Appendix B to Part 82 of Subpart B - Standard for Recover Equipment  


Latest version.
  • SAE J1989, Recommended Service Procedure for the Containment of R-12, as set forth under Appendix A, also applies to this Appendix B.

    SAE J2209, issued June, 1992.

    SAE Recommended Practice: CFC-12 (R-12)Extraction Equipment for Mobile Automotive Air-Conditioning Systems Foreword

    CFCs deplete the stratospheric ozone layer that protects the earth against harmful ultraviolet radiation. To reduce the emissions of CFCs, the 1990 Clean Air Act requires recycle of CFC-12 (R-12) used in mobile air-conditioning systems to eliminate system venting during service operations. SAE J1990 establishes equipment specifications for on-site recovery and reuse of CFCs in mobile air-conditioning systems. Establishing extraction equipment specifications for CFC-12 will provide service facilities with equipment to assure that venting of refrigerant will not occur.

    1. Scope

    The purpose of this document is to provide equipment specifications for CFC-12 (R-12) recovery for recycling on-site or for transport off-site to a refrigerant reclamation facility that will process it to ARI (Air-Conditioning and Refrigeration Institute) standard 700-93 as a minimum. It is not acceptable that the refrigerant removed from a mobile air-conditioning system, with this equipment, be directly returned to a mobile air-conditioning system.

    This information applies to equipment used to service automobiles, light trucks, and other vehicles with similar CFC-12 systems.

    2. References

    2. Applicable Documents—The following documents form a part of this specification to the extent specified herein.

    2.1.1SAE Publications—Available from SAE, 400 Commonwealth Drive, Warrendale, PA 15096-0001.

    SAE J639—Vehicle Service Coupling SAE J1990—Extraction and Recycle Equipment for Mobile Automotive Air-Conditioning Systems SAE J2196—Service Hose for Automotive Air-Conditioning

    2.1.2ARI Publications—Available from Air-Conditioning and Refrigeration Institute, 1501 Wilson Boulevard, Sixth Floor, Arlington, VA 22209.

    ARI 700-93—Specifications for Fluorocarbon Refrigerants

    2.1.3CGA Publications—Available from CGA, Crystal Gateway #1, Suite 501, 1235 Jefferson Davis Highway, Arlington, VA 22202.

    CGA S-1.1—Pressure Relief Device Standard Part 1—Cylinders for Compressed Gases

    2.1.4DOT Specifications—Available from the Superintendent of Documents, U.S. Government Printing Office, Washington, DC 20402.

    49 CFR, Section 173.304—Shippers—General Requirements for Shipments and Packagings

    2.1.5UL Publications—Available from Underwriters Laboratories, 333 Pfingsten Road, Northbrook, IL 60062-2096.

    UL 1769—Cylinder Valves 3. Specifications and General Description

    3.1The equipment must be able to extract CFC-12 from a mobile air-conditioning system.

    3.2The equipment discharge or transfer fitting shall be unique to prevent the unintentional use of extracted CFC-12 to be used for recharging auto air conditioners.

    3.3The equipment shall be suitable for use in an automotive service garage environment as defined in 6.8.

    3.4Equipment Certification—The equipment must be certified by Underwriters Laboratories or an equivalent certifying laboratory to meet this standard.

    3.5Label Requirements—The equipment shall have a label “Design Certified by (company name) to meet SAE J2209 for use with CFC-12. The refrigerant from this equipment must be processed to ARI 700-93 specifications before reuse in a mobile air-conditioning system.” The minimum letter size shall be bold type 3mm in height.

    4. Safety Requirements

    4.1The equipment must comply with applicable federal, state and local requirements on equipment related to the handling of R-12 material. Safety precautions or notices or labels related to the safe operation of the equipment shall also be prominently displayed on the equipment and should also state “CAUTION—SHOULD BE OPERATED BY CERTIFIED PERSONNEL.” The safety identification shall be located on the front near the controls.

    4.2The equipment must comply with applicable safety standards for electrical and mechanical requirements.

