§ 173.314 - Compressed gases in tank cars and multi-unit tank cars.
-
§ 173.314 Compressed gases in tank cars and multi-unit tank cars.
(a) Definitions. For definitions of compressed gases, see § 173.115.
(b) General requirements.
(1) Tank car tanks containing compressed gases must not be shipped unless they were loaded by or with the consent of the owner thereof.
(2) Tank car tanks must not contain gases capable of combining chemically and must not be loaded with any gas which combines chemically with the gas previously loaded therein, until all residue has been removed and interior of tank thoroughly cleaned.
(3) For tanks of the DOT-106A and 110A class, the tanks must be placed in position and attached to car structure by the shipper.
(4) Wherever the word “approved” is used in this part of the regulations, it means approval by the Association of American Railroads Committee on Tank Cars as prescribed in § 179.3 of this subchapter.
(5) Each tank car used for the transportation of anhydrous ammonia or any material that meets the criteria of Division 2.1 or 2.3 must have gaskets for manway cover plates and for mounting of fittings designed (for temperature, application, media, pressure, and size) to create a positive seal so that, under conditions normally incident to transportation, there will not be an identifiable release of the material to the environment. The use of sealants to install gaskets is prohibited.
(c) Authorized gases, filling limits for tank cars. A compressed gas in a tank car or a multi-unit tank car must be offered for transportation in accordance with § 173.31 and this section. The gases listed below must be loaded and offered for transportation in accordance with the following table:
Table 1 to Paragraph (c)
Proper shipping name Outage and filling limits
(see note 1)Authorized tank car class
(see note 11)Authorized tank car specification
(see note 12)Ammonia, anhydrous, or ammonia solutions >50 percent ammonia Notes 2, 10 105, 112, 114, 120 105H500W, 112H500W Note 3 106 Ammonia solutions with >35 percent, but ≤50 percent ammonia by mass Note 3 105, 109, 112, 114, 120 Argon, compressed Note 4 107 Boron trichloride Note 3 105, 106 Carbon dioxide, refrigerated liquid Note 5 105 Chlorine Note 6 105 105H600W 125 106 Chlorine trifluoride Note 3 106, 110 Chlorine pentafluoride Note 3 106, 110 Dimethyl ether Note 3 105, 106, 110, 112, 114, 120 Dimethylamine, anhydrous Note 3 105, 106, 112 Dinitrogen tetroxide, inhibited Note 3 105, 106, 112 105H500W Division 2.1 materials not specifically identified in this table Notes 9, 10 105, 106, 110, 112, 114, 120 Division 2.2 materials not specifically identified in this table Note 3 105, 106, 109, 110, 112, 114, 120 Division 2.3 Zone A materials not specifically identified in this table None See § 173.245. 105H600W Division 2.3 Zone B materials not specifically identified in this table Note 3 105, 106, 110, 112, 114, 120 105H600W Division 2.3 Zone C materials not specifically identified in this table Note 3 105, 106, 110, 112, 114, 120 105H500W Division 2.3 Zone D materials not specifically identified in this table Note 3 105, 106, 109, 110, 112, 114, 120 105H500W, 112H500H Ethylamine Note 3 105, 106, 110, 112, 114, 120 Helium, compressed Note 4 107 Hydrogen Note 4 107 Hydrogen chloride, refrigerated liquid Note 7 105 105H600W, 112H600W Hydrogen sulfide Note 3 105, 106, 110, 112, 114, 120 105H600W Hydrogen sulfide, liquefied 68 106 Methyl bromide Note 3 105, 106 105H500W Methyl chloride Note 3 105, 106, 112 Methyl mercaptan Note 3 105, 106 105H500W Methylamine, anhydrous Note 3 105, 106, 112 Nitrogen, compressed Note 4 107 Nitrosyl chloride 124 105 105H500W 110 106 Nitrous oxide, refrigerated liquid Note 5 105 Oxygen, compressed Note 4 107 Phosgene Note 3 106 Sulfur dioxide, liquefied 125 105, 106, 110 105H500W Sulfuryl fluoride 120 105 Vinyl fluoride, stabilized Note 8 105 (d) Alternative tank car tanks for materials poisonous by inhalation.
(1) As an alternative to the authorized tank car specification noted in the column 4 of the table in paragraph (c) of this section, a car of the same authorized tank car specification but of the next lower test pressure, as prescribed in column 5 of the table at § 179.101-1, may be used provided both of the following conditions are met:
(i) The difference between the alternative and the required minimum plate thicknesses, based on the calculation prescribed in § 179.100-6 of this subchapter, is added to the alternative tank car jacket and head shield. When the jacket and head shield are made from any authorized steel with a minimum tensile strength from 70,000 p.s.i. to 80,000 p.s.i., but the required minimum plate thickness calculation is based on steel with a minimum tensile strength of 81,000 p.s.i., the thickness to be added to the jacket and head shield must be increased by a factor of 1.157. Forming allowances for heads are not required to be considered when calculating thickness differences as prescribed in this paragraph.
