass or cellulose. ``Form'' refers to the physical 
    form of the product, e.g., batts, loose-fill, or rigid boardstock. 
    Most home insulation products are ``mass'' insulations, which 
    restrict the flow of heat through the product's mass. ``Reflective'' 
    insulations (which also are covered by the Rule), on the other hand, 
    restrict heat flow by reflecting back radiant heat and must be 
    installed facing an air space.
    ---------------------------------------------------------------------------
    
        The R-value Rule is designed to enable consumers to compare the 
    thermal performance of competing home insulation products when they 
    make purchasing decisions. To accomplish this purpose, the Rule 
    requires sellers (including insulation manufacturers, professional 
    installers, new home sellers, and retailers who sell insulation to 
    consumers) to disclose the insulation product's R-value and related 
    information, based on uniform standards. This information enables 
    consumers to evaluate how well a particular insulation product is 
    likely to perform, to determine whether the cost of the insulation is 
    justified, and to make meaningful cost-benefit purchase decisions among 
    competing products.
    
    III. Regulatory Review
    
        The Commission has determined, as part of its oversight 
    responsibilities, to review all current Commission rules and guides 
    periodically. These reviews seek information about the costs and 
    benefits of the Commission's rules and guides and their regulatory and 
    economic impact. The information obtained assists the Commission in 
    identifying rules and guides that warrant modification or recision. In 
    the April 6, 1995 notice, the Commission solicited comments on, among 
    other things, the economic impact of and the continuing need for the R-
    value Rule, possible conflict between the Rule and state, local, or 
    other federal laws or regulations, and the effect on the Rule of any 
    technological, economic, or other industry changes. The Commission also 
    solicited comments on whether the Rule should be revised to require the 
    use of different test procedures or standards than those currently 
    specified, and whether there are insulation products for which the Rule 
    does not sufficiently address product-specific issues relating to 
    testing or preparation of test specimens.
    
    A. Need for the Rule, Benefits, Costs, and Other Burdens
    
    1. Current Need for the Rule
        Thirty-one comments specifically addressed the current need for the 
    Rule. Thirty comments stated that there is a continuing need for the 
    Rule and supported keeping it in place.5 Only one commenter, 
    Benchmark, implied that the Rule was not needed, stating that the costs 
    of complying with the Rule far outweigh the benefits it confers.6 
    Benchmark did not explain how it reached this conclusion.
    
        \5\ AFS, #02 (must stay in place, keep regulations that work); 
    Porter, #03 (continue and strengthen); Rock Wool Mfg./1, #06 
    (provides basic guidelines by which consumers better assured of 
    receiving full value); Kettering, #07 (R-values must be maintained 
    or consumer has no guideline and inferior products will be passed 
    off on the public); Anderson, #08, at 2-3 (labeling ensures 
    consumers can easily select products with the R-value they want); 
    Raeth, #09 (eliminating Rule would be a great disservice to 
    consumers, consumers would not know the value of what purchasing); 
    McGarry, #10 (do not eliminate or weaken, uses label information to 
    compare when purchasing); SIPA, #11, at 1 (retain); Tierra, #12, at 
    1-2 (serves useful public purpose); Western, #14, at 1; Fi-Foil/
    Nowman, #15, at 1 (serves useful purpose); Regal, #16, at 1 
    (retain); ICAA/1, #17, at 1 (necessary); England, #18, at 1 (need 
    stronger today than ever); CIMA, #19, at 1 (valuable protection for 
    consuming public); Greenstone/Tranmer, #20, at 1 (critical to 
    consumers; centralized labeling requirements necessary to maintain 
    consistency in products, avoid costly production costs resulting 
    from rules differing from region to region, and encourage 
    development of advanced products); BASF, #21, at 1 (urges be 
    retained); Hamilton, #22, at 1 (still needed in today's market); 
    ECI, #23 (good Rule that should be continued); NAIMA, #24, at 1 
    (should be maintained, market place would be chaotic in its 
    absence); Celotex, #25, at 1 (continuing need), at 7 (supports the 
    Rule); TN Tech, #26, at 1 (extremely important to industry and 
    consuming public); ORNL/Wilkes, #29, at 1 (supports keeping, 
    Commission to be commended for promulgating and enforcing the Rule); 
    PIMA, #30, at 2 (continuing need), at 9 (vigorously supports 
    retaining and enforcing Rule and applauds FTC for its efforts in 
    this regard); Greenstone/Smith, #32, at 1 (provides a viable means 
    of creating broader consumer awareness of insulation value and 
    maintaining even playing field, without Rule sellers would take 
    advantage of naive consumers); Insulspan, #33, at 1 (retain); 
    Clayville, #34, at 3 (still needed to keep a level playing field); 
    FischerSips, #36, at 1 (retain); Fi-Foil/Lippy, #42 (should be 
    continued to enable general public to evaluate insulation products). 
    See also, Rock Wool Mfg./1, #06 (fully supports ICAA's submittal).
        \6\ Benchmark, #04.
    ---------------------------------------------------------------------------
    
        Based on the comments, the Commission determines that there is a 
    continuing need for the Rule.
    2. Benefits and Costs to Purchasers
        Twenty-four comments described the benefits the Rule confers on 
    purchasers.7 In summary, the comments described the major benefits 
    of the Rule to consumers as:
    
        \7\ Porter, #03; Rock Wool Mfg./1, #06; Anderson, #08, at 2-3; 
    McGarry, #10; Tierra, #12, at 1-2; Western, #14, at 1; Fi-Foil/
    Nowman, #15, at 1; ICAA/1, #17, at 1; England, #18, at 1; CIMA, #19, 
    at 1; Greenstone/Tranmer, #20, at 1; Hamilton, #22, at 1; TN Tech, 
    #26, at 1; ORNL/Wilkes, #29, at 1-2; PIMA, #30, at 2-3, 9; 
    Greenstone/Smith, #32, at 1; Clayville, #34, at 1; Celotex, #35, at 
    1; Fi-Foil/Lippy, #42. See also, Rock Wool Mfg./1, #06; Kettering, 
    #07; Raeth, #09; ECI, #23; NAIMA, #24, at 1.
    ---------------------------------------------------------------------------
    
         Increasing consumer awareness of the benefits of 
    insulation; 8
    
        \8\ ORNL/Wilkes, #29, at 1; Greenstone/Smith, #32, at 1.
    ---------------------------------------------------------------------------
    
         Giving consumers the basic thermal performance information 
    they need to compare insulation products and select those with the R-
    value they want,9 at little or no cost; 10
    
