94-15752. Consolidated Edison Co. of New York, Inc.; Indian Point Nuclear Generating Unit No. 2 Exemption  

  • [Federal Register Volume 59, Number 124 (Wednesday, June 29, 1994)]
    [Unknown Section]
    [Page 0]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 94-15752]
    
    
    [[Page Unknown]]
    
    [Federal Register: June 29, 1994]
    
    
    -----------------------------------------------------------------------
    
    NUCLEAR REGULATORY COMMISSION
    [Docket No. 50-247]
    
     
    
    Consolidated Edison Co. of New York, Inc.; Indian Point Nuclear 
    Generating Unit No. 2 Exemption
    
    I
    
        The Consolidated Edison Company of New York, Inc. (the licensee) is 
    the holder of Facility Operating License No. DPR-26. which authorizes 
    operation of the Indian Point Nuclear Generating Unit No. 2 (IP2). The 
    license provides, among other things, that the licensee is subject to 
    all rules, regulations, and orders of the U.S. Nuclear Regulatory 
    Commission (the Commission) now or hereafter in effect.
        The facility consists of a pressurized water reactor at the 
    licensee's site located in Westchester County, New York.
    
    II
    
        By letter dated January 28, 1994, the licensee requested an 
    amendment to the Technical Specifications (TSs) that would allow 
    containment isolation valve leak rate tests to be performed at 
    intervals up to 30 months. In addition, the licensee's letter requested 
    an exemption from the requirements of the Code of Federal Regulations 
    (CFR) since 10 CFR Part 50, Appendix J, Paragraph III.D.3, requires 
    that licensees perform Type C tests during each reactor shutdown for 
    refueling but in no case at intervals greater than 2 years. Type C 
    tests are tests that measure containment isolation valve leakage rates.
        The licensee commenced operating on 24-month fuel cycles, instead 
    of the previous 18-month fuel cycles, with fuel cycle 12. Fuel cycle 12 
    started in April 1993. In order to conform with the requirements of 10 
    CFR Part 50, Appendix J, Paragraph III.D.3, the licensee could be 
    required to shutdown IP2 and enter a forced outage prior to the next 
    scheduled refueling outage. The next refueling outage is scheduled to 
    commence in the February 1995 time frame.
    
