§ 193.2233 - Shutoff valves.


Latest version.
  • (a) Shutoff valves on transfer systems must be located—

    (1) On each liquid supply line, or common line to multiple supply lines, to a storage tank, or to a cargo transfer system;

    (2) On each vapor or liquid return line from multiple return lines, used in a cargo transfer system;

    (3) At the connection of a transfer system with a pipeline subject to part 192 of this chapter; and

    (4) To provide for proper operation and maintenance of each transfer system.

    (b) Transfer system shutoff valves that are designated for operation in the emergency procedures must be manually operable at the valve and power operable at the valve and at a remote location at least 50 feet (15 meters) from the valve.