        \9\ Anderson, #08, at 2-3; McGarry, #10; Greenstone/Tranmer, 
    #20, at 1; PIMA, #30, at 2-3; Fi-Foil/Lippy, #42. See Raeth, #09; 
    ECI, #23.
        \10\ ICAA/1, #17, at 1. See also Rock Wool Mfg./1, #06.
    ---------------------------------------------------------------------------
    
         Giving consumers R-value information in a uniform manner 
    that facilitates easy comparison of competing products; 11
    
        \11\ Tierra, #12, at 1-2; Fi-Foil/Nowman, #15, at 1; England, 
    #18, at 1; PIMA, #30, at 3; Celotex, #35, at 1.
    ---------------------------------------------------------------------------
    
         Helping ensure that R-value claims are substantiated so 
    consumers receive what they are promised; 12
    
        \12\ Porter, #03; Tierra, #12, at 1-2; England, #18, at 1; 
    Hamilton, #22, at 1. See Kettering, #07; Raeth, #09; ECI, #23; 
    NAIMA, #24, at 1.
    ---------------------------------------------------------------------------
    
         Helping consumers save energy (and heating and cooling 
    costs) by preventing misrepresentations about R-values of insulation 
    products,13 and by setting standards for the proper installation 
    of insulation products; 14
    
        \13\ Porter, #03. See Rock Wool Mfg./1, #06.
        \14\ See Rock Wool Mfg./1, #06.
    ---------------------------------------------------------------------------
    
         Saving consumers money by eliminating sales and marketing 
    practices that lead them to overinsulate or underinsulate; 15
    
        \15\ CIMA, #19, at 1.
    ---------------------------------------------------------------------------
    
         Improving the quality 16 and consistency 17 of 
    home insulation, encouraging the development of advanced 
    products,18 and preventing the sale of inferior products; 19 
    and
    
        \16\ TN Tech, #26, at 1.
        \17\ Greenstone/Tranmer, #20, at 1.
        \18\ Id.
        \19\ See Kettering, #07.
        
    [[Page 13661]]
    
    ---------------------------------------------------------------------------
    
         Reducing the rate of depletion of our nation's limited 
    energy resources by helping consumers conserve energy 
    expenditures.20
    
        \20\ ORNL/Wilkes, #29, at 1.
    ---------------------------------------------------------------------------
    
        In addition to the benefits described above, Greenstone/Smith 
    explained that utility companies have embraced the Rule and developed 
    their own energy savings programs that depend on the Rule to protect 
    consumers from fraudulent acts.21 Greenstone/Smith also stated 
    that state departments of consumer affairs have used the Rule as a 
    model in writing their laws, which has led to state enforcement actions 
    that generated publicity and educated consumers. Greenstone/Smith 
    further stated that consumers would be in a user-beware condition 
    without the Rule and that sellers would lower their ethical boundaries 
    and take advantage of naive consumers.22
    
        \21\ Greenstone/Smith, #32, at 1.
        \22\ Id. See also NAIMA, #24, at 1; ORNL/Wilkes, #29, at 2.
    ---------------------------------------------------------------------------
    
        Sixteen commenters addressed the costs the Rule imposes on 
    purchasers. Fifteen of these commenters stated that they did not 
    believe the Rule imposes significant costs on purchasers.23 Only 
    one, Benchmark, stated that the costs imposed by the Rule outweigh the 
    Rule's benefits.24 In brief, the commenters other than Benchmark 
    expressed the following views concerning costs the Rule imposes on 
    consumers:
    
        \23\ Rock Wool Mfg./1, #06; Tierra, #12, at 2; Western, #14, at 
    1; Fi-Foil/Nowman, #15, at 1; ICAA/1, #17, at 1; England, #18, at 1; 
    CIMA, #19, at 1; Greenstone/Tranmer, #20, at 2; Hamilton, #22, at 1; 
    Celotex, #25, at 1; TN Tech, #26, at 1; ORNL/Wilkes, #29, at 2-3; 
    PIMA, #30, at 3, 9; Greenstone/Smith, #32, at 1; Clayville, #34, at 
    1.
        \24\ Benchmark, #04.
    ---------------------------------------------------------------------------
    
         no cost; 25
    
        \25\ Rock Wool Mfg./1, #06; ICAA/1, #17, at 1; CIMA, #19, at 1; 
    Hamilton, #22, at 1.
    ---------------------------------------------------------------------------
    
         Minimal or insignificant cost,26 or small cost when 
    spread over volume of production; 27
    
        \26\ Celotex, #25, at 1; TN Tech, #26, at 1; PIMA, #30, at 3, 9; 
    Clayville, #34, at 1.
        \27\ Greenstone/Tranmer, #20, at 2; ORNL/Wilkes, #29, at 2-3.
    ---------------------------------------------------------------------------
    
         Very small cost imposed is offset by improved product 
    quality and the benefit-to-cost ratio is very large; 28
    
        \28\ TN Tech, #26, at 1. See Greenstone/Tranmer, #20, at 2.
    ---------------------------------------------------------------------------
    
         Any cost already has been born by manufacturers and is 
    embedded in product pricing; 29
    
        \29\ Tierra, #12, at 2; Fi-Foil/Nowman, #15, at 1.
    ---------------------------------------------------------------------------
    
         Required testing should already have been done so the only 
    additional cost is the Fact Sheet, which can be produced at minimal 
    expense; 30
    
        \30\ Greenstone/Smith, #32, at 1.
    ---------------------------------------------------------------------------
    
         Possibly has imposed cost, but not nearly the waste of 
    money that would have occurred without the Rule; 31 and
    
        \31\ Western, #14, at 1.
    ---------------------------------------------------------------------------
    
         Has saved consumers on cost.32
    
        \32\ England, #18, at 1.
    ---------------------------------------------------------------------------
    
        Based on the comments, the Commission determines that the Rule 
    provides substantial benefits to consumers, while imposing no 
    significant costs on them.
     3. Benefits and Burdens or Costs to Firms
        Ten comments addressed the benefits provided to firms covered by 
    the Rule.33 According to the comments, the Rule benefits firms by:
    
        \33\ Porter, #03; Tierra, #12, at 1-2; Western, #14, at 1, but 
    see, at 2; England, #18, at 2; Greenstone/Tranmer, #20, at 3; 
    Celotex, #25, at 2; PIMA, #30, at 2, 4, 9; Greenstone/Smith, #32, at 
    1; Clayville, #34, at 1, 3. See NAIMA, #24, at 1.
    ---------------------------------------------------------------------------
    
         Creating a level playing field through standardized 
    guidelines for labeling, testing, and evaluation, which promote 
    legitimate competition and make it easier for honest manufacturers to 
    compete; 34
    
