§ 154.1160 - Monitor coverage of system.  


Latest version.
  • § 154.1160 Monitor coverage of system.

    The coverage of each dry chemical system monitor under § 154.1150 must not exceed:

    (a) 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec);

    (b) 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec);

    (c) 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec);

    (d) An interpolation between 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec) and 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec); or

    (e) An interpolation between 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec) and 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec).