Table 1 to Subpart UUUUU of Part 63 - —Emission Limits for New or Reconstructed EGUs
Latest version.
-
Table 1 to Subpart UUUUU of Part 63—Emission Limits for New or Reconstructed EGUs
As stated in § 63.9991, you must comply with the following applicable emission limits:
If your EGU is in this subcategory . . . For the following
pollutants . . .You must meet the following emission limits and work practice standards . . . Using these requirements, as appropriate (e.g., specified sampling volume or test run duration) and limitations with the test methods in Table 5 to this Subpart . . . 1. Coal-fired unit not low rank virgin coal a. Filterable particulate matter (PM) 9.0E-2 lb/MWh1 Collect a minimum catch of 6.0 milligrams or a minimum sample volume of 4 dscm per run. OR OR Total non-Hg HAP metals 6.0E-2 lb/GWh Collect a minimum of 4 dscm per run. OR OR Individual HAP metals: Collect a minimum of 3 dscm per run. Antimony (Sb) 8.0E-3 lb/GWh Arsenic (As) 3.0E-3 lb/GWh Beryllium (Be) 6.0E-4 lb/GWh Cadmium (Cd) 4.0E-4 lb/GWh Chromium (Cr) 7.0E-3 lb/GWh Cobalt (Co) 2.0E-3 lb/GWh Lead (Pb) 2.0E-2 lb/GWh Manganese (Mn) 4.0E-3 lb/GWh Nickel (Ni) 4.0E-2 lb/GWh Selenium (Se) 5.0E-2 lb/GWh b. Hydrogen chloride (HCl) 1.0E-2 lb/MWh For Method 26A at appendix A-8 to part 60 of this chapter, collect a minimum of 3 dscm per run. For ASTM D6348-03(Reapproved 2010)2 or Method 320 at appendix A to part 63 of this chapter, sample for a minimum of 1 hour. OR Sulfur dioxide (SO2)3 1.0 lb/MWh SO2 CEMS. c. Mercury (Hg) 3.0E-3 lb/GWh Hg CEMS or sorbent trap monitoring system only. 2. Coal-fired units low rank virgin coal a. Filterable particulate matter (PM) 9.0E-2 lb/MWh1 Collect a minimum catch of 6.0 milligrams or a minimum sample volume of 4 dscm per run. OR OR Total non-Hg HAP metals 6.0E-2 lb/GWh Collect a minimum of 4 dscm per run. OR OR Individual HAP metals: Collect a minimum of 3 dscm per run. Antimony (Sb) 8.0E-3 lb/GWh Arsenic (As) 3.0E-3 lb/GWh Beryllium (Be) 6.0E-4 lb/GWh Cadmium (Cd) 4.0E-4 lb/GWh Chromium (Cr) 7.0E-3 lb/GWh Cobalt (Co) 2.0E-3 lb/GWh Lead (Pb) 2.0E-2 lb/GWh Manganese (Mn) 4.0E-3 lb/GWh Nickel (Ni) 4.0E-2 lb/GWh Selenium (Se) 5.0E-2 lb/GWh b. Hydrogen chloride (HCl) 1.0E-2 lb/MWh For Method 26A, collect a minimum of 3 dscm per run For ASTM D6348-03(Reapproved 2010)2 or Method 320, sample for a minimum of 1 hour. OR Sulfur dioxide (SO2)3 1.0 lb/MWh SO2 CEMS. c. Mercury (Hg) Before July 8, 2024: 4.0E-2 lb/GWh; On or after July 8, 2024: 1.3E-2 lb/GWh Hg CEMS or sorbent trap monitoring system only. 3. IGCC unit a. Filterable particulate matter (PM) 7.0E-2 lb/MWh4 9.0E-2 lb/MWh5 Collect a minimum of 1 catch of 3.0 milligrams or a minimum sample volume of 2 dscm per run. OR OR Total non-Hg HAP metals 4.0E-1 lb/GWh Collect a minimum of 1 dscm per run. OR OR Individual HAP metals: Collect a minimum of 2 dscm per run. Antimony (Sb) 2.0E-2 lb/GWh Arsenic (As) 2.0E-2 lb/GWh Beryllium (Be) 1.0E-3 lb/GWh Cadmium (Cd) 2.0E-3 lb/GWh Chromium (Cr) 4.0E-2 lb/GWh Cobalt (Co) 4.0E-3 lb/GWh Lead (Pb) 9.0E-3 lb/GWh Manganese (Mn) 2.0E-2 lb/GWh Nickel (Ni) 7.0E-2 lb/GWh Selenium (Se) 3.0E-1 lb/GWh b. Hydrogen chloride (HCl) 2.0E-3 lb/MWh For Method 26A, collect a minimum of 1 dscm per run; for Method 26 at appendix A-8 to part 60 of this chapter, collect a minimum of 120 liters per run.