        \34\ Porter, #03; Tierra, #12, at 1-2; Western, #14, at 1, but 
    see, at 2 (not much benefit for Western); Greenstone/Tranmer, #20, 
    at 3; Celotex, #25, at 2; Clayville, #34, at 3. See also NAIMA, #24, 
    at 1 (marketplace would be chaotic in its absence).
    ---------------------------------------------------------------------------
    
         Providing a more even market place in which it is easier 
    for industry to attempt to regulate itself; 35
    
        \35\ England, #18, at 2.
    ---------------------------------------------------------------------------
    
         Enhancing competition by enabling suppliers to convey 
    truthfully and meaningfully the insulation properties of their 
    products; 36 and
    
        \36\ PIMA, #30, at 2.
    ---------------------------------------------------------------------------
    
         Providing guidelines for product testing and evaluation 
    and creating confidence in the residential buyer's mind.37
    
        \37\ Id. at 4.
    ---------------------------------------------------------------------------
    
        As pointed out in Part III.A.2, above, Greenstone/Smith stated that 
    individual utility companies have developed energy savings programs 
    that depend on the Rule to protect consumers from fraudulent 
    acts.38 According to the commenter, by encouraging consumers to 
    insulate homes, these programs benefit firms by generating an ever-
    increasing demand for products covered by the Rule.
    
        \38\ Greenstone/Smith, #32, at 1 .
    ---------------------------------------------------------------------------
    
        Fourteen comments addressed the burdens or costs imposed on firms 
    covered by the Rule. Eleven of these stated that the Rule had not 
    imposed any significant costs on firms.39 Tierra stated merely 
    that any costs due to the Rule already were imbedded in the pricing of 
    the products.40 Fi-Foil/Nowman stated that the Rule had a 
    substantial economic impact on industry members originally because it 
    required redesigning and reprinting packaging and promotional materials 
    to meet the labeling requirements, but that these costs already had 
    been borne by manufacturers.41 Benchmark stated that the costs 
    imposed by the Rule outweigh its benefits.42
    
        \39\ Rock Wool Mfg./1, #06 (not aware of any significant added 
    cost); Western, #14, at 2 (for it $0); ICAA/1, #17, at 1 (no 
    significant cost burden); England, #18, at 2 (none, because what 
    Rule requires should be done anyway); CIMA, #19, at 2 (few 
    incremental costs of compliance since requirements are based on 
    existing industry and government standards); Greenstone/Tranmer, 
    #20, at 3 (does not impose large financial burden); Hamilton, #22, 
    at 1 (do not think it has imposed additional costs); Celotex, #25, 
    at 2 (no significant burdens or costs since R-value data is 
    necessary for marketing, quality control, and research purposes); 
    PIMA, #30, at 4 (no significant burdens or costs, benefits clearly 
    outweigh any burdens or costs), at 9 (does not impose significant 
    burden or cost); Greenstone/Smith, #32, at 1 (required testing 
    should already have been done when Commission issued Rule and no 
    additional tests were required, only additional cost was Fact Sheet 
    which could be produced at minimal expense to manufacturer); 
    Clayville, #34, at 1 (doesn't believe the Rule has imposed any 
    excessive costs on manufacturers or contractors).
        \40\ Tierra, #12, at 2.
        \41\ Fi-Foil/Nowman, #15, at 1.
        \42\ Benchmark, #04.
    ---------------------------------------------------------------------------
    
        Based on the comments, the Commission determines that the Rule 
    benefits firms by creating a level playing field that promotes 
    competition, by providing a market place in which industry can more 
    easily regulate itself, by providing guidelines to industry for product 
    testing and evaluation, and by creating consumer confidence. The 
    Commission also determines that the Rule does not impose significant 
    ongoing costs on firms.
    
    B. Other Federal, State, or Local Laws or Regulations
    
        Nine comments addressed the existence of other federal, state, or 
    local laws or regulations. None of the commenters was aware of any 
    conflicts with other federal, state, or local laws or 
    regulations.43 England stated that the Rule strengthens other 
    federal, state, and local laws and regulations.44 Celotex and PIMA 
    explained that the Rule is a consumer protection regulation, which does 
    not address issues such as building energy conservation standards that 
    are regulated elsewhere at the federal, state, and local levels.45 
    Greenstone/Smith stated that the Rule has been precedent-setting rather 
    than conflicting, and that
    
    [[Page 13662]]
    utility companies have embraced the Rule's requirements and developed 
    energy-saving programs that depend on the Rule to protect consumers 
    from fraudulent acts.46
    
        \43\ Rock Wool Mfg./1, #06; Tierra, #12, at 3; Western, #14, at 
    3; England, #18, at 2; CIMA, #19, at 2; Greenstone/Tranmer, #20, at 
    4; Celotex, #25, at 2; PIMA, #30, at 5; Greenstone/Smith, #32, at 1.
        \44\ England, #18, at 2 .
        \45\ Celotex, #25, at 2; PIMA, #30, at 5.
        \46\ Greenstone/Smith, #32, at 1.
    ---------------------------------------------------------------------------
    
        Based on the comments, the Commission determines that there is no 
    reason to believe that the Rule conflicts with other federal, state, or 
    local laws or regulations.
    
    IV. Adoption of Current ASTM Standards
    
        The Rule currently requires that the R-value of each home 
    insulation product be determined based on tests conducted according to 
    ASTM C 177-85, C 236-87, C 518-85, or C 976-82.47 It requires that 
    R-values based upon heat flux measurements under C 177-85 or C 518-85 
    be reported in accordance with ASTM standard practice C 1045-85. It 
    also requires that, for loose-fill cellulose, the tests be conducted at 
    the settled density determined under ASTM C 739-88 (``Standard 
    Specification for Cellulosic Fiber (Wood-Base) Loose-Fill Thermal 
    Insulation'').48
    
        \47\ In citations of ASTM standards, the letter and first series 
    of numbers refer to the basic standard; the number following the 
    hyphen refers to the version of the standard (denoting the year in 
    which the version was adopted and published by ASTM).
        \48\ This section discusses only the comments that recommended 
    the Commission revise the Rule concerning specific ASTM test 
    procedures and other standards that currently are required by the 
    Rule. It does not discuss the comments that recommended the 
    Commission adopt additional or different ASTM or other test 
    procedures or standards that are not currently required by the Rule. 
    See Part VI, infra.
    ---------------------------------------------------------------------------
    
        Four comments discussed which versions of specified ASTM test 
    procedures or other standards should be required by the Rule. Celotex 
    and PIMA recommended that the Commission revise the Rule to require the 
    use of current versions of required ASTM standards that are 
    incorporated into the Rule. Specifically, they recommended that the 
    Commission amend the Rule to require use of the following versions of 
    ASTM standards: ASTM C 177-85 (1993), ASTM C 236-89 (1993), ASTM C 518-
    91, ASTM C 976-90, ASTM C 1045-90.49 NAIMA recommended that the 
    Commission revise section 460.5(a)(2) to require settled density 
    testing of loose-fill cellulose according to C 739-91.50 No 
    comments opposed adoption of these current versions of the ASTM 
    standards.
    
