Code of Federal Regulations (Last Updated: November 8, 2024) |
Title 40 - Protection of Environment |
Chapter I - Environmental Protection Agency |
SubChapter C - Air Programs |
Part 63 - National Emission Standards for Hazardous Air Pollutants for Source Categories |
Subpart JJJJJJ - National Emission Standards for Hazardous Air Pollutants for Industrial, Commercial, and Institutional Boilers Area Sources |
Table 4 to Subpart JJJJJJ of Part 63 - Performance (Stack) Testing Requirements
Latest version.
-
Table 4 to Subpart JJJJJJ of Part 63 - Performance (Stack) Testing Requirements
As stated in § 63.11212, you must comply with the following requirements for performance (stack) test for affected sources:
To conduct a performance test for the following pollutant. . . You must. . . Using. . . 1. Particulate Matter a. Select sampling ports location and the number of traverse points Method 1 in appendix A-1 to part 60 of this chapter. b. Determine velocity and volumetric flow-rate of the stack gas Method 2, 2F, or 2G in appendix A-2 to part 60 of this chapter. c. Determine oxygen and carbon dioxide concentrations of the stack gas Method 3A or 3B in appendix A-2 to part 60 of this chapter, or ASTM D6522-00 (Reapproved 2005),a or ANSI/ASME PTC 19.10-1981.a d. Measure the moisture content of the stack gas Method 4 in appendix A-3 to part 60 of this chapter. e. Measure the particulate matter emission concentration Method 5 or 17 (positive pressure fabric filters must use Method 5D) in appendix A-3 and A-6 to part 60 of this chapter and a minimum 1 dscm of sample volume per run. f. Convert emissions concentration to lb/MMBtu emission rates Method 19 F-factor methodology in appendix A-7 to part 60 of this chapter. 2. Mercury a. Select sampling ports location and the number of traverse points Method 1 in appendix A-1 to part 60 of this chapter. b. Determine velocity and volumetric flow-rate of the stack gas Method 2, 2F, or 2G in appendix A-2 to part 60 of this chapter. c. Determine oxygen and carbon dioxide concentrations of the stack gas Method 3A or 3B in appendix A-2 to part 60 of this chapter, or ASTM D6522-00 (Reapproved 2005),a or ANSI/ASME PTC 19.10-1981.a d. Measure the moisture content of the stack gas Method 4 in appendix A-3 to part 60 of this chapter. e. Measure the mercury emission concentration Method 29, 30A, or 30B in appendix A-8 to part 60 of this chapter or Method 101A in appendix B to part 61 of this chapter or ASTM Method D6784-02.a Collect a minimum 2 dscm of sample volume with Method 29 of 101A per run. Use a minimum run time of 2 hours with Method 30A. f. Convert emissions concentration to lb/MMBtu emission rates Method 19 F-factor methodology in appendix A-7 to part 60 of this chapter. 3. Carbon Monoxide a. Select the sampling ports location and the number of traverse points Method 1 in appendix A-1 to part 60 of this chapter. b. Determine oxygen and carbon dioxide concentrations of the stack gas Method 3A or 3B in appendix A-2 to part 60 of this chapter, or ASTM D6522-00 (Reapproved 2005),a or ANSI/ASME PTC 19.10-1981.a c. Measure the moisture content of the stack gas Method 4 in appendix A-3 to part 60 of this chapter. d. Measure the carbon monoxide emission concentration Method 10, 10A, or 10B in appendix A-4 to part 60 of this chapter or ASTM D6522-00 (Reapproved 2005)a and a minimum 1 hour sampling time per run.