Table 1 to Subpart BBBBBB of Part 63 - —Applicability Criteria, Emission Limits, and Management Practices for Storage Tanks
Latest version.
-
Table 1 to Subpart BBBBBB of Part 63—Applicability Criteria, Emission Limits, and Management Practices for Storage Tanks
Table 1 to Subpart BBBBBB of Part 63—Applicability Criteria, Emission Limits, and Management Practices for Storage Tanks
If you own or operate . . . Then you must . . . 1. A gasoline storage tank meeting either of the following conditions:
(i) a capacity of less than 75 cubic meters (m3); or
(ii) a capacity of less than 151 m3 and a gasoline throughput of 480 gallons per day or less. Gallons per day is calculated by summing the current day's throughput, plus the throughput for the previous 364 days, and then dividing that sum by 365(a) Equip each gasoline storage tank with a fixed roof that is mounted to the storage tank in a stationary manner, and maintain all openings in a closed position at all times when not in use; and
(b) No later than the dates specified in § 63.11083, all pressure relief devices on each gasoline storage tank must be set to no less than 18 inches of water at all times to minimize breathing losses.2. A gasoline storage tank with a capacity of greater than or equal to 75 m3 and not meeting any of the criteria specified in item 1 of this Tabletable Do the following: or(d
(a) Reduce emissions of total organic HAP or TOC by 95 weight-percent with a closed vent system and control device, as specified in § 60.112b(a)(3) of this chapter; or
(b) Equip each internal floating roof gasoline storage tank according to the requirements in § 60.112b(a)(1) of this chapter, except for the secondary seal requirements under § 60.112b(a)(1)(ii)(B) and the requirements in § 60.112b(a)(1)(iv) through (ix) of this chapter; and
(c) No later than the dates specified in § 63.11083, equip, maintain, and operate each internal floating roof control system to maintain the vapor concentration within the storage tank above the floating roof at or below 25 percent of the LEL on a 5-minute rolling average basis without the use of purge gas, which may require additional controls beyond those specified in item 2(b) of this table; and
(d) Equip each external floating roof gasoline storage tank according to the requirements in § 60.112b(a)(2) of this chapter, except that the requirements of § 60.112b(a)(2)(ii) of this chapter shall only be required if such storage tank does not currently meet the requirements of § 60.112b(a)(2)(i) of this chapter;by the dates specified in § 63.11083, all external floating roofs must meet the requirements of § 60.112b(a)(2)(ii) of this chapter; or
(e) Equip and operate each internal and external floating roof gasoline storage tank according to the applicable requirements in § 63.1063(a)(1) and (b), except for the secondary seal requirements under § 63.1063(a)(1)(i)(C) and (D), and equip each external floating roof gasoline storage tank according to the requirements of § 63.1063(a)(2) by the dates specified in § 63.11087(b) if such storage tank does not currently meet the requirements of § 63.1063(a)(1); by the dates specified in § 63.11083, all external floating roofs must meet the requirements of § 63.1063(a)(2); and
(f) No later than the dates specified in § 63.11083, equip, maintain, and operate each internal floating roof control system to maintain the vapor concentration within the storage tank above the floating roof at or below 25 percent of the LEL on a 5-minute rolling average basis without the use of purge gas, which may require additional controls beyond those specified in item 2(e) of this table.3. A surge control tank Equip each tank with a fixed roof that is mounted to the tank in a stationary manner and with a pressure/vacuum vent with a positive cracking pressure of no less than 0.50 inches of water. Maintain all openings in a closed position at all times when not in use. [76 FR 4179, Jan. 24, 2011, as amended at 89 FR 39384, May 8, 2024]