Code of Federal Regulations (Last Updated: November 8, 2024) |
Title 40 - Protection of Environment |
Chapter I - Environmental Protection Agency |
SubChapter C - Air Programs |
Part 60 - Standards of Performance for New Stationary Sources |
Table 3 to Subpart EEEE of Part 60 - Requirements for Continuous Emission Monitoring Systems (CEMS)
Latest version.
-
Table 3 to Subpart EEEE of Part 60 - Requirements for Continuous Emission Monitoring Systems (CEMS)
As stated in § 60.2940, you must comply with the following:
For the following
pollutantsUse the following span values for your CEMS Use the following performance specifications (P.S.) in appendix B of this part for your CEMS If needed to meet minimum data requirements, use the following alternate methods in appendix A of this part to collect data 1. Carbon Monoxide 125 percent of the maximum hourly potential carbon monoxide emissions of the waste combustion unit P.S.4A Method 10. 2. Oxygen 25 percent oxygen P.S.3 Method 3A or 3B, or ANSI/ASME PTC 19.10-1981 (IBR, see § 60.17(h)) in lieu of Method 3B only.