Code of Federal Regulations (Last Updated: November 8, 2024) |
Title 40 - Protection of Environment |
Chapter I - Environmental Protection Agency |
SubChapter C - Air Programs |
Part 53 - Ambient Air Monitoring Reference and Equivalent Methods |
Subpart C - Procedures for Determining Comparability Between Candidate Methods and Reference Methods |
Table C-3 to Subpart C of Part 53 - Test Specifications for Pb in TSP and Pb in PM 10 Methods
Latest version.
-
Table C-3 to Subpart C of Part 53 - Test Specifications for Pb in TSP and Pb in PM10 Methods
Concentration range equivalent to percentage of NAAQS in µg/m3 30% to 250% Minimum number of 24-hr measurements 5 Maximum reference method analytical bias, Dq ±5% Maximum precision, PR or PC ≤15% Maximum difference (D) ±20% Estimated Method Detection Limit (MDL), µg/m3 5% of NAAQS level. [73 FR 67059, Nov. 12, 2008]