        \49\ Celotex, #25, at 3; PIMA, #30, at 5. Both comments stated 
    that the 1993 revisions to C 177-85 and C 236-89 (the year 1993 is 
    indicated in parentheses in the standards) were editorial only.
        \50\ NAIMA, #24, at 2.
    ---------------------------------------------------------------------------
    
        NAIMA pointed out that an alternative to referencing current 
    versions of ASTM standards would be to omit the specific version and 
    rely on the language in section 460.7 of the Rule, 16 CFR 460.7.51 
    Section 460.7 provides that updated, final ASTM test methods 
    automatically replace the old ones in the Rule 90 days after 
    publication by ASTM. Greenstone/Smith agreed with this approach.52
    
        \51\ Id. at 7.
        \52\ Greenstone/Smith, #32, at 3.
    ---------------------------------------------------------------------------
    
        ASTM was organized in 1898. A not-for-profit organization, it is 
    one of the largest voluntary standards-development organizations in the 
    world. ASTM's members (approximately 36,000 worldwide) include 
    producers, users, ultimate consumers, and those having a general 
    interest (including government and academia). Through 132 standards-
    writing committees, ASTM publishes more than 9,500 standards each year. 
    Membership in ASTM is open to all interested parties concerned with the 
    fields in which ASTM is active.53 ASTM standards are developed 
    through a consensus-type process and are used voluntarily. They become 
    legally binding only when a government body references them in 
    regulations, or when they are cited in a contract. ASTM standards are 
    subject to revision at any time by the responsible technical committee 
    and must be reviewed every five years, and if not revised, either 
    reapproved or withdrawn.54 ASTM's C-16 Committee on Thermal 
    Insulation is the standards-writing committee responsible for virtually 
    all of the ASTM standards referenced in the R-value Rule.
    
        \53\ 1995 Annual Book of ASTM Standards, Section 4, Volume 04.06 
    (Thermal Insulation; Environmental Acoustics), at iii.
        \54\ Id. at iv.
    ---------------------------------------------------------------------------
    
        Section 460.7 of the Rule provides for automatic incorporation into 
    the Rule of revisions to these ASTM test procedures. As part of this 
    automatic incorporation, the Commission originally cited in the Rule 
    only the basic test procedures and other standards, not the specific 
    version of each then in effect. Under section 460.7, when ASTM changed 
    a test procedure required by the Rule, the new version automatically 
    replaced the old one in the Rule 90 days after ASTM first published the 
    change.55 In 1990, the Commission amended the Rule to specify the 
    version of each ASTM test procedure that would be required in the 
    future. 55 FR 10053 (1990). The Commission explained that, because it 
    previously had taken no action to consider any of the revisions to the 
    required test procedures that ASTM had adopted since the Commission 
    promulgated the Rule, the Commission in effect had adopted the revised 
    procedures. Id. at 10054.
    
        \55\ Under section 460.7, the Commission's staff or a person 
    affected by the change can petition the Commission during the 90-day 
    period not to adopt the change or to reopen the rulemaking 
    proceeding to consider it further.
    ---------------------------------------------------------------------------
    
        The Office of the Federal Register (``OFR'') specifies additional 
    procedures that federal agencies must follow when they promulgate rules 
    requiring the use of private standards that are not printed in full in 
    the Code of Federal Regulations (``CFR'') (i.e., when they incorporate 
    private standards by reference). Section 51.1(f) of OFR's regulations 
    states that incorporation by reference is limited to the edition of the 
    publication that is approved by the Director of the Federal Register. 1 
    CFR 51.1(f). Section 51.9 of OFR's regulations requires that each 
    ``incorporation by reference'' in a federal rule specifically identify 
    the standard to be incorporated, including the title, date, edition, 
    author, publisher, and identification number of the publication. 1 CFR 
    51.9.
        Under Federal Register requirements, therefore, the Commission does 
    not have discretion to require compliance generally with the ``latest'' 
    or ``current'' version of ASTM test procedures or other standards. If 
    ASTM adopts and publishes revised test procedures or other standards 
    required by the Rule, however, the Commission may update its 
    incorporation by reference of these standards by obtaining permission 
    for the incorporation by reference from the Director of the Federal 
    Register and publishing an amendment to the Rule that requires the use 
    of the revised standard in the future.
        ASTM standards C 177-85, C 236-87, C 518-85, C 976-82, C 1045-85, 
    and C 739-88, which currently are specified in the Rule, have been 
    revised by ASTM since the Commission adopted those versions of the 
    standards in 1990.56 Because the Commission has taken no action to 
    consider any of the revised standards adopted by ASTM, and has received 
    no petitions to consider them, section 460.7 of the Rule has 
    authorized, but not required, use of the revised ASTM standards for 
    compliance with the Rule.
    
        \56\ 55 FR 10053 (1990).
    ---------------------------------------------------------------------------
    
        Based on the comments and the text of the revised versions of the 
    ASTM standards recommended by the commenters, the Commission believes 
    that these revisions to the versions of the standards currently 
    required by the Rule have been primarily technical changes or editorial 
    comments, and not significant, substantive revisions. The
    
    [[Page 13663]]
    Commission, therefore, amends the Rule to require use of the revised, 
    current versions of these standards that are published in volume 04.06, 
    section 4, of the 1995 Annual Book of ASTM Standards. Because the 
    revisions appear to be technical changes or editorial comments, not 
    significant, substantive revisions, the Commission determines that 
    these amendments are non-substantive under section 18(d)(2)(B) of the 
    FTC Act, 15 U.S.C. 57a(d)(2)(B).
        The amendments require that all future tests by manufacturers or 
    others to substantiate R-value claims for home insulation products be 
    based on the revised standards. Manufacturers or others whose home 
    insulation products have not changed can continue to rely on tests 
    conducted according to the versions of the standards that were required 
    by the Rule at the time the tests were conducted. Under section 460.7 
    of the Rule, in the future the Commission will accept, but not require, 
    the use of a revised version of any of these standards 90 days after 
    ASTM adopts and publishes the revision. The Commission may, however, 
    reopen the rulemaking proceeding during the 90-day period or at any 
    later time to consider whether it should require use of the revised 
    procedure or reject it under section 460.5 of the Rule, 16 CFR 460.5.
    
