§ 111.53-1 - General.


Latest version.
  • § 111.53-1 General.

    (a) Each fuse must—

    (1) Meet the general provisions of Article 240 of NFPA NEC 2002 70 or IEC 60092–202:2016 (both incorporated by reference; see 46 CFR § 110.10–110–1 of this subchapter) as appropriate.

    (2) Have an interrupting rating sufficient to interrupt the asymmetrical RMS short-circuit current at the point of application; and

    (

    3) Be listed by an independent laboratory.

    (b) Renewable link cartridge-type fuses must not be used.

    (c) Each fuse installation must provide for ready access to test the condition of the fuse.

    [CGD 94–108, 61 FR 28279, June 4, 1996, as amended by61 FR 33045, June 26, 1996; USCG–2003–16630, 73 FR 65197, Oct. 31, 2008; USCG–2013–0671, 78 FR 60153, Sept. 30, 2013; USCG–2020–0075, 88 FR 16363, Mar. 16, 2023]