Table 3 to Subpart Ec of Part 60 - Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies  


Latest version.
  • Table 3 to Subpart Ec of Part 60 - Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies

    Operating parameters to be monitored Minimum frequency Control system
    Data measurement Data recording Dry scrubber followed by fabric filter Wet scrubber Dry scrubber followed by fabric filter and wet scrubber
    Maximum operating parameters:
    Maximum charge rate Continuous 1 × hour
    Maximum fabric filter inlet temperature Continuous 1 × minute
    Maximum flue gas temperature Continuous 1 × minute
    Minimum operating parameters:
    Minimum secondary chamber temperature Continuous 1 × minute
    Minimum dioxin/furan sorbent flow rate Hourly 1 × hour
    Minimum HCI sorbent flow rate Hourly 1 × hour
    Minimum mercury (Hg) sorbent flow rate Hourly 1 × hour
    Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubber Continuous 1 × minute
    Minimum scrubber liquor flow rate Continuous 1 × minute
    Minimum scrubber liquor pH Continuous 1 × minute