For ASTM D6348-03(Reapproved 2010)2 or Method 320, sample for a minimum of 1 hour.OR Sulfur dioxide (SO2)3 4.0E-1 lb/MWh SO2 CEMS. c. Mercury (Hg) 3.0E-3 lb/GWh Hg CEMS or sorbent trap monitoring system only. 4. Liquid oil-fired unit—continental (excluding limited-use liquid oil-fired subcategory units) a. Filterable particulate matter (PM) 3.0E-1 lb/MWh1 Collect a minimum of 1 dscm per run. OR OR Total HAP metals 2.0E-4 lb/MWh Collect a minimum of 2 dscm per run. OR OR Individual HAP metals: Collect a minimum of 2 dscm per run. Antimony (Sb) 1.0E-2 lb/GWh Arsenic (As) 3.0E-3 lb/GWh Beryllium (Be) 5.0E-4 lb/GWh Cadmium (Cd) 2.0E-4 lb/GWh Chromium (Cr) 2.0E-2 lb/GWh Cobalt (Co) 3.0E-2 lb/GWh Lead (Pb) 8.0E-3 lb/GWh Manganese (Mn) 2.0E-2 lb/GWh Nickel (Ni) 9.0E-2 lb/GWh Selenium (Se) 2.0E-2 lb/GWh Mercury (Hg) 1.0E-4 lb/GWh For Method 30B at appendix A-8 to part 60 of this chapter sample volume determination (Section 8.2.4), the estimated Hg concentration should nominally be < 1⁄2 the standard. b. Hydrogen chloride (HCl) 4.0E-4 lb/MWh For Method 26A, collect a minimum of 3 dscm per run. For ASTM D6348-03(Reapproved 2010)2 or Method 320, sample for a minimum of 1 hour. c. Hydrogen fluoride (HF) 4.0E-4 lb/MWh For Method 26A, collect a minimum of 3 dscm per run. For ASTM D6348-03 (Reapproved 2010)2 or Method 320, sample for a minimum of 1 hour. 5. Liquid oil-fired unit—non-continental (excluding limited-use liquid oil-fired subcategory units) a. Filterable particulate matter (PM) 2.0E-1 lb/MWh1 Collect a minimum of 1 dscm per run. OR OR Total HAP metals 7.0E-3 lb/MWh Collect a minimum of 1 dscm per run. OR OR Individual HAP metals: Collect a minimum of 3 dscm per run. Antimony (Sb) 8.0E-3 lb/GWh Arsenic (As) 6.0E-2 lb/GWh Beryllium (Be) 2.0E-3 lb/GWh Cadmium (Cd) 2.0E-3 lb/GWh Chromium (Cr) 2.0E-2 lb/GWh Cobalt (Co) 3.0E-1 lb/GWh Lead (Pb) 3.0E-2 lb/GWh Manganese (Mn) 1.0E-1 lb/GWh Nickel (Ni) 4.1E0 lb/GWh Selenium (Se) 2.0E-2 lb/GWh Mercury (Hg) 4.0E-4 lb/GWh For Method 30B sample volume determination (Section 8.2.4), the estimated Hg concentration should nominally be < 1⁄2 the standard. b. Hydrogen chloride (HCl) 2.0E-3 lb/MWh For Method 26A, collect a minimum of 1 dscm per run; for Method 26, collect a minimum of 120 liters per run. For ASTM D6348-03 (Reapproved 2010)2 or Method 320, sample for a minimum of 1 hour. c. Hydrogen fluoride (HF) 5.0E-4 lb/MWh For Method 26A, collect a minimum of 3 dscm per run. For ASTM D6348-03 (Reapproved 2010)2 or Method 320, sample for a minimum of 1 hour. 6. Solid oil-derived fuel-fired unit a. Filterable particulate matter (PM) 3.0E-2 lb/MWh1 Collect a minimum of 1 dscm per run. OR OR Total non-Hg HAP metals 6.0E-1 lb/GWh Collect a minimum of 1 dscm per run. OR OR Individual HAP metals: Collect a minimum of 3 dscm per run. Antimony (Sb) 8.0E-3 lb/GWh Arsenic (As) 3.0E-3 lb/GWh Beryllium (Be) 6.0E-4 lb/GWh Cadmium (Cd) 7.0E-4 lb/GWh Chromium (Cr) 6.0E-3 lb/GWh Cobalt (Co) 2.0E-3 lb/GWh Lead (Pb) 2.0E-2 lb/GWh Manganese (Mn) 7.0E-3 lb/GWh Nickel (Ni) 4.0E-2 lb/GWh Selenium (Se) 6.0E-3 lb/GWh b. Hydrogen chloride (HCl) 4.0E-4 lb/MWh For Method 26A, collect a minimum of 3 dscm per run. For ASTM D6348-03 (Reapproved 2010)2 or Method 320, sample for a minimum of 1 hour. OR Sulfur dioxide (SO2)3 1.0 lb/MWh SO2 CEMS. c. Mercury (Hg) 2.0E-3 lb/GWh Hg CEMS or Sorbent trap monitoring system only. [81 FR 20190, Apr. 6, 2016, as amended at 89 FR 38569, May 7, 2024]