(ii) The tank car jacket and head shield must be manufactured from carbon steel plate as prescribed in § 179.100-7(a) of this subchapter.
(e) Verification of content.
(1) The amount of liquefied gas loaded into each tank may be determined either by measurement or calculation of the weight, except that DOT specification tank car tanks authorized for the transportation of anhydrous ammonia and ammonia solution may have the amount of liquefied gas loaded into the tank car measured by a metering device in conformance with paragraph (e)(2) of this section.
(2) Metering device.
(i) Tank cars loaded with anhydrous ammonia or ammonia solution through the use of a metering device in conformance with this section are not required to be weighed, but must have their outage measured with a magnetic gauging device to determine that the tank car is properly loaded in conformance with this paragraph. Written procedures for loading a tank car using a metering device must be developed and made available at each location where such loading takes place. Certification in writing of the inspection and completion of these loading and/or unloading procedures must be maintained for each tank car and maintained in accordance with the recordkeeping requirements in paragraph (e)(2)(iii) of this section, and all necessary records must be completed. At a minimum, these procedures will specify:
(A) The tank car must be offered for transportation in conformance with all applicable government regulations.
(B) Any defects found when the tank car is examined before shipping must be recorded, and the tank must not be loaded until the repairs to eliminate each defect are completed.
(C) The tank car must be allowed to sit undisturbed for at least 10 minutes after loading to allow material within the tank to settle. After this has occurred a final check for leaks must be conducted prior to offering the tank car for transportation.
(ii) One out of every 10 tank cars loaded by the use of the metering device must be gauged utilizing the fixed gauging equipment on the tank car to verify by calculation the amount of anhydrous ammonia or ammonia solution contained in the tank car.
(iii) Recordkeeping. The following information must be maintained and be made available to any representative of the DOT upon request for each tank car loaded with the use of a metering device:
(A) Date loaded,
(B) Date shipped,
(C) Tank car reporting marks,
(D) DOT Specification,
(E) Tank car stenciled shell capacity (gallons/liters),
(F) Tank car stenciled tare weight (pounds/kilograms),
(G) Outage or innage table number,
(H) Water capacity of tank in pounds and/or kilograms,
(I) Maximum permitted filling density (see § 173.314),
(J) Specific gravity of anhydrous ammonia or ammonia solution at the reference temperature,
(K) Tank car outage (inches/meters, gallons/liters),
(L) Gallons/liters of liquid ammonia in tank car,
(M) Quantity of vapor ammonia in tank car (gallons/liters), and
(N) Total calculated ammonia (liquid & vapor) in tank car (pounds/kilograms).
(f) [Reserved]
(g) Special requirements for hydrogen chloride, refrigerated liquid, and vinyl fluoride,stabilized.
(1) The shipper shall notify the Federal Railroad Administration whenever a tank car is not received by the consignee within 20 days from the date of shipment. Notification to the Federal Railroad Administration may be made by e-mail to Hmassist@fra.dot.gov or telephone call to (202) 493-6229.
(2) A tank car containing hydrogen chloride, refrigerated liquid must have the auxiliary valve on the pressure relief device closed during transportation.
(3) See § 179.102-17 of this subchapter for additional requirements.
(4) Tank cars containing hydrogen chloride, refrigerated liquid, must be unloaded to such an extent that any residue remaining in the tank at a reference temperature of 32 °C (90 °F) will not actuate the reclosing pressure relief device.
(h) Special requirements for liquefied petroleum gas -
(1) Odorization. All liquefied petroleum gas must be odorized as required in this paragraph to indicate positively, by a distinctive odor, the presence of gas down to a concentration in air of not over one-fifth the lower limit of combustibility; however, odorization is not required if it is harmful in the use or further processing of the liquefied petroleum gas or if it will serve no useful purpose as a warning agent in such use or further processing.
(i) The lower limits of combustibility of the more commonly used liquefied petroleum gases are: Propane, 2.15 percent; butane, 1.55 percent. These figures represent volumetric percentages of gas-air mixtures in each case.
(ii) The use of 1.0 pound of ethyl mercaptan per 10,000 gallons of liquefied petroleum gas is considered sufficient to meet the requirements of this paragraph. Use of another odorant is not prohibited so long as there is enough to meet the requirements of this paragraph (h).