    V. Proposed Non-Substantive Amendment to Allow Use of an Additional 
    ASTM R-value Test Procedure
    
        In the April 6, 1995 notice, the Commission also solicited comments 
    on the Petition from Ronald S. Graves, Research Staff Member, Materials 
    Analysis Group, at Martin Marietta Energy Systems, Inc.57 The 
    Petition requested that the Commission include an additional (fifth) 
    ASTM R-value test procedure (``ASTM C 1114-92--Standard Test Method for 
    Steady-State Thermal Transmission Properties by Means of the Thin-
    Heater Apparatus''), as an approved test method for complying with 
    section 460.5(a) of the R-value Rule, 16 CFR 460.5(a). This test method 
    is under the jurisdiction of ASTM Committee C-16 on Thermal 
    Measurements (the ASTM Committee responsible for the other R-value test 
    procedures required by the R-value Rule), and is the direct 
    responsibility of ASTM Subcommittee C16.30 on Thermal Measurements. Mr. 
    Graves is the Chairman of the Thin Heater Task Group within C16.30 that 
    meets semiannually to maintain and keep ASTM C 1114 current.
    
        \57\ 60 FR at 17493-94. Martin Marietta Energy Systems, Inc., 
    operates Oak Ridge National Laboratory (``ORNL'') as a contractor 
    for the U.S. Department of Energy. The Petition, plus attachments, 
    has been placed on the public record of the R-value Rule, File No. 
    R811001, and can be inspected at the Commission's Public Reference 
    Room, Room 130, Sixth Street and Pennsylvania Avenue, NW, 
    Washington, DC.
    ---------------------------------------------------------------------------
    
        Based on the documentation submitted with the Petition, the 
    Commission stated its belief that the accuracy of the ASTM C 1114-92 
    test procedure compared favorably to that of other ASTM R-value test 
    procedures the Commission has adopted under the R-value Rule.58 
    The Commission, therefore, stated that it was considering adopting a 
    non-substantive amendment to section 460.5(a) of the Rule to include 
    ASTM C 1114-92 as an optional, but not required, test procedure for 
    determining the R-value of home insulation. Because the proposed 
    amendment would not impose any new obligations upon parties covered by 
    the Rule, or lessen the protections afforded consumers by the Rule, the 
    Commission stated that the proposed change appeared to be non-
    substantive under section 18(d)(2)(B) of the FTC Act, 15 U.S.C. 
    57a(d)(2)(B). For these reasons, the Commission stated that it did not 
    have to solicit public comment or follow the rulemaking proceedings 
    that would be required for a substantive amendment to the Rule. On the 
    other hand, because the Commission was soliciting comments as part of 
    its regulatory review of the Rule, as a matter of discretion the 
    Commission determined to solicit comments on the Petition at the same 
    time.
    
        \58\ The Commission noted that C 1114-92 had been adopted as an 
    official ASTM standard and, therefore, it appeared that the industry 
    recognized it as an accurate and appropriate test procedure.
    ---------------------------------------------------------------------------
    
        Twelve comments addressed the proposed adoption of ASTM C 1114-92 
    as an optional R-value test procedure. Nine comments recommended that 
    the Commission adopt the test procedure or said that they had no 
    objections.59 Of these, Regal stated that the adoption of the test 
    procedure was ``appropriate.'' Celotex and PIMA stated that the test 
    procedure has shown excellent correlation to the R-value test 
    procedures currently required by the Rule. ORNL/Wilkes stated that the 
    test procedure is a test method that has proven minimal uncertainty, 
    high reproducibility, and broad applicability to a variety of existing 
    and advanced insulation materials.
    
        \59\ Tierra, #12, at 1-3; Fi-Foil/Nowman, #15, at 1; Regal, #16, 
    at 1; England, #18, at 4; Hamilton, #22, at 3; Celotex, #25, at 6; 
    PIMA, #30, at 8; Fi-Foil/Lippy, #42; ORNL/Wilkes, #29, at 2.
    ---------------------------------------------------------------------------
    
        Three comments expressed reservations about the proposed adoption 
    of ASTM C 1114-92. Rock Wool Mfg./1 agreed that the Commission's 
    proposal to adopt the test procedure would be appropriate, if the 
    Commission is assured that the results are comparable with other 
    required tests.60 Western stated that adding C 1114-92 may help 
    reduce burdens or costs imposed by the Rule,61 but later responded 
    specifically to the issue of adopting the test procedure with ``no 
    comment.'' 62 MRCA expressed concern that the test procedure would 
    replace ASTM tests C 177 and C 518, that only two pieces of equipment 
    currently are available to conduct the C 1114 test, that available test 
    equipment is proprietary, and that more labs should use the equipment 
    to obtain comparable test results before the FTC accepts the 
    procedure.63
    
        \60\ Rock Wool Mfg./1, #06.
        \61\ Western, #14, at 2.
        \62\ Id. at 3.
        \63\ MRCA, #31, at 1-2.
    ---------------------------------------------------------------------------
    
        The Commission has determined to adopt a non-substantive amendment 
    to allow use of ASTM C 1114-95 as an optional, but not required, test 
    method for determining the R-value of home insulation under section 
    460.5(a) of the R-value Rule.64 Based on the data submitted with 
    the Petition and the comments, the Commission believes that the 
    accuracy of the ASTM C 1114-95 test procedure compares favorably with 
    the other ASTM R-value test procedures the Commission has adopted under 
    the R-value Rule. Because the amendment imposes no new obligations upon 
    parties covered by the Rule (but merely recognizes the use of an 
    optional R-value test procedure), and because the accuracy of the test 
    procedure compares favorably to the test procedures already required by 
    the Rule, the Commission has determined that this amendment is non-
    substantive under section 18(d)(2)(B) of the FTC Act, 15 U.S.C. 
    57a(d)(2)(B).
    
        \64\ ASTM published revised version C 1114-95 of the standard in 
    August 1995, after the comment period ended. According to the 
    petitioner, the revised version contains merely technical, 
    housekeeping changes. The Commission, therefore, considers the 
    documentation in support of the Petition and the comments to apply 
    to revised version C 1114-95. Graves, #43.
    ---------------------------------------------------------------------------
    
    VI. Other Issues
    
        In addition to the subjects discussed above, the comments raised 
    numerous other issues relating to the Rule. For example:
         Whether the scope of the Rule should be expanded to cover 
    insulation sold for use in the commercial market, the thermal 
    efficiency of building systems (such as insulation used in structural 
    panels), or new products
    
    [[Page 13664]]
    (such as cellulose batts, cotton batts, cotton loose-fill, stabilized 
    cellulose);
         Whether the Rule should require different or new 
    procedures or specify additional requirements for preparing test 
    specimens for certain types of insulation products (such as aging 
    cellular plastics insulations, determining the long-term density of 
    loose-fill mineral fiber insulations);
         Whether the Rule should take into consideration additional 
    factors that can affect the thermal performance of specific products in 
    actual use (such as temperature differences, the effect of convection 
    during winter conditions); and
         Whether the Rule should impose additional requirements on 
    manufacturers or installers to help consumers ensure that the requisite 
    amount of insulation has been installed in their homes.
        Adopting the commenters' recommendations to cover, for example, 
    additional products and to create new Rule requirements would require 
    substantive amendments under section 18(d)(2)(B) of the FTC Act, 15 
    U.S.C. 57a(d)(2)(B). In addition, some of the comments suggested 
    requiring the use of specific proposed ASTM test procedures when ASTM 
    adopts them as final procedures. Because these test procedures are not 
    yet final ASTM standards, it is premature for the Commission to 
    consider requiring that they be used to determine the R-values of home 
    insulation products.
        The Commission is continuing to review the issues raised by the 
    comments and the most efficient and effective methods of dealing with 
    them, which may not necessarily include further rulemaking. For 
    example, the Commission could bring enforcement actions against 
    specific companies whose practices are not covered by the Rule, but who 
    are engaging in unfair or deceptive acts or practices under section 5 
    of the FTC Act, 15 U.S.C. 45. Another option might be for the 
    Commission to provide affected industry members informal guidance 
    instead of adopting substantive amendments to the Rule. The Commission 
    will address these other issues in other notices or forums.
    
    VII. Exemptions
    
        Section 18(g)(2) of the FTC Act, 15 U.S.C. 57a(g)(2), authorizes 
    the Commission to exempt a person or class of persons from all or part 
    of a trade regulation rule if the Commission finds that application of 
    the rule is not necessary to prevent the unfair or deceptive acts or 
    practices to which the rule relates. Since the R-value Rule became 
    effective, the Commission, in response to petitions from industry 
    representatives, has granted exemptions from specific requirements of 
    the Rule to certain classes of sellers. The Commission granted these 
    exemptions after soliciting public comment.
        Although the Commission published the exemptions in the Federal 
    Register, the exemptions are not cited in the text of the Rule in the 
    Code of Federal Regulations. To assist industry members in 
    understanding their responsibilities under the Rule, the Commission has 
    determined to amend the Rule to include a summary of the exemptions as 
    an Appendix to the Rule. These non-substantive amendments do not alter 
    the requirements of the Rule. They merely summarize the previously-
    granted exemptions as an Appendix to the Rule for easier reference. 
    Industry members should review the decisions published in the Federal 
    Register where the Commission granted the exemptions for a more 
    complete description of the scope of the exemptions. The summaries in 
    the Appendix include the citations to those decisions.
    
    A. Manufacturers of Perlite Insulation
    
        The Commission granted the first exemption in response to a 
    petition from a trade association representing manufacturers of perlite 
    insulation products, 46 FR 22179 (1981). The petitioner requested that 
    the Commission exempt manufacturers of perlite insulation from sections 
    460.12(b)(2) and 460.13(c)(1) of the Rule, 16 CFR 460.12(b)(2), 
    460.13(c)(1), which require that they disclose on labels and fact 
    sheets the minimum weight per square foot of perlite insulation 
    products that is necessary to achieve a specific R-value.
        The Rule's label and fact sheet disclosure requirements were based 
    on the fact that, for most insulation products, as the density 
    increases, the R-value per unit of thickness increases. The Rule, 
    therefore, requires that sellers of loose-fill insulations, including 
    perlite, disclose the minimum weight per square foot that is required 
    to achieve the density and thickness necessary for the claimed total R-
    value. Unlike other insulation products, however, as the density of 
    most perlite insulation increases, the R-value per unit of thickness 
    decreases. Thus, if these perlite insulations are installed at 
    densities greater than the thicknesses and weights per square foot 
    listed on their labels and fact sheets, the consumer may not receive 
    the claimed R-values. The petitioner requested that the label and fact 
    sheet disclosure requirements be changed to require disclosure of 
    maximum weight per square foot.
        The Commission exempted manufacturers of perlite insulation 
    products that have an inverse relationship between R-value and density 
    or weight per square foot from the requirements in sections 
    460.12(b)(2) and 460.13(c)(1) of the Rule that they disclose minimum 
    weight per square foot for R-values listed on labels and fact sheets. 
    The exemption is conditioned upon the alternative disclosure in labels 
    and fact sheets of the maximum weight per square foot for each R-value 
    listed. All other requirements of the Rule apply to sellers of these 
    perlite home insulation products.
    
    B. Manufacturers of Rigid, Flat-Roof Insulation
    
        The Commission granted the second exemption in response to 
    petitions filed by four manufacturers of rigid, flat-roof insulation 
    products and two trade associations representing such manufacturers, 46 
    FR 22180 (1981). One of the trade associations and all four 
    manufacturers requested an exemption from all requirements of the Rule 
    for rigid, flat-roof insulation products that are used in flat, built-
    up roofs. The other trade association limited its request to an 
    exemption from the labeling requirements of section 460.12 of the Rule, 
    16 CFR 460.12.
        The petitioners stated that more than 95 percent of the rigid, 
    flat-roof insulation boards sold were used in commercial or industrial 
    buildings and, therefore, were not covered by the Rule. They 
    acknowledged, however, that some of the products were used in multi-
    family residential buildings, such as flat-roof apartments or 
    condominium buildings. The petitioners stated that manufacturers have 
    no way of knowing which products would be used in residential 
    applications. If manufacturers were required to label all products for 
    residential use according to the Rule, they would be required to assume 
    the unnecessary expense of labeling every package of insulation even 
    though only a small percentage would be used in residential 
    applications. Furthermore, since these products were used primarily in 
    large, multi-family, flat-roof buildings, petitioners asserted that the 
    labeling information was unnecessary because the product generally 
    would be selected by an architect or another professional, not the 
    ultimate consumer.
        The Commission exempted manufacturers of rigid, flat-roof 
    insulation products that are used in flat, built-up roofs from the 
    requirement in
    
    [[Page 13665]]
    section 460.12 that all insulation products that might be used in 
    residential buildings be labeled with required R-value information. All 
    other requirements of the Rule apply to sellers of these products.
    