    III
    
        Pursuant to 10 CFR 50.12, the Commission may, upon application by 
    any interested person or upon its own initiative, grant exemptions from 
    the requirements of 10 CFR Part 50 when (1) the exemptions are 
    authorized by law, will not present an undue risk to public health and 
    safety, and are consistent with the common defense and security and (2) 
    when special circumstances are present. According to 10 CFR 
    50.12(a)(2)(ii), special circumstances are present when, ``Application 
    of the regulation in the particular circumstances would not serve the 
    underlying purpose of the rule or is not necessary to achieve the 
    underlying purpose of the rule.* * *''
        The CFR at 10 CFR Part 50, Appendix J, Paragraph III.D.3, states: 
    ``Type C tests shall be performed during each reactor shutdown for 
    refueling but in no case at intervals greater than 2 years.* * *'' The 
    underlying purpose of the requirement to perform Type B and Type C 
    containment leak rate tests of intervals not to exceed 2 years, is to 
    ensure that any potential leakage pathways through the containment 
    boundary are identified within a time span that prevents significant 
    degradation from continuing or being unknown and long enough to allow 
    the tests to be conducted during scheduled refueling outages. This 
    requirement to perform Type C leak rate tests at intervals no greater 
    than 2 years presumed the 2-year time interval was adequate to 
    accommodate the 12-month fuel cycles which were common when Appendix J 
    to 10 CFR Part 50 was published in 1993. However, IP2, along with other 
    facilities, is utilizing a core design which allows operation on a 24-
    month cycle.
        The NRC staff recognized that the current 2-year intervals for Type 
    C leak rate tests would likely require a facility to shutdown to 
    perform these tests before completion of the facility's 24-month fuel 
    cycle. Consequently, the NRC staff issued Generic Letter (GL) 91-04, 
    ``Changes in Technical Specification Surveillance Intervals to 
    Accommodate a 24-Month Fuel Cycle.'' This GL provides guidance to 
    licensees on how to prepare requests for TS amendments and CFR 
    exemptions which are needed to accommodate a 24-month fuel cycle. 
    Enclosure 3 to GL 91-04 indicated, in part, that two issues should be 
    addressed to justify extending the 2-year Type C test interval: (1) a 
    possible reduction in the combined leakage limit for Types B and C 
    tests and (2) the basis for concluding that the containment leakage 
    rate would be maintained within the acceptable limits with a Type C 
    test interval of up to 30 months. The licensee's letter of January 28, 
    1994, addressed both of these issues.
        The first issue is a reduction in the combined containment 
    penetration and isolation valve leakage rate limit for Types B and C 
    tests which increases the margin to the maximum allowable leakage rate. 
    The maximum allowable leakage rate, which is referred to as La, is 
    specified in the facility's TSs. The acceptance criterion for Types B 
    and C leak rate tests is that the combined leakage rate shall be less 
    than 0.60 La. This constitutes a margin of 0.40 La (40 
    percent of La). Enclosure 3 to GL 91-04 states, in part, that in 
    order to justify an exemption to the Appendix J requirements and extend 
    Type C test intervals up to 30 months, licensees should either: (1) use 
    leak rate test data to demonstrate that the margin of 0.40 La will 
    not be reduced as a result of the test interval increase or (2) propose 
    an acceptance criterion limit of less than 0.60 La change. The 
    licensee has proposed an acceptance criterion limit of 0.50 La for 
    IP2. This constitutes a 25 percent increase in margin (40 percent to 50 
    percent). The staff has reviewed the proposed reduction in the combined 
    leakage rate limit to 0.50 La and finds that it is consistent with 
    the recommendations of Enclosure 3 to GL 91-04 and is, therefore, 
    acceptable.
        The second issue is the basis for concluding that containment 
    leakage would be maintained within acceptable limits with a Type C test 
    interval of up to 30 months. Eleven leak rate tests have been performed 
    at IP2 since the beginning of commercial operation. The first three 
    tests (1976, 1978, and 1979) did not meet the allowable leakage limit 
    due to excessive leakage from several valves which were subsequently 
    repaired and retested. The as-found results of the next eight tests 
    were below the allowable leakage limit. The licensee has concluded that 
    there has been a noticeable downward trend in the as-found valve 
    leakage over the last seven years. The as-found value for testing 
    during the 1993 refueling outage was 9.093 La. The NRC staff has 
    considered the test result information provided by the licensee and 
    concluded that there is reasonable assurance that containment leakage 
    rate would be maintained within acceptable limits with a Type C test 
    interval of up to 30 months.
        Therefore, the application of the regulation in the particular 
    circumstances is not necessary to achieve the underlying purpose of the 
    rule. Thus, these are special circumstances present which satisfy the 
    requirements of 10 CFR 50.12(a)(2)(ii).
    
    IV
    
        Accordingly, the Commission has determined, pursuant to 10 CFR 
    50.12, that (1) the exemption as described in Section III is authorized 
    by law, will not endanger life or property, and is otherwise in the 
    public interest and (2) special circumstances exist pursuant to 10 CFR 
    50.12(a)(2)(ii). Therefore, the Commission hereby grants the following 
    exemption:
        The Consolidated Edison Company of New York, Inc. is exempt from 
    the requirement of 10 CFR Part 50, Appendix J, Paragraph III.D.3, in 
    that the interval for Type C tests may be extended greater than 2 years 
    but in no case greater than 30 months for the Indian Point Nuclear 
    Generating Unit No. 2.
        Pursuant to 10 CFR 51.32, the Commission has determined that the 
    granting of this exemption will have no significant impact on the 
    quality of the human environment (59 FR 25130).
        This exemption is effective upon issuance.
    
        Dated at Rockville, Maryland, this 20th day of June 1994.
    
        For the Nuclear Regulatory Commission.
    Steven A. Varga,
    Director of Reactor Projects--I/II Office of Nuclear Reactor 
    Regulation.
    [FR Doc. 94-15752 Filed 6-28-94; 8:45 am]
    BILLING CODE 7590-01-M
    
    
    

Document Information

Published:
06/29/1994
Department:
Nuclear Regulatory Commission
Entry Type:
Uncategorized Document
Document Number:
94-15752
Pages:
0-0 (1 pages)
Docket Numbers:
Federal Register: June 29, 1994, Docket No. 50-247