(2) Odorant fade. In addition to paragraph (h)(1)(i) of this section, the offeror must ensure that enough odorant will remain in the tank car during the course of transportation. The offeror must have procedures in place to:
(i) Ensure quantitative testing methods are used to measure the amount of odorant in the liquefied petroleum gas;
(ii) Ensure that, when the odorization of liquefied petroleum gas is manually injected, the required amount of odorant is added;
(iii) Ensure that, when odorization of liquefied petroleum gas is automatically injected, equipment calibration checks are conducted to ensure the required amount of odorant is consistently added;
(iv) Ensure quality control measures are in place to make sure that persons who receive tank cars that have been subjected to any condition that could lead to corrosion of the tank car or receive new or recently cleaned tank cars are notified of this information and that a person filling these packagings implement quality control measures so that potential odorant fade is addressed;
(v) Inspect a tank car for signs of oxidation or corrosion; and
(vi) Take corrective action needed to ensure enough odorization remains in the tank car during the course of transportation, such as increasing the amount of odorant added to the liquefied petroleum gas.
(i) [Reserved]
(j) Special requirements for materials having a primary or secondary Division 2.1 (flammable gas) hazard. For single unit tank cars, interior pipes of loading and unloading valves, sampling devices, and gauging devices with an opening for the passage of the lading exceeding 1.52 mm (0.060 inch) diameter must be equipped with excess flow valves. For single unit tank cars constructed before January 1, 1972, gauging devices must conform to this paragraph by no later than July 1, 2006. The protective housing cover must be provided with an opening, with a weatherproof cover, above each pressure relief valve that is concentric with the discharge of the pressure relief valve and that has an area at least equal to the valve outlet area. Class DOT 109 tank cars and tank cars manufactured from aluminum or nickel plate are not authorized.
(k) Special requirements for chlorine.
(1) Tank cars built after September 30, 1991, must have an insulation system consisting of 5.08 cm (2 inches) glass fiber placed over 5.08 cm (2 inches) of ceramic fiber. Tank cars must have excess flow valves on the interior pipes of liquid discharge valves. Tank cars constructed to a DOT 105A500W specification may be marked as a DOT 105A300W specification with the size and type of reclosing pressure relief valves required by the marked specification.
(2) DOT105J500W tank cars may be used as authorized packagings, as prescribed in this subchapter for transporting “UN 1017, Chlorine, 2.3 (8), Poison Inhalation Hazard, Zone B, RQ,” if the tank cars meet all DOT specification requirements, and the tank cars are equipped with combination safety relief valves with a start-to-discharge pressure of 360 psi, rather than the 356 psi. The start-to-discharge pressure setting must be marked on the pressure relief device in conformance with applicable provisions of the AAR Specification for Tank Cars (IBR, see § 171.7 of this subchapter).
(l) Special requirements for hydrogen sulphide. Each multi-unit tank car must be equipped with adequate pressure relief devices of the fusible plug type having a yield temperature not over 76.66 °C (170 °F.), and not less than 69.44 °C (157 °F.). Each device must be resistant to extrusion of the fusible alloy and leak tight at 55 °C (130 °F.). A threaded solid plug must seal each valve outlet. In addition, a metal cover must protect all valves.
(m) Special requirements for nitrosyl chloride. Single unit tank cars and their associated service equipment, such as venting, loading and unloading valves, and reclosing pressure relief valves, must be made of metal or clad with a material that is not subject to rapid deterioration by the lading. Multi-unit tank car tanks must be nickel-clad and have reclosing pressure relief devices incorporating a fusible plug having a yield temperature of 79.44 °C (175 °F.). Reclosing pressure relief devices must be vapor tight at 54.44 °C (130 °F.).
(n) Special requirements for hydrogen. Each tank car must be equipped with one or more pressure relief devices. The discharge outlet for each pressure relief device must be connected to a manifold having a non-obstructed discharge area of at least 1.5 times the total discharge area of the pressure relief devices connected to the manifold. All manifolds must be connected to a single common header having a non-obstructed discharge pointing upward and extending above the top of the car. The header and the header outlet must each have a non-obstructed discharge area at least equal to the total discharge area of the manifolds connected to the header. The header outlet must be equipped with an ignition device that will instantly ignite any hydrogen discharged through the pressure relief device.
(o) Special requirements for carbon dioxide, refrigerated liquid and nitrous oxide, refrigerated liquid. Each tank car must have an insulation system so that the thermal conductance is not more than 0.613 kilojoules per hour, per square meter, per degree Celsius (0.03 B.t.u. per square foot per hour, per degree Fahrenheit) temperature differential. Each tank car must be equipped with one reclosing pressure relief valve having a start-to-discharge pressure not to exceed 75 percent of the tank test pressure and one non-reclosing pressure relief valve having a rupture disc design to burst at a pressure less than the tank test pressure. The discharge capacity of each pressure relief device must be sufficient to prevent building up of pressure in the tank in excess of 82.5 percent of the test pressure of the tank. Tanks must be equipped with two regulating valves set to open at a pressure not to exceed 24.1 Bar (350 psi) on DOT 105A500W tanks and at a pressure not to exceed 27.6 Bar (400 psi) on DOT 105A600W tanks. Each regulating valve and pressure relief device must have its final discharge piped to the outside of the protective housing.
[Amdt. 173-224, 55 FR 52665, Dec. 21, 1990]