    C. New Home Sellers
    
        The Commission granted the third exemption in response to a 
    petition filed by a trade association representing new home sellers, 48 
    FR 31192 (1983). The petitioner requested that new home sellers be 
    exempted from certain requirements of sections 460.18 and 460.19 of the 
    Rule, 16 CFR 460.18, 460.19. Section 460.18 requires that 
    advertisements and other promotional materials that make certain claims 
    about a home insulation product include specific disclosures. Section 
    460.19 requires that ads and other promotional materials that claim 
    home insulation can cut fuel bills or fuel use (``energy savings 
    claims'') include specific disclosures, and that advertisers have a 
    reasonable basis for the claims and maintain records substantiating the 
    claims.
        The Commission determined that certain disclosures in new home 
    advertisements and other promotional materials, which would have been 
    required by the Rule, were not necessary to prevent the unfair or 
    deceptive acts or practices to which the Rule relates. The Commission, 
    therefore, exempted new home sellers from:
    
        (1) The requirement, under section 460.18(a), that they disclose 
    the type and thickness of the insulation when they make a 
    representation about the R-value of the insulation in a new home;
        (2) the requirement that they disclose the R-value explanatory 
    statement under section 460.18(a) or the savings explanatory 
    statement under section 460.19(b), conditioned upon the new home 
    seller alternatively disclosing the appropriate explanatory 
    statement in the sales contract along with the disclosures required 
    by section 460.16, 16 CFR 460.16; 65
    
        \65\ Under section 460.19(d), ads or other promotional materials 
    that otherwise would require both the R-value explanatory statement 
    under section 460.18(a) and the savings claim explanatory statement 
    under section 460.19(b) need only contain the savings claim 
    explanatory statement. This option applies under the exemption to 
    new home sellers who choose to make the explanatory statement in the 
    sales contract instead of in the ad or other promotional material.
    ---------------------------------------------------------------------------
    
        (3) the requirement that they make the disclosures specified in 
    section 460.19(c) if they claim that insulation, along with other 
    products in a new home, will cut fuel bills or fuel use; and
        (4) the requirement that they include the reference to fact 
    sheets when they must disclose the R-value explanatory statement or 
    the savings claim explanatory statement under sections 460.18(a) or 
    460.19(b), respectively.
    
        These exemptions also apply to home insulation sellers other than 
    new home sellers (such as home insulation manufacturers) when they 
    participate with a new home seller to advertise and promote the sale of 
    new homes, provided that the primary thrust of the advertisement or 
    other promotional material is the promotion of new homes, and not the 
    promotion of the insulation product. All other requirements of the 
    Rule, including the section 460.19 substantiation and recordkeeping 
    requirements for energy savings claims made in ads and other 
    promotional materials, apply to new home sellers and those who 
    participate with a new home seller to advertise and promote the sale of 
    new homes or home insulation products.
    
    VIII. Summary of Commission's Determinations
    
        For the reasons set forth in this notice, the Commission: 66 
    (1) retains the R-value Rule; (2) adopts a non-substantive amendment to 
    section 460.5(a) of the Rule to allow the use of ASTM C 1114-95 as an 
    optional, but not required, test procedure to determine the R-value of 
    home insulation; (3) adopts non-substantive amendments to sections 
    460.5(a), 460.5(a)(2), 460.5(b), and 460.5(d)(1) of the Rule to require 
    the use of ASTM C 177-85 (1993), ASTM C 236-89 (1993), ASTM C 518-91, 
    ASTM C 976-90, ASTM C 1045-90, and ASTM C 739-91 to determine the R-
    value of home insulation; (4) adopts a non-substantive amendment to add 
    an Appendix to the Rule, summarizing the exemptions from specific 
    requirements of the Rule that the Commission previously granted for 
    certain classes of persons covered by the Rule; and (5) adopts a non-
    substantive amendment to revise section 460.10 to cross-reference the 
    Commission's enforcement policy statement for foreign language 
    advertising in 16 CFR 14.9 and to delete the current Appendix to the 
    Rule, which merely repeats the text of 16 CFR 14.9.
    
        \66\ In addition to the amendments described in the text of this 
    notice, the Commission also adopts a non-substantive amendment to 
    section 460.10 and removes the current Appendix (``Enforcement 
    Policy Statement for Foreign Language Advertising''). Section 460.10 
    previously required compliance with the disclosure requirements 
    described in the Appendix. The Appendix simply reprinted 16 CFR 
    14.9. Amended section 460.10 refers directly to 16 CFR 14.9, 
    eliminating unnecessary duplication.
    ---------------------------------------------------------------------------
    
    List of Subjects in 16 CFR Part 460
    
        Advertising, Incorporation by reference, Insulation, Labeling, 
    Trade practices.
    
    Text of Amendments
    
        Accordingly, the Commission amends 16 CFR Part 460 to read as 
    follows:
    
    PART 460--[AMENDED]
    
        1. The authority citation for Part 460 is amended to read as 
    follows:
    
        Authority: 15 U.S.C. 41 et seq.
    
        2. In section 460.5, the introductory text, paragraph (a) 
    introductory text, paragraphs (a)(2) and (b), paragraph (d) 
    introductory text and paragraph (d)(1) are revised to read as follows:
    
    
    Sec. 460.5  R-value tests.
    
        R-value measures resistance to heat flow. R-values given in labels, 
    fact sheets, ads, or other promotional materials must be based on tests 
    done under the methods listed below. They were designed by the American 
    Society of Testing and Materials (ASTM). The test methods are:
        (a) All types of insulation except aluminum foil must be tested 
    with ASTM C 177-85 (Reapproved 1993), ``Standard Test Method for 
    Steady-State Heat Flux Measurements and Thermal Transmission Properties 
    by Means of the Guarded-Hot-Plate Apparatus;'' ASTM C 236-89 
    (Reapproved 1993), ``Standard Test Method for Steady-State Thermal 
    Performance of Building Assemblies by Means of a Guarded Hot Box;'' 
    ASTM C 518-91, ``Standard Test Method for Steady-State Heat Flux 
    Measurements and Thermal Transmission Properties by Means of the Heat 
    Flow Meter Apparatus;'' ASTM C 976-90, ``Standard Test Method for 
    Thermal Performance of Building Assemblies by Means of a Calibrated Hot 
    Box;'' or ASTM C 1114-95, ``Standard Test Method for Steady-State 
    Thermal Transmission Properties by Means of the Thin-Heater 
    Apparatus.'' The tests must be done at a mean temperature of 75 deg. 
    Fahrenheit. The tests must be done on the insulation material alone 
    (excluding any airspace). R-values (``thermal resistance'') based upon 
    heat flux measurements according to ASTM C 177-85 (Reapproved 1993) or 
    ASTM C 518-91 must be reported only in accordance with the requirements 
    and restrictions of ASTM C 1045-90, ``Standard Practice for Calculating 
    Thermal Transmission Properties from Steady-State Heat Flux 
    Measurements.'' These incorporations by reference were approved by the 
    Director of the Federal Register in accordance with 5 U.S.C. 552(a) and 
    1 CFR Part 51. Copies of the test procedures and standard practice may 
    be obtained from the American Society of Testing and Materials, 1916 
    Race Street, Philadelphia, PA 19103.
    
