1. Should OSHA adopt MADs that are
different from those proposed for
voltages of 72.6 kV and higher (YES) and, if so,
should it adopt the distances in Draft #9
or #10 of IEEE Standard 516?(NO)
2. Are there methods other than those
in Drafts #9 and #10 of IEEE Standard
516 that would be more appropriate in
the calculation of MAD for maximum
transient overvoltages beyond existing
data for rod-to-rod gaps? (YES, NESC 2007)
3. Should MAD for voltages of 72.6 kV
and higher be based on the minimum
tool insulation distance as is the case in
the 2007 NESC? (YES)
4. Should the final rule include
separate minimum approach distance
tables for air gaps and for tools as is
done in Drafts #9 and #10 of IEEE
Standard 516? (NO, The added complexity is not needed. In addition, tools of
some kind are needed for live line work. The 516 tables are not clear if any tool is
considered, or insulated tools only.)
Oregon adopts both OSHA and NESC. The existance of two rules will cause
confusion and violation. Please keep OSHA consistent with NESC, which apears
to be more conservative overall.
Comment from Alexanderson, Steve, Central Lincoln
This is comment on Notice
Electric Power Generation, Transmission, and Distribution; Electrical Protective Equipment; Limited Reopening of Record
View Comment
Related Comments
View AllPublic Submission Posted: 10/29/2008 ID: OSHA-S215-2006-0063-0519
Nov 21,2008 11:59 PM ET
Public Submission Posted: 10/31/2008 ID: OSHA-S215-2006-0063-0520
Nov 21,2008 11:59 PM ET
Public Submission Posted: 11/05/2008 ID: OSHA-S215-2006-0063-0521
Nov 21,2008 11:59 PM ET
Public Submission Posted: 11/21/2008 ID: OSHA-S215-2006-0063-0526
Nov 21,2008 11:59 PM ET
Public Submission Posted: 11/21/2008 ID: OSHA-S215-2006-0063-0527
Nov 21,2008 11:59 PM ET