    5. Operating Instructions

    5.1The equipment manufacturer must provide operating instructions, necessary maintenance procedures and source information for replacement parts and repair.

    5.2The equipment must prominently display the manufacturer's name, address and any items that require maintenance or replacement that affect the proper operation of the equipment. Operation manuals must cover information for complete maintenance of the equipment to assure proper operation.

    6. Functional Description

    6.1The equipment must be capable of ensuring recovery of the CFC-12 from the system being serviced, by reducing the system pressure to a minimum of 102 mm of mercury below atmospheric. To prevent system delayed outgassing, the unit must have a device that assures that the refrigerant has been recovered from the air-conditioning system.

    6.1.1Testing laboratory certification of the equipment capability is required which shall process contaminated refrigerant samples at specific temperatures.

    6.2The equipment must be preconditioned with 13.6 kg of the standard contaminated CFC-12 at an ambient of 21°C before starting the test cycle. Sample amounts are not to exceed 1.13 kg with sample amounts to be repeated every 5 minutes. The sample method fixture defined in Figure 1 of appendix A shall be operated at 24°C. Contaminated CFC-12 samples shall be processed at ambient temperatures of 10 and 49°C.

    6.2.1Contaminated CFC-12 sample.

    6.2.2Standard contaminated CFC-12 refrigerant, 13.6 Kg sample size, shall consist of liquid CFC-12 with 100 ppm (by weight) moisture at 21°C and 45,000 ppm (by weight) mineral oil 525 suspension nominal and 770 ppm (by weight) of noncondensable gases (air).

    6.3Portable refillable containers used in conjunction with this equipment must meet applicable DOT standards.

    6.3.1The container color must be gray with yellow top to identify that it contains used CFC-12 refrigerant. It must be permanently marked on the outside surface in black print at least 20 mm high “DIRTY R-12—DO NOT USE, MUST BE REPROCESSED”.

    6.3.2The portable refillable container shall have a SAE 3/8 inch flare male thread connection as identified in SAE J639 CFC-12 High Pressure Charging Valve Figure 2.

    6.3.3During operation the equipment shall provide overfill protection to assure that the storage container liquid fill does not exceed 80% of the tank's rated volume at 21°C per DOT standard, CFR Title 49, section 173.304 and the American Society of Mechanical Engineers.

    6.4Additional Storage Tank Requirements.

    6.4.1The cylinder valve shall comply with the standard for cylinder valves, UL 1769.

    6.4.2The pressure relief device shall comply with the pressure relief device standard part 1, CGA pamphlet S-1.1.

    6.4.3The container assembly shall be marked to indicate the first retest date, which shall be 5 years after date of manufacture. The marking shall indicate that retest must be performed every subsequent five years. The marking shall be in letters at least 6 mm high.

    6.5All flexible hoses must meet SAE J2196 standard for service hoses.

    6.6Service hoses must have shutoff devices located within 30 cm of the connection point to the system being serviced to minimize introduction of noncondensable gases into the recovery equipment during connection and the release of the refrigerant during disconnection.

    6.7The equipment must be able to separate the lubricant from the recovered refrigerant and accurately indicate the amount removed from the system during processing in 30 ml units.

    6.7.1The purpose of indicating the amount of lubricant removed is to ensure that a proper amount is returned to the mobile air-conditioning system for compressor lubrication.

    6.7.2Refrigerant dissolved in this lubricant must be accounted for to prevent system lubricant overcharge of the mobile air-conditioning system.

    6.7.3Only new lubricant, as identified by the system manufacturer, should be replaced in the mobile air-conditioning system.

    6.7.4Removed lubricant from the system and/or the equipment shall be disposed of in accordance with applicable federal, state and local procedures and regulations.

    6.8The equipment must be capable of continuous operation in ambient temperatures of 10°C to 49°C and comply with 6.1.

    6.9The equipment should be compatible with leak detection material that may be present in the mobile air-conditioning system.

    7.0For test validation, the equipment is to be operated according to the manufacturer's instructions.