    [[Page 13666]]
    Copies may be inspected at the Federal Trade Commission, Public 
    Reference Room, Room 130, Sixth Street and Pennsylvania Ave., NW, 
    Washington, DC, or at the Office of the Federal Register, 800 North 
    Capital St., NW, suite 700, Washington, DC.
        (1) * * *
        (2) For loose-fill cellulose, the tests must be done at the settled 
    density determined under paragraph 8 of ASTM C 739-91, ``Standard 
    Specification for Cellulosic Fiber (Wood-Base) Loose-Fill Thermal 
    Insulation.'' This incorporation by reference was approved by the 
    Director of the Federal Register in accordance with 5 U.S.C. 552(a) and 
    1 CFR Part 51. Copies of the test procedure may be obtained from the 
    American Society of Testing and Materials, 1916 Race Street, 
    Philadelphia, PA 19103. Copies may be inspected at the Federal Trade 
    Commission, Public Reference Room, Room 130, Sixth Street and 
    Pennsylvania Ave., NW, Washington, DC, or at the Office of the Federal 
    Register, 800 North Capital St., NW, suite 700, Washington, DC.
    * * * * *
        (b) Aluminum foil systems with more than one sheet must be tested 
    with ASTM C 236-89 (Reapproved 1993) or ASTM C 976-90, which are 
    incorporated by reference in paragraph (a) of this section. The tests 
    must be done at a mean temperature of 75 deg. Fahrenheit, with a 
    temperature differential of 30 deg. Fahrenheit.
    * * * * *
        (d) For insulation materials with foil facings, you must test the 
    R-value of the material alone (excluding any air spaces) under the 
    methods listed in paragraph (a) of this section. You can also determine 
    the R-value of the material in conjunction with an air space. You can 
    use one of two methods to do this:
        (1) You can test the system, with its air space, under ASTM C 236-
    89 (Reapproved 1993) or ASTM C 976-90, which are incorporated by 
    reference in paragraph (a) of this section. If you do this, you must 
    follow the rules in paragraph (a) of this section on temperature, aging 
    and settled density.
    * * * * *
        3. Section 460.10 is revised to read as follows:
    
    
    Sec. 460.10  How statements must be made.
    
        All statements called for by this regulation must be made clearly 
    and conspicuously. Among other things, you must follow the Commission's 
    enforcement policy statement for clear and conspicuous disclosures in 
    foreign language advertising and sales materials, 16 CFR 14.9.
        4. The ``Appendix to Part 460--Enforcement Policy Statement for 
    Foreign Language Advertising'' is removed.
        5. A new Appendix is added, to read as follows:
    
    Appendix to Part 460--Exemptions
    
        Section 18(g)(2) of the Federal Trade Commission Act, 15 U.S.C. 
    57a(g)(2), authorizes the Commission to exempt a person or class of 
    persons from all or part of a trade regulation rule if the 
    Commission finds that application of the rule is not necessary to 
    prevent the unfair or deceptive acts or practices to which the rule 
    relates. In response to petitions from industry representatives, the 
    Commission has granted exemptions from specific requirements of 16 
    CFR Part 460 to certain classes of sellers. Some of these exemptions 
    are conditioned upon the performance of alternative actions. The 
    exemptions are limited to specific sections of Part 460. All other 
    requirements of Part 460 apply to these sellers. The exemptions are 
    summarized below. For an explanation of the scope and application of 
    the exemptions, see the formal Commission decisions in the Federal 
    Register cited at the end of each exemption.
        (a) Manufacturers of perlite insulation products that have an 
    inverse relationship between R-value and density or weight per 
    square foot are exempted from the requirements in sections 
    460.12(b)(2) and 460.13(c)(1) that they disclose minimum weight per 
    square foot for R-values listed on labels and fact sheets. This 
    exemption is conditioned upon the alternative disclosure in labels 
    and fact sheets of the maximum weight per square foot for each R-
    value required to be listed. 46 FR 22179 (1981).
        (b) Manufacturers of rigid, flat-roof insulation products used 
    in flat, built-up roofs are exempted from the requirements in 
    section 460.12 that they label these home insulation products. 46 FR 
    22180 (1981).
        (c) New home sellers are exempted from:
        (1) the requirement in section 460.18(a) that they disclose the 
    type and thickness of the insulation when they make a representation 
    in an advertisement or other promotional material about the R-value 
    of the insulation in a new home;
        (2) the requirement that they disclose in an advertisement or 
    other promotional material the R-value explanatory statement 
    specified in section 460.18(a) or the savings explanatory statement 
    specified in section 460.19(b), conditioned upon the new home 
    sellers alternatively disclosing the appropriate explanatory 
    statement in the sales contract along with the disclosures required 
    by section 460.16;
        (3) the requirement that they make the disclosures specified in 
    section 460.19(c) if they claim that insulation, along with other 
    products in a new home, will cut fuel bills or fuel use; and
        (4) the requirement that they include the reference to fact 
    sheets when they must disclose the R-value explanatory statement or 
    the savings claim explanatory statement under sections 460.18(a) or 
    460.19(b), respectively.
        The exemptions for new home sellers also apply to home 
    insulation sellers other than new home sellers when they participate 
    with a new home seller to advertise and promote the sale of new 
    homes, provided that the primary thrust of the advertisement or 
    other promotional material is the promotion of new homes, and not 
    the promotion of the insulation product. 48 FR 31192 (1983).
    
        By direction of the Commission.
    Donald S. Clark,
    Secretary.
    [FR Doc. 96-7528 Filed 3-27-96; 8:45 am]
    BILLING CODE 6750-01-P
    
    

Document Information

Effective Date:
4/29/1996
Published:
03/28/1996
Department:
Federal Trade Commission
Entry Type:
Rule
Action:
Final rule.
Document Number:
96-7528
Dates:
The amendments are effective on April 29, 1996. The incorporation by reference of certain publications listed in the regulations is approved by the Director of the Federal Register as of April 29, 1996.
Pages:
13659-13666 (8 pages)
PDF File:
96-7528.pdf
CFR: (2)
1 CFR 460.10
16 CFR 460.5